|
COMMERCE BUSINESS DAILY ISSUE OF JUNE 25,1999 PSA#2375NASA/John F. Kennedy Space Center, Procurement, Kennedy Space Center,
FL 32899 43 -- HELIUM COLD (CRYOGENIC) RECIPROCATING GAS COMPRESSOR SOL
MR9155-4758 DUE 070899 POC Marilynn A. Nelson, Contract Specialist,
Phone (407) 867-3462, Fax (407) 867-2042, Email
Marilynn.Nelson-1@ksc.nasa.gov -- Mitch Colvin, Contracting Officer,
Phone (407) 867-7230, Fax (407) 867-2042, Email
Mitch.Colvin-1@ksc.nasa.gov WEB: Click here for the latest information
about this notice, http://nais.nasa.gov/EPS/KSC/date.html#MR9155-4758.
E-MAIL: Marilynn A. Nelson, Marilynn.Nelson-1@ksc.nasa.gov. NASA/KSC
plans to issue a Request for Quotation (RFQ) to purchase 1
reciprocating type helium cold-gas compressor (CGC) suitable for
outdoor installation with options to purchase 2 additional units. The
CGC shall be capable of compressing helium liquid and/or vapor in
accordance with the specifications herein and shall be a free-standing
unit consisting of the following: a. An all-welded vacuum insulated
cryostat, integrally connected to the compressor housing,
inlet/discharge isolation valves, discharge relief valve, and bayonet
connections The term "cryostat" is meant as the container-assembly that
thermally insulates the compressor housing (which is the "cold-end"
assembly of the compressor) and includes the vacuum jacket and
multilayer insulation (MLI) (wrapped around the compressor housing). b.
Inlet surge vessel c. Cold (cryogenic) and warm (ambient) end
assemblies d. Drive-train driven by an electric motor, with direct
current (dc) speed control, including a flywheel and protective cover
e. Pressure and temperature instrumentation on inlet and discharge
Performance. The CGC shall meet the operation performance criteria
specified below: Operating fluid: Helium (liquid and/or vapor) per
MIL-PRF-27407, Grade A; Inlet pressure: 0 to 35 psig (0 psig nominal);
Inlet temperature: 7.65 to 140 R; Inlet quality: 0 to 100% (subcooled
liquid to super-heated vapor); Discharge pressure: 35 psig (minimum);
Actual volumetric capacity: 7.83 cfm @ 300 rpm (min.); Volumetric
efficiency: 70% (approximate, worst case); Operating piston speed: 60
to 400 rpm; Nominal continuous operating piston speed: 300 rpm;
Required electrical power: 240 V ac, 30 amps, 60 Hz, 3-phase; Drive
motor: 3 hp; Speed control: Variable dc controller, 240 V ac supply,
4-20 mA input; Spatial envelope: 3.5 ft.-wide and long by 7.5-ft. high.
Cool-Down. Cool down of unit from ambient to liquid helium temperature
prior to unit start shall be approximately 30 minutes. System Shutdown
Protection. Provision shall be made to safely shutdown the unit for the
following conditions: a. High discharge pressure and/or temperature b.
High motor temperature c. Excessive unit vibration Operating Cycles.
The unit shall be capable of operating continuously, with the
capability to perform many shutdown/startup cycles per day. Operating
Environment. The unit shall be designed to operate in a seacoast
environment and shall be capable of operating in an average summer
environment of 100 degrees Fahrenheit (0F) and 100 percent (%) relative
humidity (RH), and an average winter environment of 32 0F and 70% RH.
