COMMERCE BUSINESS DAILY ISSUE OF DECEMBER 3,1997 PSA#1984Navy Public Works Center, 310 John Tower Road, Pensacola, FL
32508-5303 41 -- 15 TON A/C SYSTEM SOL N65114-98-Q-F501 DUE 123097 POC Georgia M.
Fils/850 452-4187 A/C System, two (2) each, 15 ton computer room unit
(CRU), air cooled downflow, DX, dual circuit, with outdoor condenser,
two (2) each to have the following features and be the same as or equal
to Lliebert M/N FH199A CRU, condensing unit M/N CDF205L. 1. Copper
tube/aluminum fin "A" coil. 2. Standard (SM) microprocessor control
with the following: Battery back up, current temp/humid display,
programmable temp/humid set point & sensitivity, programmable hi/low
temp & humid alarm. Hi head press. change filter & loss of air flow
local alarm. 3. 20% ASHRAE filters. 4. Individually fused, hi-voltage
compartment with safety dead front. 5. Seperate compressor compartment
with hi-efficiency, rugged semihermatic compressors with two (2)
individual refrig. circuits. 6. Sight glass, filter dries, muffler,
hi/lo press switches and manual override. 7. Outdoor dual fan, fan
speed controlled condenser w/factory wired controls designed for 95
degree f. ambient, fan grille, all aluminum construction & copper
tube/aluminum fin condensing unit coil. 8. Indoor CRU to be 460/60/30,
condenser to be 208/60/3. 9. Three (3) stage element heat stripes. 10.
17.4 lb. per/hr humidifier. 11. Non-locking disconnect switch.. 12.
Discharge plenum. (0335) Loren Data Corp. http://www.ld.com (SYN# 0137 19971203\41-0001.SOL)