COMMERCE BUSINESS DAILY ISSUE OF AUGUST 19,1996 PSA#1661USACML&MPCEN&FM, Directorate of Contracting, ATZN-DC, BLDG 241C, FORT
MCCLELLAN, AL 36205-5000 41 -- WATER COOLED LIQUID CHILLER - BUILDING 503, FORT MCCLELLAN, AL
SOL DABT02-96-B-0013 DUE 081696 POC Contract Specialist Jeffery S.
Tarvin (205) 848-5219 (Site Code DABT02) Answers to questions received
on solicitation: Question 1: Confirm selection conditions 900GPM from
95 to 85 at XX wet bulb temp. Answer 1: Design for 75 degrees wet bulb
outdoor design. Question 2: Confirm the tower is outdoors. Answer 1:
Cooling tower is outdoors. Question 3: Is it O.K. to use a propeller
fan cooling tower? Answer 3: It is O.K. to use a propeller fan cooling
tower. Question 4: Would you specify a maximum motor size? Answer 4:
No. The Government will not specify a maximum motor size. Question 5:
How do you expect to control capacity? Want to add a 2-speed motor?
Control Panel? Answer 5: Capacity control will be responsibility of
equipment installer; not required by supplier. The Government is not
specifying a 2-speed motor control panel but is not restricting vendor
in what is bid/supplies as long as it meets the Scope of Work.
Question 6: Do you need an internal ladder, platform or walkway? Answer
6: No interior ladder/platform/walkway is needed. (0228) Loren Data Corp. http://www.ld.com (SYN# 0190 19960816\41-0001.SOL)