Administration Circle, China Lake, CA 93555-6100 61 -- DIESEL GENERATOR SETS SOL N68936-98-R-0113 DUE 042498 POC
Janelle M. Etoch, Contract Specialist, (760) 939-9669 This is Part 1 of
a 2 Part Synopsis. This is a combined synopsis/solicitation for
commercial items prepared in accordance with the format in FAR Subpart
12.6 as supplemented with additional information contained in this
notice. This announcement constitutes the only solicitation; proposals
are being requested and a written solicitation will not be issued.
This is Solicitation Number: N68936-98-R-0113, and is issued as a
Request for Proposal (RFP). The solicitation document and incorporated
provisions and clauses are those in effect through Federal Acquisition
Circular Number 97-03 and Defense Acquisition Circular Number 91-12.
This solicitation contains two contract line item numbers (CLINs 0001
and 0002). Description of requirement: 0001 -- 1 unit, 50 KW Generator
set, trailer mounted with sound attenuated enclosure; 0002 -- 11
units, 25 KW Generator set, trailer mounted with sound attenuated
enclosure, all units to be identical. The term unit refers to the
generator, motor, enclosure, controls,fuel tank, trailer, and all
attached/related components as one operational assembly. All units will
be 1998 year models or newer and will meet or exceed the following
basic requirements and specifications: GENERATORS: 50 KW Continuous
Stand-by power @ 1800 RPM; 25 KW Continuous Stand-by power @ 1800 RPM.
25 KW units and 50 KW unit: 1) Multi Voltage, 12 lead, 3 phase, 60 Hz;
2) Voltages required: a) 120/208; b) 120/240; c) 277/480; 3) Multi-trip
circuit breaker for generator protection; 4) Electronic Voltage
regulator with 1% regulation or better; 5) Class F insulation, or meet
temperature rise standards of class F insulation; 6) Generator, field
circuit and thermal overload protection. The 25 KW units will
additionally require Voltage selection switch for selecting: 1) 120/208
volts; 2) 120/240 volts; 3) 277/480 volts. ENGINE: 25 KW units and 50
KW unit: 1) Diesel powered; 2) Water Cooled; 3) Secondary fuel filter;
4) Electronic governor control, Isochronous; 5) Fuel lock out
solenoid; 6) Exhaust silencer; 7) Jacket water heater-1000 watt/120
volt; 8) Flexible fuel lines; 9) Conformance and certification of
compliance with current EPA and South Coast Air Quality Management
District (SCAQMD) requirements. The 25 KW units will not exceed 50
Horse Power (HP). CONTROL CONSOLE: 25 KW units and 50 KW unit: 1)
Frequency, Voltage, and Amperage Meters; 2) Phase selector switch for
voltage and amp meters; 3) Auto/manual start switch; 4) Voltage
adjusting rheostat; 5) Shutdown and indication for: a) Low oil
pressure; b) High temperature-Low water; c) Overspeed and starter
overcrank protection; 6) Run time hour meter; 7) Full engine
instrumentation; 8) Battery charger, 10 Amp. 25 KW units require three
position selector switch off/manual/auto. WEATHER PROTECTIVE SOUND
ATTENUATED ENCLOSURE: 25 KW units and 50 KW unit: 1) Sound attenuation
76 dBA or less at 25 feet; 2) 12 gauge galvanized steel or stronger;
3) Stainless steel hardware; 4) Access doors to engine, generator, and
controls; 5) Double wall fuel tanks with spill and low level warning
systems, UL approved a) 75 gallon minimum capacity for 25 KW units; b)
100 gallon minimum capacity for 50 KW units. TRAILER: 25 KW units and
50 KW unit: 1) Meets or exceeds all DOT and California DMV regulations
for highway and off road use; 2) Adjustable G/I Pintel hitch; 3) Swivel
jack; 4) Surge brakes; 5) Stop, turn, tail, and running lights with
standard 7 pin trailer connector 6) Vibration isolation system between
trailer and generator assembly; 7) Minimum weight capacity 5000 pound.
Weight capacity of trailer must exceed total wet weight of generator
unit with enclosure and full tank of fuel by at least 15% a) Single
axle for 25 KW units; b) Tandem axle for 50 KW unit. ADDITIONAL ITEMS:
1) Three (3) sets manuals, (each set includes Service/maintenance,
parts, and operation manuals) for 25 KW unit; 2) Three (3) sets
manuals, (each set includes Service/maintenance, parts, and operation
manuals) for 50 KW unit; 3) All units will meet applicable requirements
of the SCAQMD, will be pre-approved as certified equipment, will be
EPA-certified as required under 40 CFR Part 89. The contractor shall
provide the engine family name and documentation that a Certificate of
Competency has been obtained from EPA for the engine model year
provided of either 1998 or 1999; 4) Detailed Standard warranty
information will be provided in the proposal; 5) Optional/extended
warranty and pricing information shall be provided in the proposal. End
of Part 1 of a 2 Part Synopsis. (0099) Loren Data Corp. http://www.ld.com (SYN# 0301 19980413\61-0011.SOL)