COMMERCE BUSINESS DAILY ISSUE OF JUNE 25,1996 PSA#1623Department of Veterans Affairs, Contract Service Center Building 5,
5000 W. National Ave, Milwaukee WI 53295 46 -- WATER SOFTENER SOL RFQ 69D-360-96 DUE 071696 POC Diane Ralston,
Contracting Officer, (414) 384-2000, ext. 6998 Furnish a sodium cycle,
cation exchange, vertical downflow pressure type, twin water softening
system, complete with piping services, electrical services, controls,
accessories, and auxiliary equipment for Project No. 585-96-114 at the
VA Medical Center, Iron Mountain, Michigan. Water to be treated is
reported to have a total hardness of CaCO3 of 12-20 grains and a pH of
7.75. At a minimum, each softener shall be capable of delivering water
at any rate up to 140gpm continuous flow with a a maximum pressure loss
of 15 PSIG and up to 190 gpm flow rate at a maximum pressure loss of 25
PSIG. Total loss of head through unit, and assembly, between the gages,
including softener, valves, piping, and other similar items shall not
exceed 15 PSIG. Regeneration shall be accomplished within a period of
120 minutes and occur not more than once per day. Issue date is on or
about June 26, 1996. Award is subject to the availability of funds.
Requests for solicitation must be submitted in writing. No telephone
requests will be accepted. Requests may be faxed to (414) 382-5383,
Attn: Patti Bigelow. (0173) Loren Data Corp. http://www.ld.com (SYN# 0240 19960624\46-0001.SOL)
46 - Water Purification and Sewage Treatment Equipment Index Page
|
|