COMMERCE BUSINESS DAILY ISSUE OF JANUARY 27,1998 PSA#2019Procurement Division, Naval Air Station Oceana, Supply Dept. Bldg 730,
Virginia Beach, VA 23460-5120 54 -- PRE- FABRICATED CRYOGENICS BUILDING SOL N60191-98-Q-0004 DUE
021098 POC David Capps 757-433-2361 E-MAIL: David Capps,
dcapps@livenet.net or vwhite@series2000.com. The Naval Air Station
Oceana, Va. Beach, VA is soliciting bids for a re-engineered metal
cryogenic bldg.This is a combined synopsis/solicitation for commercial
items prepared IAW FAR Subpart 12.6 as supplemented with additional
information included in this notice. This announcement constitutes the
only solicitation; proposals are being requested and a written
solicitation will not not be issued. Solicitation # N60191-98-Q-0004.
the solicitation document and incorporated provisions and clauses are
those in effect through Federal Acquisition Circular 97-02.The
following provisions apply: 52.212-1, Instructions to Offerors,
Commercial Items, 52-212-2 Evaluation-Commercial Items, 52.213-3
Offeror Representations and Certifications-Commercial Items should be
included with offers. 52.212-4 Contract Terms and Conditions-Commercial
Items and 52.212-5, Contract Terms and Conditions required To Implement
Statues or Executive Orders. Design building for following loads: Live
loads 25 PSF,Windloads 114 MPH Min, Collateral Loads 5 PSF. Bldg will
have the following dimensions: Width 40',Length 100', Height 12',bay
spacing 20' 1)Preengineered metal bldg Cat Data2)Shop drawings for
preengineered metal bldg.3)Template for anchor bolts. 4) Design data
for bldg including foundationloads, anchor bolts, perlins and gifts and
bracing design calculations for the entire bldg,stamped by a
professional engineer.Warranties: Provide warranty for weathertightness
and warranty for panel finish for a period of 20 years preformed wall
and roof panels: Minimum 26 guage galvalume substrate w/integral
fasteners and 70% kynar 500 standard color finish to match NAS Oceana
Intruder white(butler cote stone white or American Bldgs light
stone)Provide matching gutters downspouts,hangars,straps,gable and eave
trim and rake flashings. Provide closure strips premolded to match
config of covering.Provide all connectors and sealants necessary for
weathertightness. Provide vinyl faced blanket type fiberglass wall and
roof insulation.Thickness shall be R-11 for the walls and 4-19for the
roof. esterior Doors,frames and hardware:Personnel doors:3'0" X 7'0"
x 1-3/4",insulated 16 guage flushhollow metal doors and frames.
Hardware shall be providedfor all doors to provide the proper operation
and to be in compliance wit local codes.Hardware will include
hinges,closers,locksets, thresholds,and door stops. Overhead
doors:10'0" wide by 10'0" high,insulated,manually operated sectional
overhead doors.Insulation shall be factory installed polyurethane core
r-13 or better. Doors shall be in compliance with local codes and
include frame and all necessary hardware.Provide and install rooftop
exhaust fan. email address dcapps@livenet.net, vwhite@series20000.com
This replaces any previous solicitations. Delivery required by 01 Mar
1998 (0023) Loren Data Corp. http://www.ld.com (SYN# 0196 19980127\54-0003.SOL)