300, Pearl Harbor, HI 96860-5300 61 -- DIESEL ENGINE GENERATOR/RECTIFIER SETS SOL N00604-96-R-0061 DUE
120396 POC P. Mesiona, (808) 474-2397 Ext. 219, Contract Specialist,
R. Kay, Contracting Officer Diesel Engine Generator/Rectifier Sets.
Generator/Rectifier output must be capable of providing 325KW Direct
current, and 15KW auxiliary (hotel) 120V single phase A/C. System shall
be capable of producing its specified DC and AC auxiliary output
continuously and simultaneously and each (AC/DC) shall be capable of
sustaining intermittent overloads of 19% for 120 minutes, and 50% for
one (1) minute. The generators shall be self exciting, brushless and
shall conform to NEMA MG-1. Maximum voltage rating for the main
generator shall be 480VAC. 6 each with scheduled delivery dates from
March 1997 through November 1999. Inspection, testing, and acceptance
shall be performed at the contractor's facility, and witnessed by
Government Representative(s). Sets shll be capable of fitting through
crane openings of 5' width x 17' length for two (2) sets, 5' width x
19'6'' length for two (2) sets, and 7' width x 20' length for two (2)
sets. Drawings will be provided with the solicitation. Delivery to be
F.O.B. destination Pearl Harbor Naval Shipyard, Hawaii within specified
delivery schedule. All responsible sources may submit proposal which
shall be considered by the agency. Please fax your request for the
solicitation package to (808) 471-5750 or (808)474-8885 and include
with your request, your phone and fax numbers. As an alternative, you
can submit a written request to the Contracting Office identified
above. (0292) Loren Data Corp. http://www.ld.com (SYN# 0210 19961021\61-0001.SOL)