COMMERCE BUSINESS DAILY ISSUE OF NOVEMBER 18,1998 PSA#2224Navy Public Works Center, 2730 McKean St, Ste 1, San Diego, CA
92136-5294 61 -- MEDIUM VOLTAGE CABLE SOL N63387-99-Q-P014 DUE 120298 POC Cynthis
Horriatt, Purchasing Agent, (619)556-9051, FAX: (619)556-7775 3600 Feet
Medium Voltage cable. Size 4/0. Medium voltage cable shall be single
conductor, ehtylene propylene rubber (EPR) insulated; and shielded
power cable shall be rated at 15kv, 133 percent insulation level. The
cable shall be capable of operating continuously in both wet and dry
locations at 90 degree C for normal operation, 130 degree C under
emergency operating conditions and 250 degree C under short circuit
conditions. The conductor shield, insulation and insulation shield
shall be applied continuously in the same pass by an in-line triple
extrusion process. The cable shall be insulated, jacketed, and tested
in accordance with AEIC CS6, in the same plant by the same
manufacturer. Certified AEIC qualification data shall be required prior
to order placement. Cable ends must be sealed. Conductor shall be class
B stranded annealed copper per part 2 of ICEA S-68-516. Conductor
shield shall be extruded black, semi-conducting thermosetting compound
thermally and chemically compatible with the conductor and the
insulation applied over the conductor. Conductor shield shall be
uniformly and firmly bonded to the overlying insulation and be free
stripping from the conductor. The thickness of the conductor shield
shall conform to AEIC CS6. Insulation shall be EPR conforming to AEIC
CS6 and shall have a minimum average thickness of 220 mils. The
ethylene content of the EP compound shall not exceed 72 percent by
weight. Insulation shield shall be extruded black, semi-conducting
thermosetting compound thermally and chemically compatible with the
insulation and the copper tape applied directly over the insulation.
The insulation shield shall be free stripping, leaving no conductor
particles or other residual on the insulation surface. The thickness of
the insulation shield shall conform to AEIC CS6. Copper tape shield
shall have a thickness of 5 mils, helicaly applied over the insulation
shield with a minimum of 12 percent overlap. Jacket shall be
chlorosulfinated polyethylene (HYPOLON) with a minimum thickness of 80
mils. Cable to be supplied on three reels of 1200 feet each. 3600 FEET
Medium voltage cable. Size 350 MCM. Medium voltage cable shall be
single conductor, ehtylene propylene rubber (EPR) insulated; and
shielded power cable shall be rated at 15kv, 133 percent insulation
level. The cable shall be capable of operating continuously in both wet
and dry locations at 90 degree C for normal operation, 130 degree C
under emergency operating conditions and 250 degree C under short
circuit conditions. The conductor shield, insulation and insulation
shield shall be applied continuously in the same pass by an in-line
triple extrusion process. The cable shall be insulated, jacketed, and
tested in accordance with AEIC CS6, in the same plant by the same
manufacturer. Certified AEIC qualification data shall be required prior
to order placement. Cable ends must be sealed. Conductor shall be class
B stranded annealed copper per part 2 of ICEA S-68-516. Conductor
shield shall be extruded black, semi-conducting thermosetting compound
thermally and chemically compatible with the conductor and the
insulation applied over the conductor. Conductor shield shall be
uniformly and firmly bonded to the overlying insulation and be free
stripping from the conductor. The thickness of the conductor shield
shall conform to AEIC CS6. Insulation shall be EPR conforming to AEIC
CS6 and shall have a minimum average thickness of 220 mils. The
ethylene content of the EP compound shall not exceed 72 percent by
weight. Insulation shield shall be extruded black, semi-conducting
thermosetting compound thermally and chemically compatible with the
insulation and the copper tape applied directly over the insulation.
The insulation shield shall be free stripping, leaving no conductor
particles or other residual on the insulation surface. The thickness of
the insulation shield shall conform to AEIC CS6. Copper tape shield
shall have a thickness of 5 mils, helicaly applied over the insulation
shield with a minimum of 12 percent overlap. Jacket shall be
chlorosulfinated polyethylene (HYPOLON) with a minimum thickness of 80
mils. Cable to be supplied on three reels of 1200 feet each. Price to
include shipping to 32nd Street Naval Station in San Diego, CA. This
is a combination synopsis/RFQ; no solicitations will be sent out.
Acceptance of bids for this announcement will close on 2 December 1998
at 4:00 PM PST. FAX or mail quotes will be accepted. Mail quotes will
not be accepted. See Numbered Note(s): 1. Posted 11/16/98
(W-SN271820). (0320) Loren Data Corp. http://www.ld.com (SYN# 0255 19981118\61-0002.SOL)