COMMERCE BUSINESS DAILY ISSUE OF MAY 28,1999 PSA#2356Directorate of Contracting, Contract Support Team, Attn: ATZR-QD, PO
Box 33501, Bldg 1950, Fort Sill OK 73503-0501 Z -- REPLACE HEATING AND COOLING WITH GEOTHERMAL HEAT PUMP, FORT SILL,
OK SOL NG-00043-9P POC Dewayne Cochrane 580-442-3225 WEB: click here to
download a copy of the RFP, http://sill-www.army.mil/doc/doc_home.htm.
POINT OF CONTACT: Dewayne Cochrane (cochrand@doimex1.sill.army.mil)
VOICE 580-442-4315 FAX 580-442-4621 May 26, 1999 REQUEST FOR TECHNICAL
PROPOSALS PROJECT NO: NG-00043-9P BUSINESS SIZE: UNRESTRICTED
CONTRACTED SERVICES: Replace Heating And Cooling With Geothermal Heat
Pump (See attached Scope of Work) This request for technical proposals
is being conducted under Part 14 of the Federal Acquisition
Regulations (FAR) using the two-step sealed bidding process. THERE WILL
BE A PRE-PROPOSAL SITE BRIEFING ON JUNE 2, 1999AT 1:00 PM, LOCAL TIME,
AT THE ABOVE ADDRESS. VENDORS WHO DO NOT PARTICIPATE RISK NOT
RECEIVING INFORMATION VITAL FOR SUBMITTING AN ACCEPTABLE PROPOSAL (To
ensure adequate meeting space, Vendors planning to attend the
pre-proposal briefing are asked to notify the point of contact in
advance). Interested vendors must submit a technical proposal for
review. The review will determine whether the technical proposal is
acceptable, reasonably susceptible of being made acceptable, or
unacceptable. Unacceptable proposals will not be invited to submit
prices in the solicitation process. Vendors should submit proposals
that are acceptable without additional explanation or information. All
proposals must clearly identify all of the requirements as provided at
the Pre-Proposal Site Briefing. The technical proposal will be
evaluated on the basis of: method of accomplishment; 5 years of
experience in heating and air conditioning, 1 years of experience in
geothermal within the last 3 years (past performance information must
be included with the technical proposal). The Government may make a
final determination regarding a proposal's acceptability solely on the
basis of the proposal as submitted. The Government may request
additional information from offerors of proposals that it considers
reasonable susceptible of being made acceptable and may discuss
proposals with their offerors. TECHNICAL PROPOSALS WILL BE NO MORE THAN
10 PAGES IN LENGTH. An additional page is granted as a cover sheet
identifying the firm. TECHNICAL PROPOSALS WITH MORE THAN 10 PAGES MAY
BE REJECTED AS UNACCEPTABLE! Do NOT submit prices with the technical
proposal. A single offeror may submit multiple proposals. Vendors will
be bound by their technical proposals! Vendors with proposals
determined to be unacceptable will be notified on final determination
of unacceptability. Vendors will receive instructions and be notified
of any additional materials, submittals or information required before
prices are submitted. Step-two will consist of a sealed bid. The
Government will award on a Firm-Fixed Price basis to the responsible
offeror who submits the lowest price acceptable offer. The amount of
the solicitation is estimated to be between $ $100,000 and $250,000.
Bonds will be required. Late proposals and revisions of proposals will
not be considered unless the circumstances meet the specific
requirements of FAR 52.215-1(c)(3)(i). The Government will notify
vendors of the date for submission of technical proposals at the
Pre-Proposal Site Briefing. SCOPE OF WORK Project Number NG-00043-9P
BASE BID REPLACE HEATING AND COOLING IN BUILDING 5670 This building
consist of 16 quarters. The building, existing heating and cooling, is
a 2-pipe hydraulic system consisting of a boiler, 42-ton chiller with
air-cooled condenser, 40+-fan coil convector type units and 35+
fin/tube radiant heaters. New heating and cooling system shall fulfill
all local and national codes, and Fort Sill quality standards. Base
bid and bid option 1 to be for a Geothermal Heat Pump with standing
column well system. System shall be a forced air type with insulated
sheet metal duct, diffusers and local control for each quarter. The
proposal to include all work required for a complete and usable
product. BID OPTION 1 REPLACE HEATING AND COOLING IN BUILDING 5675 This
building consist of 16 quarters. The building, existing heating and
cooling, is a 2-pipe hydraulic system consisting of a boiler, 42-ton
chiller with air-cooled condenser, 40+-fan coil convector type units
and 35+ fin/tube radiant heaters. New heating and cooling system shall
fulfill all local and national codes, and Fort Sill quality standards.
Base bid and bid option 1 to be for a Geothermal Heat Pump with
standing column well system. System shall be a forced air type with
insulated sheet metal duct, diffusers and local control for each
quarter. The proposal to include all work required for a complete and
usable product. Bid Option 2 and 2a Contractor to install a
conventional type system in-lieu-of the geothermal heat pump systems
called for in the base bid and option 1. The conventional system to be
a 4-pipe hydraulic system consisting of a new boiler, packaged
air-cooled chiller, new distribution piping to a fan-coil air handler
with insulated sheet metal duct system, diffusers, and local control
for each apartment. BID OPTION 3 REPLACE HEATING AND COOLING IN
BUILDING 5674 This building consist of 16 quarters. The building,
existing heating and cooling, is a 2-pipe hydraulic system consisting
of a boiler, 42-ton chiller with air-cooled condenser, 40+-fan coil
convector type units and 35+ fin/tube radiant heaters. New heating and
cooling system shall fulfill all local and national codes, and Fort
Sill quality standards. Base bid and bid option 1 to be for a
Geothermal Heat Pump with standing column well system. System shall be
a forced air type with insulated sheet metal duct, diffusers and local
control for each quarter. The proposal to include all work required for
a complete and usable product. Bid Option 3a Contractor to install a
conventional type system in-lieu-of the geothermal heat pump systems
called for in the base bid and option 1. The conventional system to be
a 4-pipe hydraulic system consisting of a new boiler, packaged
air-cooled chiller, new distribution piping to a fan-coil air handler
with insulated sheet metal duct system, diffusers, and local control
for each apartment. Posted 05/26/99 (W-SN336126). (0146) Loren Data Corp. http://www.ld.com (SYN# 0172 19990528\Z-0039.SOL)