COMMERCE BUSINESS DAILY ISSUE OF JULY 29,1998 PSA#2147355 CONS/LGCS, 3180 S Craycroft Road, Davis-Monthan AFB, AZ 85707-3522 N -- INSTALL SECURE DATA AND ELECTRICAL SERVICE TO TWENTY-EIGHT (28)
FLOOR JACKS. SOL F02601-98-T1098 DUE 081298 POC TSgt Nanci Pigeon,
Contracting Specialist, 520-228-5476/J .L. Dantzler III, Contracting
Officer, 520-228-3598 WEB: Click here to view solicitation on the 355
CONS Business, http://www.dm.af.mil/355cons/355cons.htm. E-MAIL: Click
here to e-mail the Contracting Specialist, pigeonn@cons355.dm.af.mil.
N59 -- This is a combined synopsis/solicitation for commercial items
prepared in accordance with the format in FAR subpart 12.6, as
supplemented with additional information included in this notice. This
announcement constitutes the only solicitation; proposals are being
requested and a written solicitation will not be issued. (1)
Solicitation F02601-98-T1098 is being issued as a Request for Quote
(RFQ) (2) This solicitation incorporates clauses and provisions in
effect through the Federal Acquisition Circular 97-05. (3) This
acquisition is set aside 100% for small business. Standard Industrial
Code (SIC) 4931 ($5M) Electric and other services combined. (4) N/A (5)
Install twenty-eight (28) floor jacks, the floor jacks will include the
following connections SIPRNET, NIPRNET, phone line and power jacks.
Provide four (4) Allied Telesys hubs (P/N AT-3726TR-10) and two (2)
Allied Telesys Modules (P/N AT-3701FSC02) for fiber connections to
NIPRNET and SIPRNET networks. Provide seperate conduit runs fortwo (2)
each data outlets (10/100BaseT/RJ-45), one voice outlet (RJ-1), and
one electrical outlet (two (2) outlet jack) routed to surface mount box
in access floor. The SIPRNET R-45 jack should be red in color and the
NIPRNET RJ-45 jack should be green in color. Route data and phone lines
back to communications closet. Electrical service will utilize existing
circuits already present under floor. Utilize Category 5 plenum cable
and jacks for communications. Mount Allied hubs in communications
closet and provide for connectivity to hub from floor jacks. Phone
lines will be routed back to communications closet and terminated on
punch block. The installation will be completed in accordance with
TIA/EIA and DOD installation standards. Testing and documentation will
be turned in within five (5) days of installation. Provide copies of
final equipment layout and wiring diagram (as built one line diagrams)
within five (5) days of installation. (6) Estimated completion date is
4 September 1998. (7) The provisions 52.212.-1, Instructions to
Offerers-Commercial, applies to this acquisition. (8) Solicitation
incorporates by reference FAR 52.212-4, 52.212-3, and 52.212-5. (9)
Note 1 applies. Offers are due 12 August 1998 at 2 PM PST. Site visit
is scheduled for 5 August 1998 at 9:30 AM PST. Any inquiries shall be
in writing via e-mail or fax, no telephone inquiries will be accepted.
FAX number is 520-228-5284***** Posted 07/27/98 (W-SN228915). (0208) Loren Data Corp. http://www.ld.com (SYN# 0058 19980729\N-0003.SOL)