|
COMMERCE BUSINESS DAILY ISSUE OF JULY 16,1997 PSA#1888Navy Public Works Center, 2730 McKean St, Ste 1, San Diego, CA
92136-5294 Z -- ABOVE GROUNG STORAGE TANKS SOL N63387-97-Q-L590 DUE 073097 POC
Kohala Hembre, Purchasing Agent (Code 846), (619)556-9051, FAX:
(619)556-7775 2 EACH Provide and install two new single wall 20,000
gallon horizontally mounted above ground storage tanks with flat ends.
Tanks shall conform to UL-142, NFPA, and FM standards and shall bear
UL-142 permanently affixed, and engrave brass label with tank
construction specifications. The delivery and installation location in
Naval Submarine Base, San Diego, CA. Government will unload and
position tanks on existing saddles and contractor shall bolt tanks to
existing saddles. Equipment, delivery, installation and testing shall
be completed within 100 days of award of contract. Each tank shall have
two saddles located 6 feet from each end of the tank. Tanks shall be
designed for 5 PSIG internal pressure and vacuum. Tanks will store sea
water containing less than 50 percent diesel fuel. Tanks shall be
shop-built of steel conforming to ASTM A36. Each tank shall be twelve
feet in diameter and twenty five feet in length and have two steel
saddle attachment plates eleven inches wide welded to the wear plates
on both sides of the tank. The attachment plates shall be located
approximately six feet from the center of each plate to the end of each
tank and forty inches from the bottom of the tank measured vertically.
Each attachment plate shall have three 1 1/8 inch holes to allow
bolting to saddles, the distance between holes shall be 3 1/2 inches
(center to center) and the outside holes shall be 2 inches from the end
of the attachment plate (center to edge of plate). Contractor shall
field verify exact location of attachment plates prior to delivery to
ensure that tanks can be bolted to existing saddles. Side one of each
tank shall have the following openings: 1 each 6 inch flange fitting 1
foot from the bottom of the tank on center. Side two of each tank
shall have the following openings: 1 each 3 inch flanged fitting 1 foot
from the bottom of the tank on center and one each 3 inch flanged
fitting, on the inside and outside of the tank, 2 feet from the bottom
of the tank on center. The top of each tank shall have the following
openings; End 1: one each 6 inch flanged fitting 16 inches from the end
of the tank on center, two each 4 inch flanges fittings 12 inches apart
(center to center) and the nearest 4 inch flanged fitting shall be 12
inches from the 6 inch flanged fitting (center to center), one each 24
inch manhole with hinged top and tightening logs 30 inches from the
nearest 4 inch flanged fitting (center to center). End 2: one each 6
inch flanged fitting 16 inches from the end of the tank on center; one
each 4 inch flanged fitting 12 inches from the 6 inch flanged fitting
(center to center); one each 4 inch flanged fitting equipped with
rupture disc 12 inches from the 4 inch flanged fitting (center to
center); and one each 16 inch blank flanged emergency vent 30 inches
from the nearest 4 inch flanged fitting. Each tank shall have a
vertical exterior ladder extending to the 24 inch manhole and an
interior ladder accessible from the 24 inch manhole. The ladders shall
have slip resistant rings 12 inches on center and shall be designed
and fabricated per OSHA requirements. Bolts, nuts, and washers shall be
"corrosion resistant" which is defined as materials that are inherently
corrosion resistant and not a corrosion-resistant coating such as
provided by the galvanizing process. Each tank shall have lifting lugs
appropriately spaced on top to facilitate unloading on-site. Tank
interiors shall have amine-cured epoxy coating (Ameron-Amercoat 395 or
equal) suitable for continuous immersion in saltwater/diesel fuel
mixture. Tank exteriors shall have primer and two coats of enamel paint
suitable to protect the tank in a coastal marine environment and shall
match government supplied color. Interior and exterior coatings shall
be applied per coating manufacturers recommendations. The internal
coating shall be tested for holidays (pin holes) by either low or high
voltage spark testing. Tanks interior coating shall also be tested for
hardness and adhesion in accordance with ASTM D4541; and dry film
thickness ; and dry film thickness in accordance with SSPAC-PA2. Test
results shall be within specifications of coating manufacturer. All
test results shall be supplied to government on manufacturer's
letterhead. The tanks external coating shall be visually inspected for
defects. Contractor shall repair and/or replace areas of the coating
system which are found to be damaged or defective upon delivery of
equipment to the site and installation. Tanks shall be inspected and
tested before shipment from the factory by manufacturer as a completely
assembled vessel ready for installation. Before delivery contractor
shall perform tightness test and hydrostatic strength per UL-142. After
installation, contractor shall also perform a tightness test and
hydrostatic test per UL-142 to ensure that no damage has occurred in
shipping. The tanks must pass the assessment requirements on CCR Title
22 Section 66265.192. Contractor shall provide approval submittals for
government review prior to installation. Submittals shall include: tank
design drawing showing all components, and design calculations for tank
and tank attachment to existing saddles signed and sealed by California
Registered Structural Engineer. Before delivery, contractor shall
submit a written report stating that each tank is watertight, welds
have been inspected and are sound, interior coating is 100 percent
holiday free, exterior of tanks been coated per government
specifications and manufacturers recommendations, and tank meets the
local seismic Zone 4 requirements. Contractor will provide the
Government signed test results for the field testing of the tanks. If
the tanks do not meet requirements of this specification, such as poor
workmanship and wrong fabrications dimensions, the tanks may be
rejected. In the event Government rejects the tanks, the contractor
shall remove the tanks at their expense and replace the tanks with
acceptable tanks. Contractor is to provide a one year warranty covering
all tank components. The contractor shall repair or replace any
defective components at no cost to the government for a period of one
year following installation. No solicitations shall be mailed out. FAX
or mail quotes will be accepted. No telephone quotes will be accepted.
See Numbered Note(s): 1. (0195) Loren Data Corp. http://www.ld.com (SYN# 0228 19970716\Z-0051.SOL)
Z - Maintenance, Repair or Alteration of Real Property Index Page
|
|