|
COMMERCE BUSINESS DAILY ISSUE OF JUNE 27,1996 PSA#1625US Department of Commerce/National Oceanic and Atmospheric
Administration (NOAA), PGAS, Procurement Operations Division, 1325 East
West Highway, Station 4301, Silver Spring, MD 20910-3283 N -- INTEGRATION AND INSTALLATION OF TRANSITION POWER MAINTENANCE
SHELTERS SOL 52-DGNW-7-90004 DUE 081596 POC Robert R. Curtis, Contract
Specialist, or John O. Thompson, Contracting Officer, (301) 713-0823
The Government intends to procure approximately 130 Transition Power
Maintenance Shelters (TPMS), over a five year period under an
indefinite quantity contract in support of National Weather Service
(NWS)/Tri-Agency Doppler Weather Surveillance Radar -1988 (WSR-88D)
systems. Each TPMS will be required to provide uninterrupted
conditioned power to its WSR-88D system during cutover between
commercial power and back-up generator power. The TPMS is a stand-alone
facility consisting of the following: a precast concrete shelter, a
Transition Power Source (TPS), an environmental control unit, an
electric toilet unit, storage cabinets, and a workbench. The TPMS will
provide limited storage and working space. A central component to be
provided by the contractor is the high daily duty-cycle, long
ride-through TPS that uses motor-driven technology compatible with the
existing WSR-88D standby diesel generator. In addition to the concern
for compatibility between the TPS and the existing generator, the NWS
is concerned that necessary environmental conditions for energy
storage batteries cannot be ensured and that routine servicing at
remote locations cannot be guaranteed during the winter season.
Notwithstanding these concerns, offerors are advised that all types of
technologies will be considered for contract award. The Government
intends to conduct two-step pre-award testing on the TPS, first, at the
contractor's facility, and second, at the Norman, Oklahoma WSR-88D
site. The WSR-88D radar system has a complex power load not commonly
found in industry. The WSR-88D's existing power source is a commercial
utility grade 75 KVA, 5.75% per unit impedance transformer supplying
208 Volt, 3-phase, 4-wire, 60 Hertz input power with backup power
typically furnished by an emergency standby diesel generator, Kohler
Model Number 80ROZJ81, rated for 80 KVA. The system load consists of
WSR-88D support electronics requiring UPS protection, including a
Westinghouse 750 KW peak power pulsed klystron transmitter, two 90 Amp
DC servo drive motors moving an 8-ton antenna, and two 5-ton air
conditioners. The air conditioners do not require TPS protection. The
TPS must supply at least 35 KVA at 0.8 power factor for a continuous
load of 208 +/- 5% Volts, 3-phase, 4-wire, 60 +/-5% hertz at an outdoor
temperature of -40 degrees C to +49 degrees C, without derating, from
mean sea level (MSL) to 3300 meters above MSL. Ride-through, the
transition between commercial and back-up power, at continuous load,
must be at least 12 seconds, for up to 40 transition events per day,
with no degradation of voltage or frequency. The TPS must be capable of
supplying overload currents of at least 600% of the continuous load for
16.7 milliseconds and 150% of the continuous load for 30 seconds,
without the use of bypass mode. The voltage dip, during the transient
period, caused by the application of a 0.4 power factor lagging load
drawing 200% of the TPS's rated current, shall not exceed 5% of the
TPS's rated voltage. The output voltage waveforms shall not exceed 3%
THD at continuous load, with 50% of the load being nonlinear and no
single harmonic more than 1% of fundamental frequency, from 60 hertz to
1 megahertz. The output direct-axis subtransient reactance must be 0.2
per unit, maximum and the direct-axis transient short-circuit ti
(0177) Loren Data Corp. http://www.ld.com (SYN# 0055 19960626\N-0001.SOL)
N - Installation of Equipment Index Page
|
|