Contracting Office, Tooele Army Depot, P.O. Box 839, Building 9, Tooele, Utah 84074-5020

61 -- UNINTERRUPTIBLE POWER SUPPLY (UPS) SOL DAAC89-98-T-0127 DUE 041698 POC Paula K. Kramer, Contracting Officer, (435) 833-3146 WEB: None, None. E-MAIL: None, None. System Ratings are as follows: The input voltage shall be 208 volt, 3 phase, 60 hertz, 4 wire plus ground. The reserve input voltage shall be 208 volt, 3 phase, 60 hertz, 4 wire plus ground. The UPS system output voltage shall be 208 volts, 3 phase, 60 hertz, 4 wire plus ground. The battery cells shall be sealed, maintenance free type and have a reserve time of 15 minutes minimum with the UPS operating at full load at 0.8 power factor. The battery shall be supplied with intercell connectors mounted internal to the UPS. The battery shall be supplied preassembled, and wired in matching cabinets. (0099)