COMMERCE BUSINESS DAILY ISSUE OF MAY 7,1999 PSA#234190th Contracting Squadron, 7505 Marne Loop, F.E. Warren AFB, WY 82005 66 -- SENSORS, RELAYS, TRANSDUCERS, CONTROL PANELS & POINT TERMINATION
STRIPS SOL FB461399T0646 DUE 060799 POC Contact Kelly Snyder,
307-773-4740, Contracting Officer or Jim Clark, 307-773-4739,
Contracting Specialist PART: U.S. Government Procurements SUBPART:
Commodities CLASSCOD: 66-Pressure, Temperature, Humidity
Measuring/Controlling Instruments OFFADD: 90th Contracting Squadron,
7505 Marne Loop, F.E. Warren AFB, WY 82005 SUBJECT: 66-SENSORS, RELAYS,
TRANSDUCERS, CONTROL PANELS & POINT TERMINATION STRIPS SOL
F48608-99-T0646 DUE 060799 POC Jim Clark (307) 773-4739 DESC: 17. This
is a combined synopsis/solicitation for commercial items prepared per
the format in Subpart 12, as supplemented with additional information
included in this notice. This announcement constitutes the only
solicitation; proposals are being requested and a written solicitation
will not be issued. Solicitation number for this RFQ: F48608-99-T0646;
is a Request For Quote (RFQ) The following Provisions and Clauses are
incorporated into this RFQ by reference and are in effect through
Federal Acquisition Circular 90-45, dated 1 January, 1997. No addenda
apply to these Provisions and Clauses. FAR 52.212-1, Instructions to
offerors-Commercial Items FAR 52.212-3, Offeror Representation and
Certifications -- Commercial Items to include Alternate I & Alternate
II FAR 52.212-4 Contract Terms and Conditions-Commercial Items FAR
52.212-5, Contract Terms and Conditions Required to Implement Statutes
or Executive Orders-Commercial Items No additional FAR clauses apply.
This requirement is Set-Aside for Small Businesses. SIC 3822, 500
employees. INS requirement is: CLIN 0001 Room Sensor (LCD, Adjustable),
BAPI, BA/10K-2-RuP-303, 120 Ea; Room Sensor w/blank cover, BAPI,
BA/10K-2-R, 147 Ea; Room Sensor w/indicating cover, BAPI,BA/10K-2-R, 48
Ea; Room Sensor w/stainless cover, BAPI, BA/10K-2-SP, 137 Ea; Remote
Probe, 5', Refers, BAPI, BA/10K-2-RPP-5', 26 Ea; Duct Sensor, 12",
BAPI, BA/10K-2-D-12", 201 Ea; Duct Sensor, 18", BAPI, BA/10K-2-D-18",
83 Ea; Duct Temp Averaging Sensor, BAPI, BA/10K-2-A-24, 11 Ea;
Immersion Sensor, BAPI, BA/10K-2-1-4"-WP, 177 Ea; High Temp Water
Sensor, BAPI, BA/T1K2-1-4"-WP, 160 Ea; Outside Air Temp Sensor, BAPI,
BA/10K-2-0, 44 Ea; Duct Humidity, 2% accuracy, BAPI, BA/H220-D, 10 Ea;
Outside Humidity, 2% accuracy, BAPI, BA/H220-0, 1 Ea; Room Humidity,
2% accuracy, BAPI, BA/H220-R, 19 Ea; 4" Thermowell, BAPI, BA/4"M304,
325 Ea; CO Sensor, EIT, 4582-1-2, 10 Ea; High Current Sensor, 0-300a,
Veris, H221, 15 Ea; High Current Sensor, 0-800a, Veris, H321, 15 Ea;
High Current Sensor, 0-2400a, Veris, H421, 9 Ea; Status Switch Current
Sensing, Veris, H-708, 173 Ea; Relay, current proofing, Veris, H-735,
229 Ea; 0-20ma to 0-15PSI E-P Transducer, ACT, PXP2.2FS, 150 Ea; Low
Pressure Steam PSI 0-30# range, Kele, PSS-05-E, 28 Ea; High Pressure
Steam PSI 0-300a range, Mamac, PR264R2MA, 1 Ea; Filter or Start/Stop
Proof Air Switch, Cleveland Controls, DPS-10, 79 Ea; Start/Stop Relay-
Relay in Box, Functional Devices, RIBU1C, 12 Ea; Start/Stop Relay,
24VAC 10 amp w/base, IDEC, RH2B-ULCAC120V, 146 Ea; Air Pressure,
control air applications, 0-30psi, Mamas, PR264-R2-MA, 9 Ea;
Freezestat, Powers, 134-1504, 47 Ea; Bldg/Duct Static Pressure, Mamac,
