COMMERCE BUSINESS DAILY ISSUE OF JANUARY 19,1999 PSA#2264Fleet and Industrial Supply Center, Puget Sound, Bldg 467 W Street,
Code 200 Bid Desk, Bremerton, WA 98314-0051 66 -- LOAD BANKS REACTIVE SOL N00406-99-R-5078 DUE 030199 POC Maureen
Renville (360)476-7174 E-MAIL: Contracting Officer,
maureen_renville@puget.fisc.navy.mil. Load Banks Reactive, 1 EACH
1000KW. Transportable, electical load bank designed and costructed for
post overhaul testing of sundry shipboard electrical machinery.
Equipment shall perform continuously under any load condition including
full rated load. Overall size and weight shall not exceed 8 ft wide, 16
ft long and 8.5 ft high maximum; 18,000 lbs max. Load bank shall
provide the minimum, continuous duty, ungounded load capacities: 1000KW
-- 460V, 3 phase 3 wire; 500 KW, 460V, 1 phase 2 wire 60 Hertz; 284 KW,
240V, 3 phase 3 wire; 500 KW, 460V, 1 phase 2 wire 60 Hertz; 71 KW,
120V, 3 phase 3 wire 60 Hertz; 213 KW 120V, 3 phase 3 wire 60 Hertz;
925 KW, 250V Direct Current, 2 wire; 617 KW, 500V, Direct Current, 2
wire. Load Banks Reactive, 1 EACH 500KW. Transportable, electical load
bank designed and constructed for post overhaul testing of sundry
shipboard electrical machinery. Equipment shall perform continuously
under any load condition including full rated load. Overall size and
weight shall not exceed 8 ft wide, 16 ft long and 8.5 ft high maximum;
18,000 lbs max. Load bank shall provide the minimum, continuous duty,
ungounded load capacities: 500 KW, 460V 3 phase 3 wire, 60 Hertz; 426
KW, 120V, 3 phase 3 wire 60 Hertz; 35 KW, 120V, 3 phase 3 wire 60
Hertz; 106KW, 120V, 1 phase, 2 wire 60 Hertz; 460V 250 direct current,
2 wire; 398 KW, 500V direct current, 2 wire. For both load banks,
design and construction shall be considerate of operating and storing
the equipment, without added protection, under any combination of the
following ambient conditions without loss of capacity: Elev 50 ft below
to 100 ft above mean seal level; temp 32 to 104 degrees F; Relative
humidity 0 to 100%; wind 0 to 100 MPH; unusual service conditions: salt
water spray, direct exposure to sunlight, contaminated industrial
environment including dust, fumes, smoke, blast grit and inclement
weather wind driven rain and snow. This is a 100%_Small Business
Set-Aside. Required delivery is 180 days after effective date of
contract. Inspection at source, acceptance at destination. FOB Puget
Sound Naval Shipyard, Bremerton WA 98314-5000. For Foreign Military
Sales. NOTES: _1, 9, 12, 26__ apply. All responsible sources may submit
offer/bid which shall be considered by FISC Puget Sound. Telephone
requests will not be honore. Fax requests will be accepted at
360-476-2931. Posted 01/14/99 (W-SN288103). (0014) Loren Data Corp. http://www.ld.com (SYN# 0242 19990119\66-0004.SOL)