COMMERCE BUSINESS DAILY ISSUE OF MARCH 3,1998 PSA#2043Commanding Officer, NAVFACCO Bldg 41 Code 27, NCBC 1000 23rd Ave, Port
Hueneme, CA 93043-4301 Z -- MAINTENANCE HIGH VOLTAGE DISTRIBUTION & FIRE EXTERIOR LOOP SYSTEM
SOL N47408-98-Q-3424 DUE 040398 POC Contract Specialist, Carrie de
Jesus, (805)982-6066, FAX (805)982-9121 This is a combined
synopsis/solicitation for commercial items prepared IAW the format in
FAR Subpart 12.6. This announcement constitutes the only solicitation;
proposals are being requested and a written solicitation will not be
issued. This solicitation is unrestricted commercial item purchase, SIC
Code 1731, 7.0M; Est price range is $1,000,000.00 to $5,000,000.00.
Sub-contracting plan is required for Large Business only. Thirty (30)
minutes response time to emergency calls are required. Area of
consideration is Ventura County. This is a combination FFP & IQ
contract. Term is NTE 60 months. Service to be performed at NCBC, Port
Hueneme, CA. The following FAR Clauses are applicable to this
acquisition: FAR 52.212-1 Instructions to Offerors -- Commercial Item,
FAR 52.212-3 Offeror Representations & Certs -- Commercial Item, FAR
52.212-5 Contracts Terms & Conditions and FAR 52.212-2 Evaluation --
Commercial Items or FAR part 13.106-2 will be used as evaluation
factors. Past Performance and Cost are approx equal in importance. The
Government reserved the rights to add more contract clauses at time of
award. Site Visit shall be arranged with Mr. Bill Mussman at
(805)982-5348. GENERAL REQUIREMENTS: The KTR shall maintain the
Electrical Distribution and Emergency Generation Systems as described
in Attachment JC-1. The work shall include, but is not limited to, the
identification, planning, scheduling, status reporting, and analysis
of electrical distribution emergency generation systems operations,
maintenance and repair and rewinding of motors. Electrical Distribution
includes all facility electrical distribution systems such as (1)
overhead and underground transmission and distribution lines from
delivery points to all main service entrance switches in buildings,
including substations and accessories; (2) exterior lighting systems,
including street, flood, perimeter and security lighting; (3) secondary
drops to the building weatherhead or first connection to the building
system; (4) all components of ship-to-shore power systems, including
portable power cables and connectors, receptacles, controls, and
enclosures; and removal of limbs and debris from close proximity of
power lines. All 5kv and above underground cables repaired or replaced
made under this contract shall have a High -Potential test made upon
completion of the repairs and before cables are energized. All work
shall be in accordance with the most current National Electric Code,
Calif General Order 95 (G.O. 95), (G.O. 128) and the original equipment
manufacturers (OEM) most current written instructions and
specifications, which the KTR shall obtain at no additional cost to the
Gov't. The KTR shall establish and maintain a complete Quality Control
program in compliance of the statement of work and shall furnish all
facilities, equipment, materials, parts, supplies and tools necessary
for the performance of the work of this contract unless otherwise
specified in this contract. Items of equipment necessary to perform
work, shall be furnished, maintained and operated by the KTR which
include but not limited to trucks, forklifts, roll-off containers, and
hand operated power driven equipment. DETAILED REQUIREMENTS: 0001AA --
Provide Substation Maintenance. On a semi-annual basis, provide
maintenance to the three NCBC Substations (Lehman, CBC, and West
Jetty). The KTR shall inspect, clean and lubricate substation
equipment. Equip shall be maintained to OEM 's most current specs. The
KTR shall perform housecleaning services to the substation grounds and
areas like trash cleanup and sweeping. Provide a schedule of regularly
scheduled inspection and cleaning of systems to the Gov't Rep, prior
to start of work and maintain records of repair and/or replacement to
include labor, material and equip. 001AB-Remedial repairs labor.