The unit shall be designed in accordance with ANSI/ASCE 7 for a basic
wind speed of 150 miles per hour (mph). Periodic Maintenance. Shaft
seals (cold and warm ends) shall be capable of a minimum of 4000 hours
of operation before being replaced. Piston seals and valves shall be
capable of 17,500 hours (minimum) of operation at the nominal
conditions, specified herein, before the "as-new" volumetric efficiency
decreases more than 10%. Configuration. Inlet and Discharge
Connections. A 1 inch close tolerance, dual seal, female bayonet and a
1 inch straight or Y pattern type isolation valve (for liquid helium
service) shall be incorporated on both the inlet and discharge
connections in a vertical orientation. The bayonets shall have an ANSI
flanged connection and shall be suitable for liquid helium service and
long duration usage in a fixed system. The ANSI flanges shall be in
accordance with ASME B16.5 with material conforming to ASTM A182-F316L.
Anti galling design for isolation valves shall approved prior to valve
selection and shall be verified to have proven reliability in
industry. The inlet and discharge process lines shall be vacuum
insulated using MLI. Process line vacuum spaces shall be integral to
the compressor housing vacuum space (i.e., no vacuum break), unless
otherwise approved by the Contracting Officer. The total heat leak to
the inlet process line, including and from the male female bayonet
assembly to the suction/inlet valve (in the compressor housing),
shallbe no more than 16 British thermal units per hour (Btu/hr). The
isolation valves shall have a flow coefficient (Cv) greater than 15, as
defined by ISA S75.01. Cryostat. The cryostat enclosing the compressor
housing (e.g., also known as the compressor "cold-end" assembly) and
inlet/discharge process lines (including components) shall be insulated
using MLI (also known as "super-insulation" and/or laminar radiation
shielding). The cryostat shall have a 79K14672-2 vacuum pump-out and
relief (VPR) valve with Fredricks model 2100-31 thermocouple gauge
(suggested source: part number VR-46-6272A, PHPK Technologies Inc., 535
Enterprise Dr., Westerville, OH 43081, or approved equal) mounted to
the vacuum jacket. The VPR valve shall be protected by an 11 gauge, 304
type stainless steel (SST) protective enclosure secured with quick
release latches (also made of 304 SST). Mounting. The unit shall be
mounted on a heavy duty structural steel base suitable for fastening to
a poured concrete foundation with provision for anchor bolts. Electric
Drive Motor. The electric motor shall be a totally enclosed fan cooled
(TEFC) dc motor in accordance with NEMA MG 1 and have a dc variable
speed controller capable of local and remote operation. The motor shall
be suitable for outdoor use in the environment specified. Electrical
design shall be in accordance with NFPA 70. Drive Train. The design and
selection of all drive train components shall be in accordance with
accepted industry standards and shall have a 90% survival life greater
than 100,000 hours. Guards. Personnel protection guards shall be
provided for all exposed moving parts to eliminate any hazard to
personnel. Guards shall conform to the following require-ments: (1)
prevent entry of loose clothing, hands, fingers, and other body parts
into the point of hazard by reaching through, over, under, or around
the point of hazard; (2) protect personnel from breakage of
components/parts; (3) not create a hazard themselves; (4) capable of
being removed by authorized personnel; and (5)not be rendered
ineffective from the unit vibration and operation in the environment.
Instrumentation and Controls. Pressure and temperature measurement
shall be provided on the unit inlet and discharge. A gas-bulb-type
temperature measurement shall be used. Pressure and temperature
measurements shall be taken as close to the compres-sor inlet and
discharge as practical and shall be downstream of the inlet isolation
valve and upstream of the discharge isolation valve. An appropriate
pressure pulsation damp-ening device (i.e., a pressure snubber) shall
be used for the pressure measurement instrumentation. A gas bulb
calibration table and curve shall be provided. Calibration shall
list/show temperatures from 7.6 to 540 R and the corresponding
pressure, using at least 75 data points spaced closer at lower
temperatures. Equations, data (i.e., helium property values used), and
unit-specific constants (i.e., volumes) used to generate the
calibration table/curve shall be provided. Measurements shall be
displayed using gauges mounted on a panel attached to the unit.
