COMMERCE BUSINESS DAILY ISSUE OF MARCH 17,1997 PSA#180345CONS, 1201 Minuteman St, MS 7200, Patrick AFB, FL 32925-3237 59 -- FOUR WAY VACUUM SWITCHES SOL F08650-97-R-0410 DUE 050197 POC Ms
Thyra Hayes, Contract Specialist (407) 494-9513/Jimmy McDaniel,
Contracting Officer (407) 494-7227 The government has a requirement for
a quantity of three 4-way switches/SF6 and one 4-way vacuum switch with
AFIS. The three 4-way vacuum switches/SF6 are to include: Three
fiberglass equipment enclosures, light brown, 304 SS hardware, penta
bolt locking system; must provide protection for vacuum switch from
elements and easy access for repair or maintenance. Three vacuum
loadbreak/fault interrupter switches, SF6 insulation, 15kV, 95 BIL, 200
amp, 4-way, 34kV AC withstand, 3-phase, group operated, 60 hertz,
deadfront, 12 kA, monetary and fault close (SYM) or 20 kA (ASYM),
hermetically sealed 304L SS tank pressure gauge, in conformance with
ANSI C37.60 and C37.72, one source circuit to be 200A continuous and
loadbreak/remote operator, three tap circuits to be 200 amp continuous
and 200kA (SYM) interrupting. Three motor operated control local and
remote operation, totally enclosed induction type motor, duff-norton
type mini-pac. Nine electronic controls for fault interrupting,
overcurrent protection, powered by internal current transformers, trip
settings. Three control power transformer deadfront, 7970V to 120V,
95kV Bil, with internal primary fuse. Three control cabinets include:
3-mode selector switch, local-off-remote six open/close pushbuttons,
six open/close indicator lights, one control power on/off switch, one
backpanel with fuse block, terminal blocks, wiring, etc., one
fiberglass cabinet, 12"Wx14"Hx8"D. The switches will be used on a high
voltage 13.8kV distribution system. The one 4-way vacuum switch with
AFIS is to include: 15kV, 95kV Bil, 3-phase 4-way vacpac with automatic
fault interrupting system. Vacpac is vacuum interrupting switch with
SF6 insulation in a stainless steel tank rated for 12kA (SYM) fault
interrupting and 20kA (ASYM) momentary and fault close; two source ways
feature manual hookstick operation with 6-200A bushing wells; two tap
ways feature automatic fault interruption with electrical trip and
manual reset with 6-200A bushing wells; automatic fault interrupting
system features Vacop III stored energy spring operators and 3-phase
overcurrent protection. Vacpac and controls are housed in a fiberglass
enclosure measuring 53"Wx72"Dx60"H. AFIS system includes: one NEMA
4-control cabinet; two Vacop III stored energy spring operators; two
Vacop III capacitor trip panels; six current transformers rate D200:5;
two potential transformers for control power from either source way.
This acquisition is 100% set aside for small businesses. The applicable
SIC code and size standard are 3625/750 employees. Solicitation issue
date of 1 Apr 97 and proposal due date of 1 May 97 are tentative.
Requests for RFP must be faxed to (407) 494-2983 or mailed to 45
CONS/LGCSAL, Attn: T Hayes, 1201 Minuteman St M/S 7200, Patrick AFB FL
32925-3237. Phone calls will not be accepted. All responsible small
business sources may submit an offer which will be considered by the
45th Space Wing. (0072) Loren Data Corp. http://www.ld.com (SYN# 0370 19970317\59-0018.SOL)