Loren Data Corp.

'

 
 

COMMERCE BUSINESS DAILY ISSUE OF JUNE 3,1997 PSA#1858

Panama Canal Commission, Purchasing and Contracts Brach, Logistical Support Division, Unit 2300, APO Miami, FL 34011-5000

61 -- POWER TRANSFORMER SOL CNC-095285-MQ-29 DUE 080497 POC Carmen M. Lee, Contract Specialist, (507) 272-3140, Henry Stec, Contracting Officer, (507) 272-4075 Fabrication and delivery of a regulating and Phase-Shifting Power Transformer Oil-filled, Outdoor, Three phase, three Winding, 60Hz, High Voltage Winding 115000 GrdY/66395 volts with +/- 10% (33 positions) On-Load Tap Changer, Medium Voltage Winding 43800 GrdY/25290 Volts with +/- 15 degrees ( 19 positions) On-Load Tap Changer, Low Voltage Tertiary Winding 11000 Volts Delta Connected of KVA rating to be determined by the manufacturer, 40000/53333/66667 continuous KVA rating for high and medium voltage windings based on not exceeding 65 degrees C average winding temperature rise, and in accordance with the specifications. Quantity: One each. Delivery within 300 calendar days after notice of award, C.I.F destination Miraflores, Republic of Panama. When requesting solicitation, state name, address and solicitation number. Requests will be accepted by facsimile at 011-507-272-7661. All responsible sources may submit an offer which, if timely received, shall be considered by the Commission. " See note 12 and 26." (0150)

Loren Data Corp. http://www.ld.com (SYN# 0305 19970603\61-0005.SOL)


61 - Electric Wire and Power and Distribution Equipment Index Page