COMMERCE BUSINESS DAILY ISSUE OF FEBRUARY 6,1998 PSA#2027Naval Surface Warfare Center, Carderock Division, Philadelphia Purchase
Branch, Code 335, Bldg. 4, Philadelphia Business Center, Philadelphia,
PA 19112-5083 28 -- GOVERNOR CONTROL FOR MAIN PROPULSION DIESEL ENGINES DUE 021398
POC Mrs. B. Reppert, Contract Specialist, 215-897-7644 A governor
control for Main Propulsion Diesel Engines. The application is for
reciporcating Isotta Fraschini 6 cylinder, 600 horsepower diesel
engines with a Woodwrd EGB-2P forward acting governor actuator. One
control per propulsion engine is required, allowing autonomous
operation, if necessary. The engine speed/load control must have soft
loading/unloading and closed loop load sharing capabilities, and
utilize a master/slave speed reference scheme. Major functions
required: -Ability to control engine speed range of 800 -- 1800 rpm.
-Engine mapped variable dynamics, in which th edynamics can be varied
as functions of speed, load, speed error, and when clutched in. -- Dual
magnetic pickup input in the 320 Hz -- 800 Hz frequency range for
normal and redundant speed signal input operation. -- Isochronous
mechanical load sharing based on rack position feedback from a Woodward
rotary variable differential transformer (RVDT) with actuator demand as
automatic backup, should RVDT input fail. -- Speed reference during
load sharing determined by the first unit clutched in by a configurable
0-5 Vdc or 1-5 Vdc remote speed setting input or local Raise/Lower
discrete contact inputs. -- Clutch sequencing to allow first unit asked
to clutch in to ramp to idle an dissue a signal for the clutch to
engage. With one unit one line, th eoncoming unit asked to clutch in
will match speed with the master and issue a signal for the clutch to
engage. -- Soft loading and unloading in which the oncoming unit will
ramp its load to match the masters and perform isochronous load
sharing. In the de-clutching sequence, the unit will ramp its load to
the unload trip level and issue a de-clutch signal. The first unit
on-line is designated as the master and the system will run at the
masters speed reference, any changes to the slave speed reference are
ignored. -- One analog remote speed setting in put to the control
(configurable 1-5 or 1 -- 5 Vdc) is required, with additional local
discrete contact raise and lower speed inputs and independently
adjustable speed ramp rates. -- Engine protection via torque (fuel)
limiting is required and is to be based on percent fuel rack position
versus engine speed. Aa discrete input must be available to disable
this feature in battle conditions. -- A 4 to 20 mA fuel rack position
input signal to the control must be available for load sharing,
indication, and limiting for accurate control. -- Start fuel limitig
FEATURE is required to protect the engine and reduce smoke. -- Maximum
fuel limiting is required as an electronic fuel rack stop. -- As a
minimum, two configurable relay outputs must be available for alarm
condition indications such as overspeed indication, fuel rack position
indication failure, fuel limiter in control, speed switch, and remote
speed command input failure. -- Three configurable analog outputs must
be available for engine speed (tachometer) indication, speed reference,
remote speed reference, % load, actuator signal, and fuel demand.
Required inputs to the control/outputs from the control to other
systems: -- 24 Vdc input power with internal ground isolation, nominal
power 40 watts. -- Two magnetic pickup unit inputs (320 Hz -- 720 Hz
representing 800 to 1800 rpm) for redundant engine speed sensing. -- A
a minimum, five discrete inputs requiring approx. 10 mA at 24 Vdc for
"close for shutdown" indication, "Close when clutch is engaged"
indiation, local raise speed, loacl lower speed, and fuel limiter
override. -- At a minimum, three discrete outputs for minor and major
alarm indications, and engage clutch or clutch permissive signal. -- At
a minimum, three analog inputs for fuel rack position sensing (4-20
mA), remote speed setting (0-5/1-5 Vdc), and manifold air pressure
(4-20 mA). -- Actuator output (20-160 mA, forward acting). Must meet
the following MIL-SPEC requirements: -- MIL-SPEC 901D -- MIL-STD 167-1
Type 1 -- MIL-STD 461D (CE101, RE101, RE102, CS101, CS116, RS101)
Dueto limited real estate onboard MCM-1 class ships, each unit (4 units
per ship) must be no larger than 18"X12"X3". 50 Total units required no
later than 30 September 1998. (0035) Loren Data Corp. http://www.ld.com (SYN# 0229 19980206\28-0016.SOL)