Additionally, a 4 to 20 milliampere (mA) signal shall be provided for
the said measurements for remote monitoring. Gauges shall be in
accordance with ASME B40.1. All electrical design shall be in
accordance with NFPA 70. Enclosures shall be NEMA 4 rated. Field
installed (or unused) electrical connections shall be properly
capped/sealed prior to shipping. Identification and Marking. All
components and instrumentation shall be clearly identified and legibly
marked. Identification and marking shall not interfere with the
operation of the unit. Additionally, a name plate on the unit shall
include the model/part number, serial number, date of manufacture,
capacity (horsepower), and manufacturer name/address. The method of
marking and identification shall be selected so that the en-vironment
will not degrade its original clarity and appearance. Design. Design
Construction. The design and construction of the unit shall conform to
the ASME BPVC Section VIII and ASMEB31.3. All components, system
elements, and materials shall be selected, designed for, and compatible
with the most severe service conditions expected, as specified herein.
Pressure containing parts shall be pressure tested in accordance with
the specifications herein. Use of aluminum and its alloys shall not be
allowed for construction, unless otherwise approved by the Contracting
Officer. All materials of construction shall be approved prior to
fabrication. Pressure Relief. An ASME BPVC Section VIII, Division 1,
certified pressure relief valve for liquid helium service shall be
provided in the discharge piping (upstream of the unit discharge
isolation valve). The device shall be selected and sized to preclude
over-pressurizing an operating and/or nonoperating unit if discharge is
completely blocked and a trapped (confined) volume full of liquid
helium exists in the unit. Discharge shall be oriented to prevent
impingement onto/at personnel. Protective Coating. Carbon steel
surfaces exposed to the environment shall be protected using a
three-coat system, consisting of a single application of inorganic zinc
(2.5 to 4 mils), an intermediate/tie coat, and a top coat. The
300-series SST's do not require pro-tective coating. However, a
dissimilar metal weld, involving a 300-series SST, shall be
protectively coated a minimum of 2 inches beyond the weld line.
Surfaces to be protected shall be properly degreased and cleaned per
manufacturer's recommendations. Surface preparation procedures,
protective coating system, and selected colors shall be approved prior
to purchase and application. Dissimilar Metals. To preclude galvanic
corrosion, a suitable material or dielectric shall be used to prevent
the contact of dissimilar metals. This procurement is being conducted
under the Simplified Acquisition Procedures (SAP). NASA/KSC intends to
purchase the items from Cryo Technologies, 761 Brookside Road,
Allentown, PA 18106. Cryo Technologies is the only known responsible
source capable of satisfying our requirements. The authority for Other
Than Full and Open Competition is 10 U.S.C. 2304(c)(1) The Government
intends to acquire a commercial item using FAR Part 12. Accordingly,
any interested firms must demonstrate that they have successfully
produced compressors that satisfy the requirements described above, are
currently used in industry, and are available commercially. See NASA
Specific Numbered Note "A". Interested firms have fifteen (15) days
from the publication of this synopsis to submit, in writing to the
identified point of contact, their qualifications and capabilities to
respond to the requirement or submit proposals. Oral communications are
not acceptable in response to this notice and will not be considered.
This notice of intent is not a request for competitive proposals.
However, all written responses/proposals received within fifteen days
after date of publication of this synopsis will be considered by the
Government. Proposals/responses received after the fifteen days or
without the required information will be considered non-responsive to
the synopsis and will not be considered. Information received will
normally be considered solely for the purpose of determining whether to
conduct a competitive procurement. A determination by the Government
not to compete this proposed procurement on a full and open competitive
basis, based upon responses to this notice, is solely within the
discretion of the Government. An Ombudsman has been appointed. See
Internet Note "B". Any referenced notes can be viewed at the following
URL: http://genesis.gsfc.nasa.gov/nasanote.html Posted 06/23/99
(D-SN346178). (0174) Loren Data Corp. http://www.ld.com (SYN# 0277 19990625\43-0001.SOL)
43 - Pumps and Compressors Index Page
|
|