COMMERCE BUSINESS DAILY ISSUE OF FEBRUARY 19,1998 PSA#2035Federal Emergency Management Agency, Mt. Weather Emergency Assistance
Center, 19844 Blue Ridge Mountain Road, Bluemont, VA 20135 41 -- AC UNIT SOL EMV-1998-RQ-0014 POC Jennie K. Nickleson,
540/542-2133 E-MAIL: EMV-1998-RQ-0014, jennie.nickleson@fema.gov. This
is a combined synopsis/solicitation according to the format in FAR
Subpart 12, as supplemented with additional information includes in
this notice. EMV-1998-RQ-0014 is to purchase a self-contained air
conditioners, 30 ton 11,000 CFM 280V, 60 HZ, 3 PH., 1 each. The air
conditioner unit contains for following listed items: CABINET: The unit
framework shall be formed structural steel members of 14-gauge
galvanized steel. Exterior panels shall be fabricated from 18-gauge
galvanized steel. The unit exterior shall be painted with air dry
enamel paint. The fan and compressor sections shall be insulated with
-inch of 1.75 pound density fiberglass insulation. The unit shall be
provided with removable panels to allow service access to compressors,
condensers, fan motor, fan bearings, coils and valves. Serviceable
panels shall be secured with quick-acting fasteners. The refrigerant
sight glasses shall be accessible during operation. The control panel
door shall have lift-off hinges. All panels shall be self-supporting.
COMPRESSOR: Shall be manufactured by the unit manufacturer. Units shall
have multiple compressors with independent circuits. Scroll compressors
shall be heavy-duty, suction-cooled type with suction screen,
centrifugal oil pump with dirt separator, oils sight glass and oil
charging valve. Protective devices for low pressure, high pressure and
motor temperature shall be provided. The compressors shall be mounted
on rubber-in-shear isolators for vibration insolation. CONDENSER: One
condenser shall be provided for each Compressor. The condensers shall
be shell-and-tube design with removal heads and mechanically cleanable
tubes. Condenser tubes shall be nominal inch O.D. copper. Condenser
waterside working Pressure shall be 400 psig. Unit will allow condenser
water piping to be brought to the condensers from the right side of the
unit. All water piping including economizer valve package shall be
manifolded into a single inlet and outlet and extended to the exterior
of the unit. EVAPORATOR: The evaporator coil shall be seamless copper
tubes expanded into aluminum fins. Tubes shall be -inch O.D. with
internally enhanced surfaces. The coil shall have a staggered tube
arrangement with interlaced circuiting and no more than 12 fins per
inch. The drain pan shall be fabricated of stainless steel and be
insulated with -inch of one pound density fiberglass. Drain piping
shall be provided to the exterior of the unit. REFRIGERANT CIRCUIT:
Shall be independent and completely piped including filter driers,
sight glasses, distributors, expansion valves with adjustable superheat
and external equalizer, and high-pressure relief valves with a -inch
SAE flare connection. The circuits shall be tested, dehydrated and then
charged with oil and Refrigerant-22. SUPPLY FAN, DRIVE AND MOTOR: The
supply fan shall be dual, forward curved medium pressure fans secured
to a solid steel shaft with grease-lubricated bearings designed for
200,000 hours. The drive components shall include fixed-pitch sheaves
and multiple V-belts sized for 150 percent of nominal motor horsepower.
