COMMERCE BUSINESS DAILY ISSUE OF JANUARY 23,1997 PSA#1767Department of the Navy, Navy Public Works Center, Bldg. 1A, Material
Dept., Code 840, 2703 Sheridan Road, Suite 120, Great Lakes, IL
60088-5600 61 -- ELECTRICAL SWITCHBOARD SOL N65113-97-Q-0062 DUE 021497 POC Midge
Rosendahl, 847-4233. Electrical Switchboard, Power Style QED
Switchboard: Designed and tested in accordance with: UL 891/National
Electric Code/NEMA PB-2, 2000 AMP 208Y/120 VAC 3 Phase 4 Wire 60 Hertz,
Suitable for use as Service Entrance Equipment, Short Circuit Current
Rating: 42,000 AMP RMS Symetrical, Accessibility: Front, Incoming: Top
2000 AMP Busway Fed, Bussing: plated Copper Bus/UL891 Heat Rise.
(0021) Loren Data Corp. http://www.ld.com (SYN# 0248 19970123\61-0015.SOL)
61 - Electric Wire and Power and Distribution Equipment Index Page
|
|