PR274, 10 Ea; Pump Flow Proof Switch, Kete, P74FA-1, 3 Ea; 100VA
Transformer, 120Vac to 24Vac, Core, 120-024-100-2TF-CB, 195 Ea; Large
Control Panel, Landis & Staefa, 23 Ea; Medium Control Panel, Landis &
Staefa, 35 Ea; Small Control Panel, Landis & Staefa, 35 Ea; Point
Termination Strips, 5 screw terminals, Kele, 105SP, 20 Ea; Point
Termination Strips, 10 screw terminals, Kele, 110SP, 30 Ea; Point
Termination Strips, 15 screw terminals, Kele, 115SP, 40 Ea; Point
Termination Strips, 20 screw terminals, Kele, 120SP, 40 Ea; Point
Termination Strips, 25 screw terminals, Kele, 125SP, 130 Ea; Point
Termination Strips, 30 screw terminals, Kele, 130SP, 30 Ea; all sensors
4-20ma unless otherwise indicated; Engineering Specifications for CO
Sensor Transmitter: (1) Transmitter shall consist of a single unit with
a shell manufactured from a metal-impregnated spun epoxy material for
rejection of RF/EMI interference, (2) Transmitter circuits immersed in
epoxy for physical protection, (3) Transmitter shall operate on 24vac,
(4) Transmitter provides 4-20ma signal, (5) Sensor range of 0 to 100
ppm, (6) Sensor accuracy of 2% of full scale, (7) Sensor membraned,
amperometric, electrochemical cell-type requiring no sample pumps or
replacement of membranes and/or electrolyte, (8) Sensor replaceable,
not requiring alignment of pins, twist locks or other easily damaged
connectors, (9) Transmitter shall be certified to be intrinsically
safe, meeting requirements of CENELEC standard EN50.020 to Eex ia iiC
T6, CSA Class 2258 and CSA Class 4828. Engineering Specifications
0-20-ma to 0-15psig Transducer: (1) Transducer 0-20ma analog input, (2)
0-5vdc or 4-20ma feedback of branch pressure, (3) Bleed branch line
pressure on power failure, (4) Use a 24vac power, (5) Have accuracy of
3%, (6) Operating temp 32 to 120 degree F, (7) Use " OD (1/8" ID)
pneumatic tubing, (8) 3.5" L x 2.5" W x 1.5" H or less, (9) Mounted on
supplied snaptrack. Engineering Specifications Thermo Wells: (1)
Machined 304 stainless steel, (2) Except 4" x .25" sensor probe, (3)
Have standard " NPT, (4) Rated at 1000 degree F and 4000 psi and 100
fpm. Engineering Specifications Current Sensor/Command Relay: (1)
Induce powered from monitored load, (2) Combines a status sensor for
monitoring positive status and command relay for starting or stopping
motors in a single package, (3) Have integral N.O. command relay
capable of switching 5A resistive, 3A inductive @ 30VDC, 240 VAC, (4)
Adjustable operating range from 1-125A, (5) Provide visual indication
(LED) for sensor and relay status, (6) Adjustable trip set-point of
+/-1% of the range from -15 to 60 degree C, (7) Isolated to 600VAC rms,
(8) Adjustable mounting bracket for installation flexibility, (9)
Output N.O., solid state, 0.1A @ 30VAC/DC, (10) N.O., 5A resistive, 3A
inductive @ 30 VDC, 240VAC, (11) Solid core type w/hole size of 0.75"
D, (12) Dimensions 3.125" L X 2.15" W X 1.00" H. Engineering
Specifications Current Sensor: (1) Induce powered from monitored load,
(2) Adjustable operating range from 1-135A, (3) Visual indication
(LED) for output status and sensor power, (4) Adjustable trip set-point
of +/-1% of range from -15 to 60 degree C, (5) Isolated to 600 VAC rms,
(6) Adjustable mounting bracket for installation flexibility, (7)
Output N.O., solid state, 0.1A @ 30 VAC/DC, (8) Solid core type w/hole
size of 0.75" D, (9) Dimensions 3.125" L x 2.15" W x 1.00" H.
