COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 11,1996 PSA#1677National Institute of Standards & Technology, Acquisition & Assistance
Division, Building 301, Room B117, Gaithersburg, MD S -- RADIOACTIVE WASTE DISPOSAL SOL 53SBNB6C9276 DUE 091696 POC Linda
Shariati This is a modification to the Commerce Business Daily (CBD)
announcement which was published on August 12, 1996 (page 15) for
radioactive waste disposal and the modification which was published on
August 28, 1996 (page 9). The original CBD was published as a combined
synopsis/solicitation for commercial items prepared in accordance with
the format in Subpart 12.6. The solicitation number is 53SBNB6C9276.
The modification published on August 28, 1996 extended the date that
responses are due. This modification is to identify questions which
were received regarding this requirement and provide all interested
parties with the questions and the responses. Question 1: For each
individual article or disposal package, the following minimum
information is desired - Present packaging type, methodology and
specification. Answer 1: All packages shall be strong, tight
containers, i.e.: Contractor's supplied Sealand container or
equivalent. Shipments will be LSA, exclusive use. Question 2: For each
individual article or disposal package, the following minimum
information is desired - Individual radio-isotopes and activities per
isotope (curie or SI units). Answer 2: Ferrous Metals: less than
0.1mCi, Co60. Non-ferrous Metals: less than 1 mCi, Co60, H3. Filters:
less than 1 mCi, Co60, H3, Zn65, Ag110m. Asbestos: less than 0.1
microCi, Co60. Aqueous Liquids: 10 mCi, H3, Zn65, Ag110m, Co60. Oil:
0.1 mCi, H3, Zn65, Ag110m. Bead Resin: 10mCi, H3, Zn65, Ag110m.
Question 3: For each individual article or disposal package, the
following minimum information is desired - Weights, dimensions, special
handling requirements for non-standard packages. Answer 3: Ferrous
metals: pipe sections less than 1'D and less than 6'L; others are less
than 3' x 4' x 5' overall and are hollow shells, average weight of 200
pounds per item. Non-Ferrous: pipe sections or small parts, each less
than 80 pounds. Filters, Asbestos, Aqueous Liquids, Oil or Bead Resins
are separately packaged in 55 gallon drums, all are greater than 200
pounds each. Question 4: For each individual article or disposal
package, the following minimum information is desired - Dose Rates, on
contact and at one meter (mrem/hr or equivalent SI units). Answer 4:
Ferrous Metals: Average 0.2 mrem/hr; all less than 25. Non-ferrous
Metals: Average less than 10 mrem/hr. contact. Filters: Average less
than 30 mrem/hr. contact. Asbestos: background. Aqueous Liquids:
Average less than 10 mrem/hr. contact. Oil: less than 0.1 mrem/hr. Bead
Resin: less than 200 mrem/hr. Question 5: For each individual article
or disposal package, the following minimum information is desired -
Contamination levels (dpm/100 cm square) of packages and inner articles
with high levels of contamination. Answer 5: The external, accessible
surfaces of all items (bags, drums, pipes, etc.) is less than 300
dpm/100 cm sq. beta (no alpha). There are no inner articles with high
levels of contamination. Question 6: For each individual article or
disposal package, the following minimum information is desired -
Physical description of contents (i.e. Lab Trash - paper, plastic,
etc., Sealed or check sources, neutron or radiography devices, soil,
debris, luminous dials, smoke detectors ..). Answer 6: As described in
the combined synopsis/solicitation published in the CBD August 12,
1996. Question 7: For each individual article or disposal package, the
following minimum information is desired - Additional description of
potential hazards/characteristics (EPA listed/characteristic, lead,
liquids, infectious, etiologic, biological, etc.) Answer 7: There are
no EPA listed/characteristic materials, lead, infectious, etiologic, of
biological material in any of the shipments. Question 8: For each
individual article or disposal package, the following minimum
information is desired - Waste Classification and Stability required
per 10 CFR 61, Neuclear Regulatory Commission's Branch Technical
Positions and applicable disposal site licenses and acceptance
criteria. Answer 8: All are well within LLRW class A criteria for
radioactivity. Liquids, e.i. oil and aqueous liquids must be stabilized
or alternatively may be incinerated; they conform to incinerable
criteria. Question 9: CLIN 0001 and CLIN 0002, Metal Types and sizes
(dimensions W x L x T (guage), as applicable) and expected
contamination - loose/fixed and isotope/activities. Answer 9: CLIN 0001
and CLIN 0002: Metal types are Carbon Steel & Stainless Steel, with
max. thickness of 1/2 inch. See General Information, re: Ferrous
Metals. Question 10: CLIN 0003, Size, construction, media filtered and
condition (i.e. One each 24'' x 24'' x 12'' wood and paper HEPA air
filter with 48 microcuries (uCi) of Cesium-137 or One each, drained,
Cuno oil filter, model 456, for Mobile MultiLube (MSDS attached), 3''d
x 6''l, Aluminum and paper construction, 15 uCi of Co-60, 28 uCi of
Co-59, 10 uCi C0-58). Answer 10: CLIN 0003, Filters are dewatered, spun
cotton fiber cartridges, 12''L x 3''D, or cloth bags 2'L x 6''D.
Filters were used for aqueous systems only. All are consolidated in
drums, and are to be compacted. Separate isotopics will be provided to
contractor. See General Information, re: Filters. Question 11: CLIN
0005 and CLIN 0006, waste profile data and MSDS for liquids/oils.
Answer 11: CLIN 0005 and CLIN 0006, Liquids/Oils will be certified by
NIST as non-EPA/RCRA hazardous material. MSDS for Aqueous Liquids will
be provided; they are non-toxic, inert, non-hazardous. Aqueous Liquids
and Oils meet incinerable criteria. Question 12: CLIN 0007,
Radioanalytical data required by the Barnwell Waste Management Facility
(License/Acceptance Criteria) and resin type (Manufacturers data/MSDS)
and use (reactor coolant, shield pool, etc.). Answer 12: CLIN 0007,
separate isotopics will be provided for Bead Resins, see General
Information. The resin beads are IRN-150, H-OH type, used in shield
pool or Thermal Shield Systems (aqueous, non-reactor system). It is
non-hazardous, MSDS will be provided. This modification extends the
date responses are due. Responses are due by 3:00 pm local time on
September 16, 1996. Offers or modifications to offers received at the
address above after the exact time specified for receipt of offers will
not be considered. Requests for a copy of a solicitation will be
disregarded since the original CBD and this modification constitute the
solicitation. For information contact Linda Shariati, Contract
Specialist. Her telephone number is (301) 975-5053. (0253) Loren Data Corp. http://www.ld.com (SYN# 0067 19960910\S-0001.SOL)