COMMERCE BUSINESS DAILY ISSUE OF DECEMBER 10,1996 PSA#1738Contracting Officer (90C4), DVA Medical Center, Salem, Virginia
24153-5483 43 -- PROVIDE MEDICAL AIR COMPRESSORS SOL 658-11-97 DUE 010897 POC
Priscilla Zaebst (540) 983-1050 This is a combined
synopsis/solicitation for commercial items prepared in accordance with
the format in Subpart 12.6, as supplemented with additional
information included in this notice. This announcement constitutes a
formal Request for Quotations (RFQ #658-11-97), and a written
solicitation will NOT be issued. The solicitation document and
incorporated clauses and provisions are those in effect through Federal
Acquisition Circular 90-42. The Standard Industrial Classification
(SIC) code for this acquisition is 3563. Contractor shall provide
medical air compressors which will deliver medical compressed air for
patient use only with all components factory packaged
(prewired/prepiped) on a steel base. The quality of air shall be equal
to or better than the quality of the intake air, without the use of
purification equipment. Multiplex shall be such that the design load is
provided with the largest single unit out of service; design piping,
accessories and controls to withstand up to 150 PSIG. A duplexed,
positive displacement, two-stage rotary screw air compressor capable of
delivering 100% oil-free air shall be supplied. The assembly shall be
fully packaged including air compressors, main drive motors, oil
cooler, intercooler/aftercooler (air cooled, not water cooled),
regulation/control systems, and all mounted on a common base frame. All
coolers shall be cross-flow, aluminum construction to achieve maximum
cooling efficiency and shall be rated 250 PSIG at 450 degrees F.
operating conditions. The capacity shall be expressed in terms of free
air delivery cubic feet per minute measured at the discharge pressure
and related back to inlet conditions, and shall be rated at 150 SCFM
at 100 PSIG discharge pressure and be suitable for use on 480 volts, 3
phase, 60 Hz. The capacity and specific power shall be guaranteed per
modified ASME PTC 9. Tolerances shall be within +/- 4% for free air
delivery and +/- 5% for specific power consumption and shall meet
Medical Air Standards as required in NFPA99 -- 1996 Edition. All
gaskets shall be asbestos-free. The motor shall be of standard
manufacture; NEMA Design B with Class B temperature rise and Class F
insulation; be totally enclosed fan-cooled (TEFC) design; and be
provided with automatic, fully enclosed, magnetic starter of type
specified by Contractor's design requirements. Control panel shall be
housed in an NEMA ICS-6, Type 12, listed, dustproof enclosure; prewired
to include all specified electrical, electronic and electropneumatic
devices. Wiring diagrams and operating descriptions shall be included
in the cabinet. The control system shall be controlled by a
Programmable Logic Controller (PLC) and provide: (1) circuit breaker
for each control and motor circuit; (2) hand-off automatic selector
switch for each compressor; (3) magnetic motor starter for each
compressor; (4) panel with external visual lights (red for
running/green for safe); and (5) audible (horn/ buzzer) signals which
shall include compressor in operation (visual only). The compressor
package shallhave appropriate gauges and indicators, and all necessary
automatic shut-off switches as required by NFPA99 -- 1996 Edition. The
receiver tank shall be welded steel, galvanized, and in compliance with
ASME Section VIII, 125 PSIG working pressure stamped and certified. The
receiver tank shall be equipped with safety relief valve set at 120
PSIG, motorized automatic drain system, sight glass, pressure gauge,
and be provided with a 200 gal capacity to ensure practical on/off
operation of compressors. The compressor shall be designed so that the
installation is simplified and no special foundations are required
other than those necessary to support the weight of the unit. The unit
shall be delivered with all internal compressed air, water piping, and
wiring complete with a 2-source hook-up for utilities, one for
discharge and one for incoming electrical service, and shall be
installed utilizing existing medical air dryers and filtration system.
Descriptive literature on the medical air compressors shall be
submitted with offer. Equipment will be delivered within forty-five
(45) calendar days after contract award along with 2 user's/operator's
manuals and 2 service manuals with schematics and parts list at NO
COST to the Government. The provision at FAR 52.212-1 Instructions to
Offerors - -- Commercial Items, applies to this solicitation. All
offerors are to include with their offer, a completed copy of provision
52.212-3 Offeror Representations and Certifications -- Commercial Items
(a copy of this provision may be obtained by faxed request to
540-983-1065). The following FAR clauses apply to this acquisition:
52-212-4 Contract Terms and Conditions -- Commercial Items; 52-212.5
Contract Terms and Conditions Required to Implement Statutes or
Executive Orders -- Commercial Items; as well as the following
additional FAR clauses also cited in Clause 52.212-5: 52.222-26 Equal
Opportunity; 52.222-35 Affirmative Action for Special Disabled and
Vietnam Era Veterans; 52.222-36 Affirmative Action for the Handicapped
Workers; 52-222-37 Employment Reports on Special Disabled Veterans and
Veterans of the Vietnam Era; 52.222-3 Buy American Act -- Supplies; and
52.222-18 European Union Sanctions for End Products. The following VAAR
provision is added by addendum: 852.219-70 Veteran-Owned Small
Business. The period of acceptance is 30 calendar days. The offers are
due on January 3, 1997, 2:00 PM, EST. The offer must be signed by an
official authorized to bind the offeror's organization. All offers must
be sent to: Contracting Officer (90C4), VA Medical Center, Bldg. 74,
Room 212, 1970 Roanoke Blvd., Salem, VA 24153. Faxed bids WILL NOT be
accepted. (0341) Loren Data Corp. http://www.ld.com (SYN# 0184 19961210\43-0003.SOL)