COMMERCE BUSINESS DAILY ISSUE OF JANUARY 22,1997 PSA#1766DOC; Mountain Administrative Support Center; Acquisition Management
Division; 325 Broadway MC3; Boulder, CO 59 -- UPGRADE ENGINE GENERATOR CONTROL SOL NB847-700083 POC Doris
Turner, Purchasing Agent, (303) 497-3872 or Fax (303) 497-3163 E-MAIL:
NOAA; MASC Acquisition Management, Joyce.J.Mills@noaa.gov. The
National Institute of Standards and Technology (NIST) requires an
upgrade for the existing engine generator control and transfer switch
system purchased from Electric Equipment & Engineering Co. (EECO). The
upgrade must function with the existing EECO engine generator control
and transfer switch system and must be compatible with all EECO
controls and engineering. Specifications for the 3 phase, 3 wire
automatic transfer breaker system follow: a) Individual motor operators
will be provided to allow open circuit time as the transfer breaker
system is operated from one source to the other, b) Normal source
breaker will be equipped with a 1000 ampere integral overcurrent
device, c) Engine source breaker will not be equipped with an integral
overcurrent device because the 1000 ampere breaker is not available
with an overcurrent device small enough to protect the circuit from the
480 volt side of the new generator transformer, d) Three phase
adjustable overcurrent relay with associated current transformers all
arranged to trip the generator circuit breaker in case of a short
circuit or overload condition to allow the generator system to be
uprated at a later date with only minor modifications, e) Breakers will
include plug-in features to allow for ease of maintenance or
replacement, f) Transfer breaker system will be arranged for service
entrance duty, g) Transfer breaker system will be arranged to start the
generator by providing the proper interface to the existing engine
control equipment, h) Transfer breaker system will be rated at 30,000
amperes interrupting capacity, i) Necessary bus systems to allow
termination of the line, load, and generator cables will be provided,
j) Normal source voltmeter and switch, k) Essential bus ammeter and
switch, l) Circuit breaker position indicating lamps, m) Normal source
breaker trip button, n) Necessary control buttons and selector
switches to allow manual operation of the transfer system, o) Power
failure test selector, p) Necessary startup engineering servicesshall
be provided once the equipment has been installed. Ground fault relay
system arranged to trip either transfer breaker element if a ground
fault condition exists beyond the transfer breaker system. This relay
is intended to limit the arcing fault damage which can occur on 480
volt systems which experience low amperage faults. Sensitive negative
sequence voltage relay to detect single phasing conditions. Essential
wattmeter connected to monitor the power through the transfer system.
Change the normal source transfer breaker motor operator to a DC
operated device to allow the normal source breaker to be opened on a
low voltage or single phase condition as soon as the condition occurs
rather than waiting until the standby generator starts and reaches
normal voltage. A 600 ampere manually operated circuit breaker which
would be connected to the normal power source ahead of the transfer
breaker system. This circuit breaker would be used to supply 480 volts
to the 408/208 volt transformer for the existing building loads.
Provide ground fault protection for the 600 ampere manually operated
circuit breaker. Interested sources proposing to supply an equivalent
system must submit a written qualification statement clearly
establishing capability to meet the above requirements within 15 days
from the date of this synopsis. In the absence of other qualified
sources, it is the intent of the Government to negotiate a sole source
contract under the authority of 41 U.S.C. 253(c)(1) with Electric
Equipment & Engineering Co., 40 West 49th Avenue, Denver, CO 80216 as
this source is considered to be the only responsible source and no
other items will satisfy agency requirements. No formal RFQ is
available. (0017) Loren Data Corp. http://www.ld.com (SYN# 0225 19970122\59-0005.SOL)
59 - Electrical and Electronic Equipment Components Index Page
|
|