COMMERCE BUSINESS DAILY ISSUE OF JULY 2,1997 PSA#1879Officer in Charge of Construction, P. O. Box 209 Oceanside, CA
92049-0209 E -- PURCHASE OF RELOCATABLE FACILITIES FOR THE FLEET HOSPITAL
OPERATIONS AND TRAINING COMMAND AT THE MARINE CORPS BASE, CAMP
PENDLETON, CALIFORNIA SOL N68711-97-Q-6357 DUE 072197 POC Al Munoz,
Contract Specialist (760) 725-3525/Contracting Officer, E. Charette
E-MAIL: Officer in Charge of Construction, Camp Pendleton, California,
amunoz@efdswest.navfac.navy.mil. This is a combined
synopsis/solicitation for commercial items prepared in accordance with
the format in Federal Acquisition Regulation (FAR) Subpart 12.6, as
supplemented with additional information included in this notice. This
announcement constitutes the only solicitation; quotations are being
requested and a written solicitation will not be issued. This
solicitation is being issued as a Request for Quotations (RFQ). The
solicitation documentation and incorporated provisions and clauses are
those in effect through Federal Acquisition Circular 90-46. This
solicitation is 100% set aside for small business concerns. The
Standard Industrial Code (SIC) is 2451. The size standard is 500
employees. The work will include but is not limited to all labor,
supervision, tools, materials, equipment, transportation and facilities
necessary to construct, deliver, set-up, level and tie-down the
relocatable facilities identified herein, complete and ready for use at
the Marine Corps Base, Camp Pendleton, California.The relocatable
facilities shall be set up and ready for occupancy 45 days after award
of this contract. This contract shall be a firm-fixed price
requirement for the acquisition of the commercial use mobile building
in accordance with the specifications stated herein. The contract
schedule will be as follows: Item 0001, All work to provide the
relocatable facilities described herein, including modification,
purchase, delivery, assembly, level, anchor and set-up, complete and
ready for use. GENERAL BUILDING REQUIREMENTS. The relocatable
facilities provided shall be new and meet B 2 occupancy standards (with
options as identified in the following paragraphs) for commercial coach
building as approved by the Department of Housing for the State of
California. The relocatable facilities shall contain approximately 2160
square feet [36' X 60' exterior dimension], and shall be set up on
location and according to appropriate codes and regulations. The
relocatable facilities, at the site, shall comply with the Uniform
Building Code Seismic, wind, and static loading requirements for the
occupancy indicated. STAIRS, LANDING AND HANDICAP RAMP. Provide and
install the required minimum size stairs with landing and handicap ramp
where designated. The stairs landing and ramp shall be rigidly
constructed and coated with a non-skid surface; have handrails,
guardrails and meet all applicable requirements of the Uniform Building
Code. EXTERIOR FINISH. The relocatable facilities shall be neutral in
color, i.e., beige or tan siding with contrasting brown trim with
skirting to match. WINDOWS. Provide no windows. WINDOW COVERINGS.
Provide no window coverings. DOORS. Provide two (2) exterior metal clad
door with deadbolts, panic hardware and hydraulic closer. Doors shall
meet applicable requirements of NFPA 101 and American Disabilities Act
(ADA). WALLS. Provide 2" X 6" exterior framing with R-19 insulation,
covered with 5/8" T1-11 plywood grooved 8" o.c. painted tan with brown
trim. All interior walls shall have 5/8" textured drywall painted
Arizona White (Latex flat ). FLOOR COVERING. Provide 20 ounce
industrial pile carpeting (neutral color) throughout. ELECTRICAL WIRING
AND EQUIPMENT. Comply with the requirements of NFPA 70, the California
State Electrical Safety Code, and the following requirements: (1) All
wire shall be copper. (2) Panelboard: Circuit breaker type for
connection to 100 amp single phase, 120/240 volt feeder. Service
connections will be made from underground power supply directly to
service panel. The Government will make service connection. (3)
Receptacles: Provide and install 125 VAC, NEMA 5-20R, 20A 3-wire
grounding type duplex convenience receptacles in 2-gang boxes at each
location. All receptacles shall be spaced at eight (8') foot intervals
and wired in accordance with the latest edition of the National
Electrical Code. (4) Lighting: Provide and install energy efficient
diffused fluorescent lighting with electronic ballast and T-8 lamps in
2' X 4' fixtures in accordance with applicable codes. (5) Provide and
install two (2) energy efficient interior emergency exit lights (light
emitting diode [LED] type) with battery back-up mounted inside above
exit doors. HEATING AND AIR CONDITIONING SYSTEM. Provide electric
heating and air conditioning units thermostatically controlled and
capable of maintaining interior temperature above 65o F. when outside
temperature is 40o F and below 650 F. when outside temperature is 100o
F. Normal office occupancy and heat generating equipment shall be
considered when sizing equipment and maintaining interior temperature.
