Loren Data Corp.

'

 
 

COMMERCE BUSINESS DAILY ISSUE OF JANUARY 12,1998 PSA#2009

Navy Public Works Center, 310 John Tower Road, Pensacola, FL 32508-5303

41 -- PURCHASE OF COOLING TOWER/MOD #1 SOL N65114-98-Q-E001 DUE 011498 POC Edwina Black 850-452-4612 1. Cooling tower entering water temp. 96 deg F 2. Cooling tower leaving water temp. 85 deg F 3. Cooling tower GPM 948 to 952 GPM 4. " " " " ent. water temp. D.B. 90 deg F 5. " " " " ent. water temp. W.B. 80 deg F 6. Cooling tower max. heat feet water 20 feet 7. ;Motorj, vari-drive, h.p. 20 8. ELE. 480/60/3 9. Control Voltage 120/60/3 10. Maked up water Ball & float valve 11. Motor out of air stream 12. Extend-a-tube 13. Vibration switch 14.Cooling tower to include variable frequency drive control package, indoor mounting auto by pass & smart sys. temp control. 15. Marley Cooling Tower Model NC5201SS or Equal 16. When faxing your request, give your name, company name, phone & fax #'s and solication number (mod #1) to the attention of Edwina Black 904-452-5088 .If you have any questions, call Edwina Black 850-452-4612. (0007)

Loren Data Corp. http://www.ld.com (SYN# 0208 19980112\41-0001.SOL)


41 - Refrigeration, Air Condition and Air Circulating Equipment Index Page