COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 14,1998 PSA#217942d Contracting Squadron/LGC, 50 Lemay Plaza South, Bldg 804, Maxwell
AFB, AL 36112-6334 41 -- FURNISH A 170 TON CENTRIFUGAL (R-123) CHILLER SOL
F01600-98-Q1698 DUE 092498 POC Mary Lou Crook, 334-953-2560 E-MAIL:
mary.crook@max2.maxwell.af.mil, mary.crook@max2.maxwell.af.mil. This is
a combined synopsis/solicitation for commercial items prepared in
accordance with the format in Subpart 12.6, as supplemented with
additional information included in this notice. This announcement
constitutes the only solicitation; quotations are being requested and
a written solicitation will not be issued. This synopsis/solicitation
is issued as a Request for Proposal (RFP).. Simplified acquisition
procedures shall be utilized. This solicitation and incorporated
provisions are those in effect through FAC 97-05 and DAC 91-13.
Reference Solicitation Number: F01600-98-Q1698. This acquisition is to
purchase a new 170 ton centrifugal (R-123) chiller in accordance with
the following minimum specifications: The 170-ton chiller performance
shall be certified in accordance with ARI Standard 550-92. The sound
pressure shall be measured in accordance with ARI Standard 575-87. The
following items shall be included. 1) Industrial design centrifugal
compressor; (2) MicroComputer control panel with the following safety
and control features: 1) alphanumeric display annunciates the following
operating parameters: entering and leaving chilled water temperatures;
entering and leaving condenser water temperatures, refrigerant
pressures, oil pressure differential, percent motor current, 2) digital
keypad entry allow for programming of: leaving chilled water, percent
current limit (40% to 100%), automatic load limiting on start-up (400%
to 100%, 1 to 255 minutes) time remaining in load limiting cycle
displayed; 7day/24hour start/stop schedule with holiday function;
Allowable range of chilled water temperature reset for DDC system and
automatic printout function of operating log, 3) interface capabilities
for: chilled water pump start/stop, condenser water pump start/stop,
chilled water reset from an external signal, cycling shutdown
annunciator "Run" signal; Remote "Ready to Start" signal, Printer to
provide hard copy of log reports, alarins, etc, 4) alphanumeric display
annunciates the following safety and cycling shutdowns and warning
conditions. Time and day of safety/cycling shutdown and type of restart
required (automatic or manual) annunciated: low water temperature,
Power fault, high compressor discharge temperature high oil pressure,
low oil pressure, low evaporator pressure, high condenser pressure,
motor starter shutdown, chilled water pump interlock, remote stop (from
DDC system), high condenser pressure limit in effect, low evaporator
pressure limit in effect. Evaporator differential pressure switch;
Evaporator factory insulated; Current limit and temperature reset
interface boards; Condenser water readout; Factory mounted solid state
starter. Factory piped, refrigerant cooled oil cooler;. HCFC-123
refrigerant charge.; Marine water box on condenser. Start-up and
training of operational personnel shall be included as separate pricing
with the submission of your offer. The start-up and training will be
conducted on-site. Delivery date and place of delivery shall be not
later than 90 days after receipt of purchase order. Inspection and
delivery shall be at FOB destination point; 42CES/CEOG, 115 South
Butler Street, MAFB-Gunter Annex, AL 36114. Warranty provisions and
installation information shall be included with your offer. The
Government will award a contract resulting from this solicitation to
the responsible offeror whose offer conforming to the solicitation will
be most advantageous to the Government. The following provisions and
clauses apply to this acquisition: 52.512-1, Instructions to
Offerors-Commercial; 52.212-2, Evaluation-Commercial items, The
specific evaluation criteria under paragraph (a) of FAR 52.212-2 are:
(a) price; (b) technically acceptable; (c) past performance. All
evaluation factors other than price when combined is approximately
equal to price. 52.212-3, Offerors Representations and Certifications
Commercial Items (Offerors must include a completed copy with their
offer) and must accompany the offeror's quote; 52.212-4, Contract Terms
and Conditions Commercial Items; 52.212-5, Contract Terms and
Conditions Required to Implement Statutes or Executive Orders
Commercial Items; 52.222-26, Equal Opportunity; 52.222-35, Affirmative
Action for Special Disabled and Vietnam Era Veterans; 52.222-36,
Affirmative Action for Handicapped Workers, 52.222-37, Employment
Reports on Special Disabled Veterans and Veterans of the Vietnam Era.
The following DFAR provisions are hereby incorporated by reference;
252.204-7004, Required Central Contractor Registration (Lack of
registration in the CCR database will make an offeror/quoter ineligible
for award of a contract/purchase order. Please ensure compliance with
this regulation when submitting your quote. Call
888-227-2423/800-841-4431 for more information) and 252.232-7009,
Payment by Electronic Funds Transfer, (CCR). The SIC Code is 3585.
Small Business Size; 750 employees. This acquisition is an unrestricted
purchase. CLIN: 0001: quantity: 1 each; (give unit price) CLIN: 0002:
Installation of Chiller -- quantity: 1 job; CLIN 0003: Training:
quantity: 1 job,CLIN 0004: Start-Up: quantity: 1 job. An award will be
made to the responsible offeror whose offer conforms with all
requirements of this solicitation. The CLIN's awarded will be subject
to availability of funds. Preference will be given to those quotations
based on Federal Supply Schedules: Offerors should include GSA
contract number, expiration date, terms and conditions of specific GSA
Schedule and item description with specifications that comply with the
item described above. The quotation shall be submitted not later than
3:00 p.m. CDT, 24 September 1998. Point of contact is 2Lt Chad Nichols
at (334) 953-3593 and Mary Lou Crook, Contracting Officer (334)
953-2560. If a site visit is required, please contact 2Lt Chad Nichols
no later than 22 September 1998 and arrangements will be made (prior
to submission of offer). All responsible sources may submit an offer,
which shall be considered by the agency. Posted 09/10/98 (W-SN248290).
(0253) Loren Data Corp. http://www.ld.com (SYN# 0255 19980914\41-0003.SOL)
41 - Refrigeration, Air Condition and Air Circulating Equipment Index Page
|
|