COMMERCE BUSINESS DAILY ISSUE OF MAY 6,1999 PSA#2340USDI, Bureau of Reclamation, Northern California Area Office, 16349
Shasta Dam Blvd., Shasta Lake, CA 96019-8400 61 -- POWER TRANSFORMER SOL 99SQ230006 POC Sam Varner, (530)275-3091
WEB: click here to electronically access the solicitation,
http://ideasec.usgs.gov. E-MAIL: click here to contact the agency point
of contact, svarner@mp.usbr.gov. The transformer shall be indoor
ventilated dry type, self cooled, NEMA Class AA, with Class H
insulation and shall conform to the applicable and latest requirements
of ANSI C57.12.00 and C57.12.90, NEMA Publication No. TR1 and NEMA
Publication No. TR27 "Commercial, Institutional and Industrial Dry-Type
Transformers." The power transformer shall be provided with a high
voltage terminal box on the front side and a low voltage terminal box
on the rear side. Cable entries in both cases will be from the top. The
ratings and characteristics of the transformer shall be as follows:
Normal continuous self cooled rating...2500 kVA Frequency...60 Hertz
Number of phases...3 High voltage (rated)...13,800 volts Low voltage
(rated)...2,300 volts High voltage winding connection...Delta Low
voltage winding connection...Delta Impedance (maximum)...5.75 percent
BIL requirements high voltage (minimum)...95 kV High voltage taps at
rated kilovoltampere capacity...Four at 2-1/2 percent Low voltage
taps...None Sound level (maximum)...68 dB Temperature rise (above 40
degree C ambient)...150 degree C (maximum) Dimensions (not to
exceed)...96" high by 84" wide by 84" deep Insulation...Dry type,
vacuum pressure impregnated Winding and bus material...Copper At the
time of this notice, the solicitation response date has not been
determined. The estimated issuance date of the solicitation is May 25,
1999 with responses due by June 11, 1999. Delivery of the transformer
shall be 75 days after issuance of order. See Note 1. Posted 05/04/99
(W-SN327605). (0124) Loren Data Corp. http://www.ld.com (SYN# 0301 19990506\61-0005.SOL)
61 - Electric Wire and Power and Distribution Equipment Index Page
|
|