COMMERCE BUSINESS DAILY ISSUE OF MAY 20,1997 PSA#1849Navy Public Works Center, 310 John Tower Road, Pensacola, FL
32508-5303 J -- RETROFIT KIT FOR TRANE CHILLER SOL N65114-97-Q-F001053197 POC
Georgia M. Fils, Purchasing Agent, (904)452-5086 WEB: NONE, NONE.
E-MAIL: Navy Public Works Center, PWCA.P08 (8519). Retrofit kit for
Trane Chiller Model #CVHE-032-AL-2JB237ECEZA11DEEA0000000041Z1D0 300
ton chiller, kit shall convert unit from R-11 to R-123 refrigerant and
comply with current CFC, EPA and RCRA regulations and guidelines.
Conversion kit shall be equal to Trane P/N PC196-032-E and include the
following: All engineering services, impeller modifications, orfice
plates, gaskets, o-rings, oil regulating system, hermetic oil pump,
factory engineered named plate, hermetic drive motor, prevac leak
prevention system and rupture guard. Refrigerant 123 monitoring system
equal to Trane Model RMWD shall include (1) L.C.D. human interface,
back lit, clear language display, (2) NEMA 4 enclosures, (3) 3-levels
of alarming, each with SPDT binary contact closures for signaling
alarms remotely, (4) four-20MA and 0-10 VDC analog outputs representing
a 0-100 or 0-1000 PPM range, (5) service diagnostics, (6) integrate
directly with Trane UCP2 control system, (7) sample particle filter(s)
and power fuses and jumpers (8) wall mounting brackets and (9)
installation, operation and maintenance literature. Oil filter and
initial oil charge and freight prepaid to job site. The Kit shall be
same or equal to Trane P/N PC196-032-E. Inquiries to be sent via FAX
(904) 452-5088 to the POC indicated above. Quotes will be accepted
between 0700 and 1400 CST. Quotes to be submitted no later than 1400,
97MAY31. (0136) Loren Data Corp. http://www.ld.com (SYN# 0041 19970520\J-0006.SOL)