|
COMMERCE BUSINESS DAILY ISSUE OF DECEMBER 24,1998 PSA#2249National Cancer Institute, Research Contracts Branch, PSAS, 6120
Executive Blvd, EPS/Room 638, Bethesda, MD 20892-7227 63 -- ALARM, SIGNAL & SECURITY DETECTION EQUIPMENT SOL RFQ-NCI-90021
DUE 010899 POC Cynthia Brown, Purchasing Agent, 301-402-4509, Todd
Cole, Contracting Officer RFQ-NCI-90021-NQ for "Alarm, Signal &
Security Detection Equipment," which was issued as a combined
synopsis/solicitation in the Commerce Business Daily (CBDNet) on
November 30, 1998 and subsequently amended on December 15, 1998, is
hereby amended to provide clarification and answers to questions raised
by prospective offerors. Per the previous amendment, a deadline for
additional questions was set for December 30, 1998 and remains
unchanged. After the foregoing deadline for additional questions has
passed, there is no guarantee that a timely response will be
forthcoming prior to the due date of proposals which is now 3:00 PM EST
on January 8, 1999. Clarifications: The following sentence: "The
National Cancer Institute (NCI) requires the ability to monitor, in a
quantitative fashion, specimen freezer temperatures." is revised to
read as follows: "The National Cancer Institute (NCI) requires the
ability to monitor, in a quantitative fashion, equipment temperatures."
Also, within FAR Clause 52.213-4, Year 2000 Compliance is applicable to
this acquisition and required for each item of hardware, software, and
firmware that may be purchased. Questions From Offerors: Question 1.:
The specifications require the system to control up to 64 outputs.
Please explain the interrelation between the 128 inputs and the 64
outputs of the system. For example, does the user have to be able to
program the function determining the state of the digital outputs based
on information from the inputs? Please elaborate on the functions of
the 64 digital outputs that will be controlling? Answer 1.: The outputs
referenced are not necessarily "digital" and are not described as such.
NCI wants to provide offerors flexibility in meeting the requirement.
There is no direct relation between the 128 inputs and the 64 outputs.
The number of inputs and outputs are based on the current need and the
ability to expand the system in the future. Question 2.: Please define
at which temperature ranges 0.1C resolution will be required? Answer
2: The requirement is that the system includes the standard 8 bit A/D
converter. The ability to upgrade to a 12 bit A/D converter to provide
.1 degree centigrade resolution is desireable, but it is not a
requirement and this ability to upgrade will not be evaluated.
Therefore, further definition cannot be provided at this time. Question
3.: Please explain the requirement of comingling the security
monitoring and temperature monitoring into the same PC? Are there
specific functions that require these two systems to integrate? Answer
3.: The requirement for co-mingling the security and equipment
monitoring systems is functional. The guard station where the
monitoring equipment will be located is relatively small and lacks
space for additional hardware. Therefore, both systems shall reside on
the same Personal Computer (PC). Question 4.: Please define the
requirement for inputs to be field programmable to address various
monitoring issues. What are NCI's future monitoring needs? Answer 4.:
The requirement for field programming of inputs is based on
environmental elements that are commonly monitored within a research
environment (e.g., temperature, humidity, etc.). The NCI
researchers/technicians may wish to be able to attach additional
devices to measure environmental elements such as humidity and adjust
the settings for the environmental element being measured. Question 5.:
Please provide a floorplan indicating the location of each piece of
equipment to be monitored, along with its operating temperature range.
Answer 5.: The Advanced Technology Center containing the monitored
equipment is undergoing renovations. A floor plan is available which
shows the general locations of the monitored equipment and the
approximate square footage of the facility. To receive a copy of the
floor plan, contact Cynthia Brown at (301)402-4509. A copy will be
faxed and Federal Expressed to you. Question 6.: Please describe how
NCI envisions an alarm being responded to in this application. Please
include your expected response procedure during both business and
non-business hours. Answer 6.: The security guard will monitor the
terminal screen and follow established written procedures during
alarms. Question 7.: Please elaborate on NCI's requirement for off-site
notification for alarms. Under which situations does NCI need this
capability? Answer 7.: Currently, there is no requirement for offsite
notification. However, the system shall provide the capability for
off-site notification of alarms through the telephone to use this
feature if it becomes necessary. Question 8.: Please elaborate on the
need for prioritizing alarms? What does NCI hope to accomplish with
this capability? Answer 8: There are commonly pieces of equipment
(points) that require attention prior to others in a research
environment. Therefore, certain points will be more important than
others. NCI requires the ability to sequence (prioritize) all monitored
equipment points in case multiple alarms occur simultaneously. Question
9.: Is it considered acceptable for the intended application, for a
single point failure in the monitoring system's hardware or software to
cause a complete system shutdown or a complete loss of data collection
capability? Answer 9.: This issue is not addressed in the
specifications, and backup measures to prevent such occurrences are
therefore not required. However, each system shall provide a warranty
and shall be installed properly to minimize the likelihood of such
shutdowns and loss of data. Question 10.: Is it considered acceptable
for a single point failure in the monitoring system's hardware or
software to go undetected by the system resulting in no indication of
the failure to a human being? Answer 10.: While routine and repetitive
point failures are not acceptable, additional measures such as backups
to prevent such occurrences are not required. However, each system
shall provide a warranty and shall be installed properly so as to
minimize the likelihood of such failures. Question 11.: Is the
possibility of data loss due to a system failure acceptable? Answer
11.: Routine system failures are not acceptable; therefore, data loss
in such a context is not acceptable. However, special back-up features
to prevent data loss are not required. Each system shall provide a
warranty and shall be installed properly to minimize the likelihood of
system failures and subsequent loss of data. Question 12.: Is it
acceptable for on premisis alarm indication to occur at only one
location so that, in the event of an undetected failure of that
recording apparatus, no information will be recorded? Answer 12.:
Undetected failures resulting from incorrect installation of the system
are not acceptable. However,the alarm only needs to be received at the
system site (i.e. the security guard's PC). Each system shall provide
a warranty and shall be installed properly so as to minimize the
likelihood of system failures and subsequent loss of data. Question
13.: Is the possibility of radio or magnetic interference, induced onto
wires carrying analog signals, causing incorrect data readings or false
alarms acceptable? Answer 13.: The scientific equipment will be located
in areas without significant interference. Therefore, the systems
offered do not have to include special features to safeguard against
such interference. However, disturbances from incorrect installation of
the system are not acceptable. Question 14.: How important is the
adherence of a monitoring system to Clinical Laboratory Standards in
meeting the goals of the Advanced Technology Center? Answer 14.: The
NCI equipment being monitored is not located in a clinical or patient
care area. Clinical Laboratory Standards are not relevant or required.
Question 15.: Are factors such as mean time between failure important
in the decision to purchase off the shelf items? Answer 15.: This
issue is not addressed in the specifications and is not important to
this purchase. Each system shall provide a one-year warranty and shall
be installed properly so as to minimize the concern for mean time
between failures Posted 12/22/98 (W-SN282599). (0356) Loren Data Corp. http://www.ld.com (SYN# 0336 19981224\63-0003.SOL)
63 - Alarm, Signal and Security Detection Systems Index Page
|
|