TELEPHONE WIRING, GANG BOXES, TERMINAL BLOCK AND CABINET. Provide,
install and label phone wire (six (6) pair) from each location,
adjacent to electrical outlets, run through a minimum 3/4" conduit from
1-gang box back to telephone terminal block secured in either metal,
wood or plastic cabinet with door at the location to be indicated. Gang
boxes shall be flush mounted at each location and have approximately 12
inches of excess phone wire remaining at the gang box end andconnected
at terminal block end. The Contractor shall provide and install box
covers for each box. DELIVERY AND SET-UP. The complete delivery and
set-up of the relocatable facilities shall be ready for occupancy 45
days after contract award. Delivery and set-up shall include: a.
Delivery of relocatable facilities, stairs, landing and handicap ramp
to the site. b. Locating, assembly, installing anchors/tie-downs and
leveling; using as a minimum, four inch (4") blocking to prevent
leveling jacks from sinking. NOTE: BEFORE TRENCHING OR DIGGING --
LOCATING SERVICES REQUIRE TEN (10) WORKING DAY ADVANCE NOTICE.
WARRANTY. The Contractor agrees that the work furnished under this
contract, all parts material and workmanship, shall be covered by the
most favorable warranties the Contractor gives to any customer. a. The
Contractor shall remedy at the Contractor's expense any failure to
conform, or any defect, of parts material and workmanship. b. The
Contracting Officer will notify the Contractor, in writing within a
reasonable time after the discovery of any failure, or defect
determined by the Government to be due to the performance of the work
under this contract. CONTRACTOR AVAILABILITY. The Contractor shall be
available at all times while work is being performed on this contract.
Telephone calls to the contract superintendent shall be responded to
within 60 minutes. WORK SCHEDULE. The schedule shall list the start
date and time and the estimated time of completion. The work schedule
shall be submitted to the Contracting Officer for approval at the
pre-performance meeting. Once approved, all work shall be performed in
strict compliance with the work schedule to facilitate the
Government's inspection of the work. Changes to the work schedule shall
be submitted for the Contracting Officer's approval at least three
working days prior to performance. PRE-PERFORMANCE CONFERENCE: A
Pre-performance conference will be held within 3 days prior to the
Contractor beginning work to discuss the general terms of the contract.
Theprovision at FAR 52.212-1, Instructions to Offerors -- Commercial
Items, applies to this acquisition. Offerors should submit a completed
copy of the provision at FAR 52.212-3, Offeror Representations and
Certifications -- Commercial Items, with its offer. The clauses at FAR
52.212-4, Contract Terms and Conditions -- Commercial Items and FAR
52.212-5, Contract Terms and Conditions Required to Implement Statutes
or Executive Orders -- Commercial Items apply to this acquisition and
will form a part of any resulting contract. Offers are due no later
than 4:00 P.M. Local Time, July 21, 1997. Offers may be mailed, hand
delivered or facsimile transmitted to the OICC, Building 22101, Marine
Corps Base, Camp Pendleton, P. O. Box 209, Oceanside, CA 92049-0209.
The telephone number for fax transmission is (760) 725-3222 or
725-8210. The point of contact for information regarding this
solicitation is Al Munoz, Contract Specialist at (760) 725-3525.