COMMERCE BUSINESS DAILY ISSUE OF MAY 7,1999 PSA#2341Military Sealift Command, Pacific, Code N-10, 140 Sylvester Road, San
Diego, CA 92106-3521 N -- INSTALLATION OF OUT DOOR BACK UP GENERATOR SOL N32205-99-R-6166
DUE 052199 POC Bea Appling at (619) 553-7688 or Fax at (619) 553-7695
E-MAIL: JoAnn.Yamane@smtpgw.msc.navy.mil,
Bea.Appling@smtpgw.msc.navy.mil. Amendment 0003: A pre-proposal site
visit is scheduled for 7 May 1999, 10:00 a.m., PST. All interested
parties shall meet at the entrance to the MSCPAC Building 570, SUBBASE,
Point Loma, San Diego, CA. Line Item 0001 description specified the
original synopsis dated 18 March 1999 is hereby deleted in its
entirety. Replace Line Item 0001 with the following information:
Contractor shall provide one (1) 125 kW Out-door Back-up Generator and
all labor and material necessary to complete the installation and
ensure full operation of the generator. In addition, the contractor
shall accomplish the following system modification; 1) Feeder 4-#500
kCM THWN in 3" rigid steel conduit, to replace existing. Re-use
existing control wiring. 2) A 100 Amp, 3-pole, 200 VAC disconnect, NEMA
3R to replace existing 100 Amp fusible disconnect. 3) 400 Ampere,
3-pole, 250 VAC automatic transfer switch to replace existing 100 Amp
automatic transfer switch. 4) 400 Amp, 3-phase, 4-wire 120/208V panel
board to handle all loads of proposed back-up generator. Panel board
shall contain 400 Amp main circuit breaker and two branch breakers (1)
rated 225 Amps, 3-pole and (1) rated 100 Amps, 3-pole. 5) Remove
existing 225A, 3P circuit breaker serving panel 'TPA' from existing
Panel 'PDP' and replace with new 400 Amp, 3-pole circuit breaker to
serve as normal power source to new ATS. Connect with (4) #500 kCM THWN
and #2 ground in 3-inch RGS. 6) Reroute circuits for Panel 'EM' and
Panel 'TP-A to new distribution panel. 7) Wire under floor receptacles
in Communication Room 209 to circuits #4 and #6 in Panel 'TPA'.
Reroute existing wiring. 8) Reroute existing wiring for under floor
outlets rated 30A-08V in Communication Room to Panel 'TPA-A'. Provide
l-30A, 2P circuit breaker in available space. 9) Remove existing under
floor outlets connected to Panel 'EM' at Third Floor. 10) Provide two
quad receptacles in Hub Room 308. Serve dedicated circuit. Connect to
Panel 'EM" -- circuits #13 and #15. 11) Relabel panel boards as
follows; (1) New distribution panel = 'EM', (2) Existing 'E ='EM-A',
(3) Existing 'TPA' = 'EM-B', (4) Existing 'TPA-A' = 'EM-Bl; 12) Label
all outlets affected by this modification. 13) Upon completion of the
installation, the contractor shall test the installed emergency
generator to ensure that the generator is fully operational and meets
the requirements of the solicitation, technical attachments, state,
federal, and industry codes/regulations. FAR 5.212-5, Contract Terms
and Conditions Required to Implement Statues or Executive Orders
Commercial Items is modified to include FAR 52.222-41, Service Contract
Act of 1965, As Amended. Contractors shall contact Bea Appling (619)
553-7688 for Technical Attachment (1)-U. S. Department of Labor Wage
Determination #94-2057, Revision No. 19, dated 23 Jul 1998, Technical
Attachment (2)-Generator Specification Sheet, Technical Attachment
(3)-Load Survey/Projected Load Survey, Technical Attachment
(4)-Electrical Drawings. The closing date for this requirement is set
for 21 May 1999, 11:00 a.m., PST. Posted 04/28/99 (W-SN325583). (0118) Loren Data Corp. http://www.ld.com (SYN# 0117 19990507\N-0003.SOL)