Engineering Specifications 4-20 mA High Amperage Analog Current Sensor
0-300amps: (1) Loop powered, (2) Split-core type w/removable latching
bar, (3) Three adjustable ranges of 100, 200 & 300A w/full scale
output of 20 mA, (4) Transducer accurate to +/- 2.0% of the reading
over a temperature range of -15 to 60 degree C, (5) Loop powered (10-30
VDC) and limited current draw of 30 mA, (6) Isolated to 600 V AC rms,
(7) Optional mounting bracket, (8) Current sensor output 4-20 mA, (9)
Hole size 1.25" W X .125" H, (10) Dimensions 3.75" L X 3/75" W X 1.10"
H. Engineering Specifications 4-20 mA High Amperage Analog Current
Sensor 0-800 Amps: (1) Loop powered, (2) Split-core type w/removable
latching bar for installation ease, (3) Three adjustable ranges of 300,
600 & 800A w/full scale output of 20 mA, (4) Accurate to +/-2.0% of
reading over temperature range of -15 to 60 degrees C, (5) Loop powered
(10-30 VDC) and limited current draw of 30 mA, (6) Isolated to 600 VAC
rms, (7) Optional mounting bracket, (8) Output 4-20 mA, (9) Hole size
1.25" W X .125" H, (10) Dimensions 5.38" L X 4.75" W X 1.10" H.
Engineering Specifications 4-20 mA High Amperage Analog Current Sensor
0-2400amps: (1) Loop powered, (2) Split-core type w/removable latching
bar, (3) Three adjustable ranges of 600, 1200 & 2400A w/full scale
output of 20 mA, (4) Transducer accurate to +/- 2.0% of reading over
temperature range of -15 to 60 degree C, (5) Loop powered and limited
current draw of 30 mA or less from 10-30 VDC, (6) Isolated to 600 VAC
rms, (7) Optional mounting bracket for installation flexibility, (8)
Output 4-20 mA, (9) Hole size 1.25" W x .125" H, (10) Dimensions 7.88"
L X 4.75" WX 1.10" H. Engineering Specifications Room, Refer, Duct,
Immersion & Outside Air Sensors: (1) 10,000 ohm thermistor, curve 2,
(2) Accuracy of 0.2 degree C (0-70 degree C), (3) Stability of +0.05%
per year over a 10 year period, (4) Room sensors use Delta style or
2X4" blank covers, (5) Adjustable room sensors software adjustable, (6)
Indicating covers LCD, (7) Operating range of -55 to 150 degree C, (8)
Duct & immersion sensors .25" D probes, (9) Probes 4" L. Engineering
Specifications Humidity Sensors: (1) 4-20ma output, 2% accuracy, (3)
Impedance type sensing element, (4) Room sensors use Delta style or 2X4
blank covers, (5) Operating range of 0-100%. Offerors shall state their
standard warranty they offer in response to this RFQ. Award will be
based on lowest price for all equipment. This RFQ closes at 2:00 P.M.
on 7 Jun 1999 POC is Jim Clark, Contracting Specialist (307) 773-4739
or Kelly Snyder, Contracting Officer (307) 773-4740.***** Posted
05/05/99 (W-SN328046). (0125) Loren Data Corp. http://www.ld.com (SYN# 0634 19990507\66-0016.SOL)