Cable, medium voltage shall be single conductor, ethylene propylene
rubber (EPR) insulated, shielded power cable shall be at 15kv, 133
percent insulation level. The cable shall be capable of operating
continuously in both wet and dry locations at 90 degree C for normal
operation, 130 degree C under emergency operating conditions and 250
degree C under short circuit conditions. The conductor shield,
insulation, and the insulation shield shall be applied continuously in
the same pass by an in-line triple extrusion process. The cable shall
be insulated, jacketed, and tested in accordance with AEIC CS6, in the
same plant by the same manufacturer. Certified AEIC qualification data
shall be required prior to order placement. Cable ends must be sealed.
Conductor shall be class B stranded annealed copper per part 2 of AEIC
S-68-516. Conductor Shield: Shall be extruded black, semi- conducting
thermosetting compound thermally and chemically compatible with the
conductor and the insulation, applied over the conductor. Conductor
shield shall be uniformly and firmly bonded to the overlying insulation
and be free stripping from the conductor. The thickness of the
conductor shield shall conform to AEIC CS6. Insulation: Shall be EPR
conforming to AEIC CS6 and shall have a minimum average thickness of
220 mils. The ethylene content of the EPR compound shall not exceed 72
percent by weight. Insulation Shield: Shall be extruded black,
semi-conducting thermosetting compound thermally and chemically
compatible with the insulation and the copper tape shield, applied
directly over the insulation. The insulation shield shall be free
stripping, leaving no conductor particles or other residual on the
insulation surface. The thickness of the insulation shield shall
conform to AEIC CS6. Copper tape shield shall have a thickness of 5
mils, helicaly applied over the insulation shield with a minimum of
12.5 percent overlap. Jacket shall be PVC with a minimum thickness of
80 mils. Written solicitations will not be forwarded. Oral/FAX quotes