COMMERCE BUSINESS DAILY ISSUE OF JANUARY 27,1998 PSA#2019Procurement Division, Naval Air Station Oceana, Supply Dept. Bldg 730,
Virginia Beach, VA 23460-5120 54 -- PREFABRICATED METAL CRYOGENIC BUILDING SOL N60191-98-Q-0004 DUE
021198 POC d. capps 757-433-2361 fax 757-433 WEB: n60191-98-q-0004,
cbdnet.gpo.gov/ACCEPT.template. E-MAIL: vwhite@series2000.com,
dcapps@livenet.net. DESC: The Naval Air Station Oceana in Virginia
Beach, VA is soliciting bids for a preengineered metal cryogenic
building. Design building for following loads: Live loads 25 PSF, Wind
loads 114 MPH Min, Collateral Loads 5 PSF. Building will have the
following dimensions: Width 40', Length 100', Height 12', Bay Spacing
20' 1) Preengineered metal building Catalog Data. 2) Shop drawings for
preengineered metal building. 3) Template for anchor bolts. 4) Design
data for building including foundation loads, anchor bolts, perlins
and gifts and bracing design calculations for the entire building,
stamped by a professional engineer. WARRANTIES: PROVIDE WARRANTY FOR
WEATHERTIGHTNESS AND WARRANTY FOR PANEL FINISH FOR A PERIOD OF 20 YEARS
PREFORMED WALL AND ROOF PANELS: MINIMUM 26 GAUGE GALVALUME SUBSTRATE
W/INTEGRAL FASTENERS AND 70% "KYNAR 500" STANDARD COLOR FINISH TO MATCH
NAS OCEANA "INTRUDER WHITE" (BUTLER-COTE "STONE WHITE" OR AMERICAN
BUILDINGS "LIGHT STONE"). PROVIDE MATCHING GUTTERS, DOWNSPOUTS,
HANGARS, STRAPS, GABLE AND EAVE TRIM, AND RAKE FLASHINGS. PROVIDE
CLOSURE STRIPS PREMOLDED TO MATCH CONFIGURATION OF THE COVERING.
PROVIDE ALL CONNECTORS AND SEALANTS NECESSARY FOR WEATHERTIGHTNESS.
PROVIDE VINYL FACED BLANKET TYPE FIBER-GLASS WALL AND ROOF INSULATION.
THICKNESS SHALL BE R-11 FOR THE WALLS AND 4-19 FOR THE ROOF. EXTERIOR
DOORS, FRAMES, AND HARDWARE: PERSONNEL DOORS: 3'-0"X7'0"X1-3/4",
INSULATED 16 GAUGE FLUSH HOLLOW -METAL DOORS AND FRAMES. HARDWARE SHALL
BE PROVIDED FOR ALL DOORS TO PROVIDE THE PROPER OPERATION AND TO BE IN
COMPLIANCE WITH LOCAL CODES. HARDWARE WILL INCLUDE HINGES, CLOSERS,
LOCKSETS, THRESHOLDS, AND DOOR STOPS. -OVERHEAD DOORS: 10'-0" WIDE BY
10'-0" HIGH, INSULATED, MANUALLY OPERATED SECTIONAL OVERHEAD DOORS. THE
INSULATION SHALL BE FACTORY INSTALLED POLYURETHANE CORE R-13 OR BETTER.
DOORS SHALL BE IN COMPLIANCE WITH LOCAL CODES AND INCLUDE FRAME AND ALL
NECESSARY HARDWARE. PROVIDE THREE ROOF CURBS WITH PREENGINEERED
BUILDING FOR ROOFTOP EXHAUST FAN. PROVIDE AND INSTALL ROOFTOP EXHAUST
FAN. (0022) Loren Data Corp. http://www.ld.com (SYN# 0194 19980127\54-0001.SOL)