Conduct baseline industrial ventilation survey for 21 ventilation
systems as required by 29 CFR and AFOSH 161-17. Location: 161 ARW, 3200
E. Old Tower Road, Phoenix, AZ. 85034-7263. Individual site locations
to be determined. Per Diem and Travel expenses will not be included in
award. Vendor is responsible for all costs incurred outside the scope
of work. All systems must meet the following criteria: Verify system
parameters are within 10% of design criteria; detailed survey plan
delivered within 30 days of award. Survey plan must contain minimum
components: Diagram of vent system, duct size and sampling locations;
Identifications of sampling parameters; Identifications of formulas to
be used and references to source literature; Dimensions of all system
openings and the associated cross-sectional area of each system
opening; Physical location, description, and intended use of the
system; Blower design parameters, voltage, amperage, CFM, size, type
and flow direction; Identification of the target contaminates for each
system; Description of the sampling protocol; the plan will be
submitted for approval by 161 BES before the survey is conducted. All
systems to be marked for location of measurement. Measurement equipment
to be identified by; Company name, Model number, Serial number,
Accuracy of equipment, last calibration date, calibration due date,
standard used to calibrate instrument, date primary standard due
calibration. 161 BES staff will observe the surveys. Contractor must be
available to conduct survey within 10 days after notification that vent
system is operational. System completion date schedule to be provided
at time of award. A full detailed report will be provided to the 161st
BES within 10 working days. Report to include: Comparison of actual
measurements to design criteria; All formulas used showing calculations
and answers for all parameters; Evaluation of system performance and
identification if system is less than 90% of design criteria; Identify
if system is appropriate or not for intended use. If system will not
control target contaminate or is less than 90% recommend corrective
actions. Posted 06/30/98 (0181) Loren Data Corp. http://www.ld.com (SYN# 0034 19980702\H-0001.SOL)