The supply fan motor shall have a standard T-frame. The entire fan
assembly, including drive components, shall be mounted on a common
base. The fan base shall be isolated inside the unit. The entire
assembly shall be statically and dynamically balanced at the factor to
a maximum tolerance of 3 mils peak to peak. FAN MODULATION: The
variable volume unit shall operate at design airflow based on fan and
motor drive selections. Fan and motor sheaves will be selected for a
rpm to develop airflow at design static pressure. INLET GUIDE VANES:
Airflow modulation shall be by inlet guide vanes. The inlet vanes,
complete with electric actuator, linkage and controller shall be
factory-installed and adjusted. The static pressure setpoint shall be
adjustable. A duct static pressure sensing probe shall be proved for
field-installation. FILTERS: Two-inch medium velocity throwaway filters
shall be provided for unit operation. UNIT CONTROLS: Unit Control
Module- The microprocessor controller shall control all unit functions,
including the economizer, mechanical refrigeration and fan modulation
and monitor diagnostics. All controls shall be factory installed and
adjusted. The controller shall include a switch to place the unit in
Auto Remote, Auto Local or Stop/Reset mode; an indicator display to
show unit operating status, diagnostics and setpoints; and adjustable
setpoints for supply air temperature, supply air pressure, economizer
minimum position, supply air temperature control band and supply air
pressure high static limit. The three-position switch and indicator
display shall be accessible without opening any unit panels. ENTERING
AIR TEMPERATURE PROTECTION: A single-point sensor is used to detect
entering air temperature to the unit. If entering air temperature to
the unit exceeds 135 F or falls below 37 F, the unit will shut down and
display a diagnostic code. Manual reset is required when the entering
air temperature rises above 135 F. RATINGS: Design cooling capacity
shall be 30 tons nominal based on standard ARI conditions. Designs
airflow shall be 11,000 CFM @ 0.65" E.S.P. Power supply shall be 280
volts, 60 Hertz, 3 phase. DIMENSIONS: Unit dimensions shall not exceed
95" wide and 52" deep with all options and accessories installed. The
unit shall be shipped in separate sections such that it can be
transported through a freight elevator and a 35" wide doorway and
assembled in place. ACCESSORIES TO BE PROVIDED: 1) discharge plenum for
mounting on top of the unit. Discharge opening shall be field cut. 2)
unit mounted electrical disconnect switch, 3) 5 year compressor
warranty, 4) Spring isolators, 5) water flow switch, 6) UL approved, 7)
water side economizer. It shall be 4 row, mechanically cleanable and
shall be shipped separately for installation in place. Modulating
valves shall be provided for control of water flow through the
economizer. SUBMITTALS: Three sets of shop drawings shall be submitted
for approval prior to fabrication of the unit. Construction and
delivery shall not proceed until one set of drawings has been returned
approved. Please provide manufacturer's name and model number of
proposed product. In addition, provide descriptive literature of the
product being offered in order for the Government to determine if the
offered product meets the Government's minimum requirements. Failure to
provide descriptive literature for proposed product will result in your
offer not being considered. This announcement constitutes the only
solicitation; quotes are being requested and a written request for
quotes will not be issued. The solicitation is issued as a Request for
Quote (RQ). Contractor must meet all requirements detailed in this
synopsis. Government's desired delivery time is 60 days. Please specify
best delivery time upon approval of the submitted drawings. Include
shipping charges, if any, in your quote as a separate line item. It is
anticipated that a firm-fixed price single award purchase order will
result from this RQ. Price is of greater importance when compared with
technical. Quoters must include with the pricing any shipping costs
applicable to this procurement. Quoters are to include a completed copy
of the provisions at 52.212-3 Offeror Representations and
Certifications-Commercial Items with this quote. The following clauses
also apply 52.212-1 Instruction to Officers-Commercial Items, 52.212-2
Evaluation Commercial Items, 52-212-4 Contract Terms and
Conditions-Commercial Items, 52.212-5 Contract Terms and Conditions
Required to Implement Statutes or Executive Order-Commercial Items,
52.222-26 Equal Opportunity (E.O.11246), 52.222-35 Affirmative Action
for Special Disabled and Vietnam Era Veterans (38 U.S.C. 4212),
52.222-36 Affirmative Action for Handicapped Workers (29 U.S.C. 793),
52-225-3 Buy American Act-Supplies (41 U.S.C. 10). All responsible
sources may submit a quote, which shall be considered. The SIC code is
3585 with the small business size standard being 750 employees. The
due date for submission of quotes is February 27,1 998,a t 10:00 A.M.,
local time,to FEMA, Mt. Weather Emergency Assistance Center, 19844
Blue Ridge Mountain Road, Bluemont, Virginia 20135. All requests for
information are to be addressed to Mrs. Jennie K. Nickleson, Contract
Specialist, at 540-542-2133. Technical and/or administrative questions
must be received no later than five business days after publication of
this notice and may be faxed to 540-542-2631-2632 or mailed to the
address for submission of quotes shown above. Any amendments to this
solicitation will be published in the same manner as the initial
synopsis/solicitation. (0048) Loren Data Corp. http://www.ld.com (SYN# 0259 19980219\41-0002.SOL)
41 - Refrigeration, Air Condition and Air Circulating Equipment Index Page
|
|