COMMERCE BUSINESS DAILY ISSUE OF FEBRUARY 18,1998 PSA#2034Federal Emergency Management Agency, Mt. Weather Emergency Assistance
Center, 19844 Blue Ridge Mountain Road, Bluemont, VA 20135 41 -- AC UNIT SOL EMV-1998-RQ-0014 POC Jennie K. Nickleson,
540/542-2133 E-MAIL: EMV-1998-RQ-0014, jennie.nickleson@fema.gov. This
is a combined synopsis/solicitation according to the format in FAR
Subpart 12, as supplemented with additional information included in
this notice. EMV-1998-RQ-0014 is to purchase of a self-contained air
conditioner, 30 ton 11,000 CFM 280V, 60 HZ, 3 PH., 1 each. The air
conditioner unit contains the following listed items: CABINET: The unit
framework shall be formed structural steel members of 14-gauge
galvanized steel. Exterior panels shall be fabricated from 18-gauge
galvanized steel. The unit exterior shall be painted with air dry
enamel paint. The fan and compressor sections shall be insulated with
-inch of 1.75 pound density fiberglass insulation. The unit shall be
provided with removable panels to allow service access to compressors,
condensers, fan motor, fan bearings, coils and valves. Serviceable
panels shall be secured with quick-acting fasteners. The refrigerant
sight glasses shall be accessible during operation. The control panel
door shall have lift-off hinges. All panels shall be self-supporting.
COMPRESSOR: Shall be manufactured by the unit manufacturer. Units shall
have multiple compressors with independent circuits. Scroll compressors
shall be heavy-duty, suction-cooled type with suction screen,
centrifugal oil pump with dirt separator, oils sight glass and oil
charging valve. Protective devices for low pressure, high pressure and
motor temperature shall be provided. The compressors shall be mounted
on rubber-in-shear isolators for vibration insolation. CONDENSER: One
condenser shall be provided for each compressor. The condensers shall
be shell-and-tube design with removable heads and mechanically
cleanable tubes. Condenser tubes shall be nominal inch. O.D. copper.
Condenser waterside working pressure shall be 400 psig. Unit will allow
condenser water piping to be brought to the condensers from the right
side of the unit. All water piping including economizer valve package
shall be manifolded into a single inlet and outlet and extended to the
exterior of the unit. EVAPORATOR: The evaporator coil shall be
seamless copper tubes expanded into aluminum fins. Tubes shall be -inch
O.D. with internally enhanced surfaces. The coil shall have a staggered
tube arrangement with interlaced circuiting and no more than 12 fins
per inch. The drain pan shall be fabricated of stainless steel and be
insulated with -inch of one pound density fiberglass. Drain piping
shall be provided to the exterior of the unit. REFRIGERANT CIRCUIT:
Shall be independent and completely piped including filter driers,
sight glasses, distributors, expansion valves with adjustable superheat
and external equalizer, and high pressure relief valves with a -inch
SAE flare connection. The circuits shall be tested, dehydrated and then
charged with oil and Refrigerant-22. SUPPLY FAN, DRIVE AND MOTOR: The
supply fan shall be dual, forward curved medium pressure fans secured
to a solid steel shaft with grease-lubricated bearings designed for
200,000 hours. The drive components shall include fixed-pitch sheaves
and multiple V-belts sized for 150 percent of nominal motor horsepower.
The supply fan motor shall be high efficiency open drip-proof. The
supply fan motor shall have a standard T-frame. The entire fan
assembly, including drive components, shall be mounted on a common
base. The fan base shall be isolated inside the unit. The entire
assembly shall be statically and dynamically balanced at the factory to
a maximum tolerance of 3 mils peak to peak. FAN MODULATION: The
variable volume unit shall operate at design airflow based on fan and
motor drive selections. Fan and motor sheaves will be selected for a
rpm to develop airflow at design static pressure. INLET GUIDE VANES:
Airflow modulation shall be by inlet guide vanes. The inlet vanes,
complete with electric actuator, linkage and controller shall be
factory-installed and adjusted. The static pressure setpoint shall be
adjustable. A duct static pressure sensing probe shall be provided for
field-installation. FILTERS: Two-inch medium velocity throwaway
filters shall be provided for unit operation. UNIT CONTROLS: Unit
Control Module -- The microprocessor controller shall control all unit
functions, including the economizer, mechanical refrigeration and fan
modulation and monitor diagnostics. All controls shall be factory
installed and adjusted. The controller shall include a switch to place
the unit in Auto Remote, Auto Local or Stop/Reset mode; an indicator
display to show unit operating status, diagnostics and setpoints; and
adjustable setpoints for supply air temperature, supply air pressure,
economizer minimum position, supply air temperature control band and
supply air pressure high static limit. The three-position switch and
indicator display shall be accessible without opening any unit panels.