(Option Years Only) Est 2500 MH: The KTR shall provide labor for
remedial repairs to the Distribution Sys and Fire Alarm Loop. This work
shall be ordered as needed by the Gov't Rep. Unscheduled repairs and
emergency service call work under this line item shall be for labor
only. This work shall be identified by PW personnel through service
call or work order. 0001AC-Fire Alarm Loop Testing: Provide testing
services four hrs a week for fifty-two consecutive weeks. Testing shall
include open and closed circuit tests. Tests shall alternate each week
so even weeks the circuits are tested open and odd weeks the circuits
are tested closed. Tests shall consist of one box tested on each
circuit. boxes shall not be routinely tested again until all boxes in
the circuit have been tested. Maintain records of all tests and shall
be kept at the Fire Station and shall be kept current. 0002AA --
Emergency Call-in (After hrs): After hrs shall be defined as 1630
through 0700 Mon through Fri and 0001 through 2400 Sat, Sun and Federal
holidays. Provide maintenance staff to respond to NCBC emergencies.
This shall include Distribution and Fire Systems trouble calls.
Maintain records of alarm and trouble call response. Provide a
"Call-In" reportone working day after call has been received, to the
Gov't Rep. The report shall include the following: 1. Date and time of
call 2. Caller from NCBC. 3. Type of work required (Power Distribution
or Fire Alarm System). 4. ECD 5. Est cost if required) 0002AB --
Emergency Call-in (Normal hrs): Normal hr response shall be between the
hrs of 0700 and 1630 Mon through Fri. 0002AC -- Remedial Repairs
(labor): A portion of the work included in the scope of this contract
cannot be identified in advance in sufficient detail to be included as
a unit priced task. Provide labor to perform remedial repairs (during
normal work hrs) identified and approved by Gov't Rep. Maintain
documentation for all work. 0002AD -- Remedial Repairs (materials): A
portion of the work included in the scope of this contract cannot be
identified in advance in sufficient detail to be included as a unit
priced task. Material prices shall be the manufacturer's current retail
or the suppliers listed prices. KTR shall provide invoices to Gov't Rep
for all material purchased. 0002AE. -- Equipment: A portion of the work
included in the scope of this contract cannot be identified in advance
in sufficient detail to be included as a unit priced task. Equipment
price shall be the KTR's actual cost for use of equipment. 0001 BASE
YEAR -- FIRM FIXED PRICE: 0001AA Provide semi-annual substation
maintenance for 3 units; 0001AC Fire Alarm Loop Testing 300 MH; 0002
BASE YEAR -- INDEFINITE QUANTITY: 0002AA Emergency Call-in After Hours-
Est. 300 MH0002AB Emergency Call-in Normal Work Hours- Est. 200 MH;
0002AC Remedial Repair (Labor) Est. 2,500 MH; 0002AD Remedial Repair
(Material) NTE (Base: $45,000; First Option: $45,900; 2nd, 3rd, and 4th
$46,818 each option yr); 0002AE Remedial Repair (Equipment) NTE (Base:
$75.50: First Option : $77.01; 2nd, 3rd, and 4th $79,051.02 each
option yr); NOTE: Above line items are repeated on all the options
years + above described line item 0001AB Remedial Repair (Labor)
estimated at 2500 MH. KTR to furnish priceson above in detail with
extended cost and totals. OTHER REQUIREMENTS: The Gov't, at its option,
may require the KTR to utilize GFP when available. The KTR shall
provide all equip, new parts, materials and services to perform the
requirements of this contract. All replacement units, parts, and
materials to be used in the maintenance and repair of equip shall be
compatible with existing equip; shall conform to mfgr technical specs,
and shall be used IAW original design and mfgr intent. DISPOSITION OF
ENVIRONMENTALLY SENSITIVE WASTES: Appropriate Material Safety Data
sheet (MSDS) shall be submitted to the Gov't Rep for approval. All
consumable products shall be the responsibility of the KTR, and as
such, the KTR shall make every effort to recycle versus dispose of the
consumable wastes. HAZARDOUS WASTE SPILL: A spill contingency plan
shall be submitted for approval within 15 days from "DOA." The
Contractor shall transport these items to an approved recycling and/or
treatment/disposal facility by the U.S. EPA/Calif Dept of Toxic
Substances Control (DTSC). Should a spill occur during transportation
of the hazardous wastes, the KTR shall immediately notify the NCBC
Environmental Dept, Deputy Director, Mr. Bill Venable, (805) 982-3771.
