22331-0700 A -- TWO(2)LARGE CAPACITY FIELD HEATERS SOL DAAB07-98-R-6005 DUE
010598 POC Peggy W. Butler, 703/325-4994, Contracting Officer, Ollie
Johnson, 703/325-6805, Contract Specialist WEB: CECOM-Acquisition
Center-Washington, 128.190.157.78. E-MAIL:
pbutle@hoffman-issaa2.army.mil, ojohns@hoffman-issaa2.army.mil. The USA
CECOM Acquisition Center -- Washington intends to issue RFP
DAAB07-98-R-6005 to procure the design, engineering analysis, prototype
manufacturing and documentation in the fabrication of two (2) 300,000
British Thermal Units per Hour (BTUH) Heaters. The heaters shall be
self-powered; provide re-circulating air and operate with either diesel
or JP-8 fuels. The heaters shall deliver not less than 300,000 BTUs per
Hour of clean air when operated in the all fresh air mode, with an
ambient air temperature of 0 degrees Fahrenheit, at sea level, against
an 0.5-inch water gauge (WG) pressure, using diesel fuel, grade Low
Sulfur No. 1-D conforming to A-A-52557. For this rated output, the
temperature at the output duct connection on the heater shall be
between 200 and 225 degrees Fahrenheit. The heaters shall deliver
clean, heated and ventilated air through sealed detachable flexible
ducts; have a protective enclosure; be trailer mounted for local
movement and positioning; and be capable of withstanding the
environmental conditions of arctic use. The complete heater assembly
with accessories stowed for packing shall not exceed: 42 inches height,
65 inches length and 45 inches width. Separate duct storage is
acceptable and shall not be included as part of the overall dimensions.
Weight shall not exceed 555 pounds, including the weight of
accessories, lubricants and internal fuel sufficient for one hours of
operation. Overall heater efficiency output/input shall not be less
than 80 percent. The noise levels at the operator's position is defined
to be 18 inches from the control panel, and other personnel occupied
area's of the heater( defined to be anywhere within 1 meter from the
perimeter of the heater at locations other than the operator's
position) shall not exceed 85 db(A). It is anticipated that the RFP
will be available on or about 17 December 1997 for downloading from the
website, located at 128.190.157.78. No hard copies will be provided.
The due date for proposals will be 16 January 1998. Questions should be
directed to the USA CECOM Acquisition Center- Washington,
AMSEL-AC-WB-B(O. Johnson), 2461 Eisenhower Avenue, Hoffman I,
Alexandria, VA 22331, or faxed to the attention of Ollie Johnson at
(703) 325-4995. (0325) Loren Data Corp. http://www.ld.com (SYN# 0004 19971125\A-0004.SOL)