COMMERCE BUSINESS DAILY ISSUE OF DECEMBER 12,1997 PSA#1991Fleet And Industrial Supply Center Seal Beach Detachment, Naval Weapons
Station, Supply Dept., Bldg. 239, Code 210J, 800 Seal Beach Blvd., Seal
Beach, CA 90740 54 -- FURNISH AND INSTALL 1 EACH 3000 GALLON ABOVE-GROUND STORAGE
TANK, PUMP & PIPING SOL N00244-97-Q-0010 DUE 122997 POC Toni D.
Duenas-Ignacio, Contract Specialist (562) 626-7366; Fax: (562) 626-7479
WEB: Click here to get more information about FISC, San Diego,
http://www.sd.fisc.navy.mil. E-MAIL: Click here to contact the
contracting officer via e-mail, add6008@eagle.sbeach.navy.mil. This
action was initially synopsized in the CBD on 31 Oct. 97. Notice is
modified to delete specs and replaced with the following. Furnish and
install 1 each: 3000 gallon above-ground storage tank, must be double
wall, fire-rated, horizontal with remote panel electrical leak
detection device, overfill protection and end-mounted rung ladder.
Inner tank must be of material resistant to solvents such as:
chlorinated solvents, organic acids, phenolic bodies, chlorinated
hydrocarbons, trichlorethane, sodium hydroxide, sodium carbonate,
sodium phosphate, surfactants, sulfuric acid, dichromate salt, simple
& complex fluoride salt, water, chromic acid, and ferricyanide salts.
Tank will be located outdoors, elevated on an existing concrete pad.
Pump capacity should be 10 Gallons Per Minute at a 20 ft head.
Discharge should be from 1.5 to 2 inches with suction between 2 and 2.5
inches. Pump components be resistant to the material listed above. 100
ft of double walled piping with inner pipe of stainless steelalso with
connections and plumbing tie-in to tank, pump, and pit. Piping will
rise from top of tank and pump to approximately 20 feet. Distance
between tank and pump in stripping room is approx. 50 feet all indoors
and must pass through 2 walls. Distance between pit and pump is
approx. 20 feet. Upon completion of installation, provide certification
by a professional engineer registered in the State of California which
will satisfy users requirements for compliance with California Code of
Regulations Title 22, 66265.192. Drawing showing layout of existing
concrete pad, piping system, tank positioning is available upon
telephone or fax request to contract specialist. The revised closing
date is COB Dec 29, 1997. Anticipated Award Date is Jan 6, 1998.
(0343) Loren Data Corp. http://www.ld.com (SYN# 0221 19971212\54-0001.SOL)