WORK DOCUMENTATION required by this contract to be submitted within 15
calendar days of "Notice of Award" are: Work Scheduling. The KTR shall
coordinate work with the CO for approval, a work schedule of planned
power outages during the term of this contract. Any changes to the
schedule shall be coordinated with the Contracting Officer at least 24
hours in advance. Maintenance procedures: The KTR shall submit
documentation of circuit breaker (Substation Maintenance) to the Gov't
Rep for approval, a schedule of maintenance procedures for the
systems. The schedule shall include activity, frequency, and
manufacturer's reference. Recycling/Disposal Facility. The KTR shall
submit the name(s), address, phone number(s) of the recycling/disposal
facility utilized in the disposition of any wastes generated by the
specifications. A copy of the facility's permit for the type of waste
processed shall be required. Contractor's Personnel, and Contractor's
License Certifications: The KTR shall provide Certs, or resumes showing
training or experience of personnel to work on High Voltage power lines
that have qualifications as "lineworkers". These keyworkers shall have
a minimum of five years experience as certified lineworkers. Certs
shall be by a state recognized organizations i.e. City, County, State
or similar association(s). Personnel shall be trained in the
appropriate procedures in accordance with the OEM installation and
maintenance specs for the equip being maintained and shall comply with
all State of CA Licensing Requirements for the work being performed.
Certs shall include the name of the person to whom the license was
issued, classification(s), license number, and the date of expiration.
Reporting. The KTR shall provide a written report with each invoice
for payment of all work accomplished during the preceding month
including work done in addition to scheduled preventive maintenance.
ELECTRICAL DISTRIBUTION AND EMERGENCY GENERATION SYSTEMS/EQUIPMENT The
KTR shall maintain the following systems and equip- Overhead
Distribution Lines: 1). Overhead Distribution Lines: 4,160 volt, 3
phase, 4 wire, wye connected, solidly grounded, est. length 28.9 miles.
2). Underground Distribution Lines: 4,160 volt, 3 phase, 4 wire, wye
connected, solidly grounded, 4 single conductor cables in duct, est.
length 4.4 miles and 480 volt, 3 phase, ungrounded, one 3 conductor
cable in duct (under or in piers), est. length 6,000 feet. 3). Outdoor
Substations: a. "Seabee Sub", 12,470 volts -- 4,160 volts, 20,000 KVA,
9 secondary feeders, b. "Lehman Sub", 12,470 volts -- 4,160 volts,
20,000 KVA, 4 secondary feeders, c. "West Jetty Sub", 12,470 volts --
4,160 volts, 20,000 KVA, 2 secondary feeders, d. "Wharf 6 Sub", 12,470
volts -- 480 volts, 1,500 KVA, 2 secondary circuits and e. "Wharf 4
Sub", 12,470 volts -- 480 volts, 1,500 KVA, 1 secondary circuit. e.
"Wharf 4 Sub", 12,470 volts -- 480 volts,,500 KVA, 1 secondary circuit.
5). Emergency Generation System: Est. 21 generator sites Generators
range in size from 45 kw to 800 kw. 1-800, 12-200, 5-100, 1-60, and
2-45. 6) Exterior Lighting System: Two hundred Fifty street lights on
steel and wood poles, 150 to 250 watt, HPS type with integral photo
cell control in each. (0057) Loren Data Corp. http://www.ld.com (SYN# 0135 19980303\Z-0005.SOL)