COMMERCE BUSINESS DAILY ISSUE OF MAY 2,1997 PSA#18373 Contracting Squadron, 6920 12th Street, Elmendorf AFB, Alaska
99506-2570 Z -- INSPECTION, TESTING, PREVENTATIVE MAINTENANCE AND REPAIR
UNDERGROUND STORAGE TANKS SOL F56601-97-QM310 DUE 051397 POC Point of
Contact: TSGT TRAMP, CONTRACTING OFFICER; LORI L. JOHNSTON, PURCHASING
AGENT, (907)552-7573. WEB: none, none. E-MAIL: 3rd Contracting
Squadron Elmendorf AFB AK, perryt@elmmail.topcover.af.mil. The
Contractor shall perform monthly visits to inspect and test UST, leak
detection, and associated alarm systems to include sensors, indicators,
printers, and computer systems. Perform minor maintenance on UST
systems to include resetting alarms and detection systems, maintaining
and repairing control panels, and bringing UST systems into good
working order. Provide all transportation and equipment to perform this
work. Provide a scope and cost estimate for any large scales repairs
for Elmendorf AFB action. All work shall be in accordance with all
applicable base, Air Force, State, and Federal codes and regulations.
Perform impressed current cathodic protection system performance test
every 60 days. (Building 41-659, 2 tanks only). Perform annual cathodic
system performance tests for all sacrificial anode cathodic protection
systems on UST's. Perform minor maintenance and determine scope of any
large repairs for Elmendorf AFB action. Respond within 24 hours, or the
next duty day, to UST problems as directed. Perform inspection of
entire system and determine cause of alarm or other adverse indicator.
Submit documentation of inspection, testing, maintenance, and minor
repairs to the contracting officer or designated representative. Each
tank shall be documented on a separate piece of paper and delivered
within 48 hours. All work on this project shall be limited to Monday
through Friday inclusive, between 0715 hours through 1715 hours,
excluding federal holidays, unless approved otherwise by the
contracting officer or designated representative. The contractor shall
provide emergency service response within 4 hours for the duration f
this contract. The contractor shall notify the contracting officer or
designated representative immediately if any alarm or system fails to
reset or troubleshooting procedures prove to be inclusive. The
contractor shall provide proof of technician certification on systems
listed in Attachment 1 before any work on this contract begins. (0119) Loren Data Corp. http://www.ld.com (SYN# 0147 19970502\Z-0012.SOL)
Z - Maintenance, Repair or Alteration of Real Property Index Page
|
|