ENTERING AIR TEMPERATURE PROTECTION: A single-point sensor is used to
detect entering air temperature to the unit. If entering air
temperature to the unit exceeds 135 F or falls below 37 F, the unit
will shut down and dispay a diagnostic code. Manual reset is required
when the entering airtemperature rises above 135 F. RATINGS: Design
cooling capacity shall be 30 tons nominal based on standard ARI
conditions. Designs airflow shall be 11,000 CFM @ 0.65" E.S.P. Power
supply shall be 208 volts, 60 Hertz, 3 phase. DIMENSIONS: Unit
dimensions shall not exceed 95" high, 90" wide and 52" deep with all
options and accessories installed. The unit shall be shipped in
separate sections such that it can be transported through a freight
elevator and a 35" wide doorway and assembled in place. ACCESSORIES to
be provided: 1) discharge plenum for mounting on top of the unit.
Discharge opening shall be field cut. 2) unit mounted electrical
disconnect switch, 3) 5 year compressor warranty, 4).Spring isolators,
5) water flow switch, 6) UL approved, 7) water side economizer. It
shall be 4 row, mechanically cleanable and shall be shipped separately
for installation in place. Modulating valves shall be provided for
control of water flow through the economizer. SUBMITTALS: Three sets of
shop drawings shall be submitted for approval prior to fabrication of
the unit. Construction and delivery shall not proceed until one set of
drawings has been returned approved. Please provide manufacturer's
name and model number of proposed product. In addition, provide
descriptive literature of the product being offered in order for the
Government to determine if the offered product meets the Government's
minimum requirements. Failure to provide descriptive literature for
proposed product will result in your offer not being considered. This
announcement constitutes the only solicitation; quotes are being
requested and a written request for quotes will not be issued. The
solicitation is issued as a Request for Quotes (RQ). Contractor must
meet all requirements detailed in this synopsis. Government's desired
delivery time is 60 days. Please specify best delivery time upon
approval of the submitted drawings. Include shipping charges, if any,
in your quote as a separate line item. It is anticipated that a
firm-fixed price single award purchase order will result from this RFQ.
Price is of greater importance when compared with technical. Quoters
must include with the pricing any shipping costs applicable to this
procurement. Quoters are to include a completed copy of the provisions
at 52.212-3 Offeror Representations and Certifications-Commercial
Items with this quote. The following clauses also apply 52.212-1
Instruction to Offers-Commercial Items, 52.212-2 Evaluation Commercial
Items, 52-212-4 Contract Terms and Conditions-Commercial Items,
52.212-5 Contract Terms and Conditions Required to Implement Statutes
or Executive Order-Commercial Items, 52.222-26 Equal Opportunity
(E.O.11246), 52.222-35 Affirmative Action for Special Disabled and
Vietnam Era Veterans (38 U.S.C. 4212), 52.222-36 Affirmative Action for
Handicapped Workers (29 U.S.C. 793), 52.225-3 Buy American Act-Supplies
(41 U.S.C. 10). All responsible sources may submit a quote, which shall
be considered. The SIC 3585, the small business size standard is 750
employees. The due date for submission of quotes is February 27, 1998,
at 10:00 A.M., local time, to FEMA, Mt. Weather Emergency Assistance
Center, 19844 Blue Ridge Mountain Road, Bluemont, Virginia 20135. All
requests for information are to be addressed to Mrs. Jennie K.
Nickleson, Contract Specialist, at 540-542-2133. Technical and/or
administrative questions must be received no later than five business
days after publication of this notice and may be faxed to
540/542-2631/2632 or mailed to the address for submission of quotes
shown above. Any amendments to this solicitation will be published in
the same manner as the initial synopsis/solicitation. (0043) Loren Data Corp. http://www.ld.com (SYN# 0237 19980218\41-0001.SOL)