COMMERCE BUSINESS DAILY ISSUE OF NOVEMBER 12,1997 PSA#197056 Contracting Squadron, 14100 W Eagle Street, Luke AFB, AZ 85309-1217 54 -- PREFABRICATED BUILDING SOL F02604-98-T0071 DUE 112197 POC Amn
Joe Chapman (602)856-7179 ext. 235 This is a combined
synopsis/solicitation for commercial items prepared in accordance with
the format in subpart 12.6 as supplemented with additional information
included in this notice. This announcement constitutes the only
solicitation; proposals are being requested and a written solicitation
will not be issued. This solicitation, No. F02604-98-T0071 is issued
as a request for quotations (RFQ). This solicitation document and
incorporated provisions and clauses are those in effect through Federal
Acquisition Circular 97-1. This acquisition is unrestricted; SIC: 3448;
Size Std.: 500 employees. Prefabricated Building to include the
following: Deliver and install a telecommunications shelter at Luke AFB
inside the fence surrounding the 969 water tower. The shelter will be
installed on a supplier provided cement pad floated level with loading
appropriate for the equipment (450PSF min). The use of copper
reinforcing mesh to improve grounding is encouraged but not required.
Configuration: Interior dimensions are 12' WIDE (not to exceed 15') x
18' LONG (not to exceed 20')x 10'8" HIGH (not to exceed 12').
Maintaining the lowest possible profile is a goal. Unoccupied
Telecommunications Structure Comply with: 1994 UBC, UMC, UFC -- 1996
NEC -- Motorola R56 Standards Loading: Floor 450PSF -- Roof 170PSF --
Wind 100MPH -- Seismic Zone 4 Building Specs: Ballistic ratings are not
desired but will be accepted. Steel door with good locks required;
ballistics are not a concern. Shelter should be insulated to at least
R-11. Exterior finish should be stucco and painted beige or mellow
brown. Interior walls: Finished painted white using abrasion resistant
material. Upgraded wall finish will be accepted. Interior Floor 1 1/8"
T&G Plywood covered with white tile and cove base minimum. Ceiling: "
plywood painted white. Upgrades accepted. Frame: Rigid steel, welded
construction, pan-style floor. Technical Specs: Furnish and install
Ladder Rack IAW Attachment 2, 8' off the floor. Lighting: One exterior
light next to the door. Interior fluorescent lighting that will not be
blocked by the ladder rack and will provide a good balanced working
environment. The commercial power supplied to the shelter will be three
phase 120/208 VAC Install alarm system for door open, over temp, under
temp, loss of commercial power. Provide instructions on how to connect
the system to a paging company. Install complete ground system.
External ring ground. Halo ground ring bonded to outside ground (must
be less than 5 ohms to earth) Equipment ground bars in cable tray and
power panel(s) Ground windows (cable ports) Both systems shall be
bonded at a single point. Install a dual redundant 4 ton HVAC system
with lead-lag. System should operate off of commercial 3 phase power.
Bard or MarvAir equipment. Low ambient kit. Mount equipment on the
shelter's side to minimize height. Award will be made to low-priced
technically acceptable offeror. To be technically acceptable, offeror
must demonstrate that the item offered satsifies the descriptive
requirements specified herein. Desired delivery and installation: Must
be installed by 15 Dec 97. FOB: destination to Luke AFB, AZ. The
provisions at FAR 52.212-1, Instructions to Offerors -- Commercial
Items applies to this solicitation. Offerors shall include with the
submission of their offer a completed copy of the provision at FAR
52.212-3, Offeror Representations and Certifications -- Commercial
Items. The clause at FAR 52.212-4, Contract Terms and Conditions --
Commercial Items applies to this acquisition. The clause at FAR
52.212-5, Contract Terms and conditions Required to Implement Statutes
or Executive Orders -- Commercial Items applies to this acquisition
with addenda incorporating FAR clause(s) 52.222-26, Equal Opportunity;
52.222-35, Affirmative Action for Special Disabled and Vietnam ERA
Veterans; 52.222-36, Affirmative Action for Handicapped Workers. The
clause at DFARS 252.212-7001, Contract Terms and Conditions Required to
Implement Statutes or Executive orders Applicable to Defense
Acquisitions of Commercial items applies to this solicitation with
addenda incorporating DFARS clause(s) 252.225-7001, Buy American Act
and Balance of Payment Program. Offers shall be submitted in writing
and received not later than 4:30 PM local time, 21 Nov 97. Fax offers
to (602)856-3057. Arizona does not observe daylight savings time.
(0310) Loren Data Corp. http://www.ld.com (SYN# 0238 19971112\54-0001.SOL)