COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 3,1998 PSA#2173National Institute of Standards & Technology, Acquisition & Assistance
Div., Bldg. 301, Rm B117, Gaithersburg, MD 20899 59 -- DRAW OUT LOW VOLTAGE AIR CIRCUIT BREAKERS SOL 53SBNB860146 DUE
090798 POC Contract Specialist, Tamara Grinspon -- (301) 975-4390 --
Contracting Officer, David J. Orris -- (301) 975-4154 WEB: NIST
Contracts Homepage, http://www.nist.gov/admin/od/contract/contract.htm.
E-MAIL: NIST Contracts Office, Contract@nist.gov. Solicitation Number
53SBNB860146 is hereby modified as follows: The due date for receipt of
quotations by the National Institute of Standards and Technology (NIST)
has been changed. The new due date is September 7, 1998.*****Technical
questions have been raised with respect to the combined
synopsis/solicitation published in the Commerce Business Daily on
August 20, 1998. These questions (Q), each followed by the respective
answer (A), are as follows: Re: CLIN Item 001-Westinghouse DB-75: (Q1)
Is the circuit breaker electrically or mechanically operated? (A1)
Electro/Mechanical -- Closed by a D.C. coil; opened by springs
electronically tripped.*** (Q2) If electrically operated, what are the
control voltages? (A2) Coil Rating -- 125 volts D.C. ***(Q3) If
electrically operated, are there any accessories (U.V.R. or Bell
alarms)? (A3) Auxiliary contacts for "open" and "closed". *** (Q4)
Mounting. Is the breaker a bolt-in, 1 position, or 3 position? (A4) 3
position- open, test, closed.***(Q5) If electrically operated, do you
have a print or connection diagram #? (A5) No print or diagram
available.***Re: CLIN Item 002-Westinghouse DB-50: (Q6) Is the circuit
breaker electrically or mechanically operated? (A6) Electro/Mechanical
-- closed by D.C. Coil; opened by springs, electronically tripped.***
(Q7) If electrically operated, what are the control voltages? (A7) Coil
rating -- 125 volts D.C.*** (Q8) If electrically operated, are there
any accessories (U.V.R. or Bell Alarms)? (A8) Auxiliary contacts for
"open" and "closed". *** (Q9) Mounting. Is the breaker a bolt-in, 1
position, or 3 position? (A9) 3 position -- open, test, closed.***
(Q10) If electrically operated, do you have a print or connection
diagram #? (A10) No print or diagram available.*** Re: CLIN Item
008-Carriere Kit: (Q11) You have "CT rating 1800/600 amp". Does that
slash mean you want a multi-tap CT? (A11) The Carriere "CT" required is
a multi-tap sensor designed to function with the required Carriere
static trip unit.*****All interested, responsible firms should submit
quotes, by 3:00 PM, Washington, DC time, on September 7, 1998, to the
National Institute of Standards and Technology, Acquisition and
Assistance Division, ATTN: Tamara Grinspon, Building 301, Room B117,
Gaithersburg, Maryland 20899-0001. Faxed quotes will NOT be accepted.
Posted 09/01/98 (W-SN244309). (0244) Loren Data Corp. http://www.ld.com (SYN# 0313 19980903\59-0008.SOL)
59 - Electrical and Electronic Equipment Components Index Page
|
|