Loren Data Corp.

'

 
 

COMMERCE BUSINESS DAILY ISSUE OF JULY 2,1999 PSA#2380

United States Air Force, Air Education and Training Command, Sheppard AFB Contracting Office, 82d Contracting Squadron, 136 K Avenue Ste 1, Sheppard AFB, TX, 76311-2746

R -- REPAIR AND INSPECT WATER STORAGE TANKS SOL F41612-99-T0474 DUE 070999 POC Thomas Manning, Contract Specialist, Phone (940) 676-5189, Fax (940) 676-3784, Email Thomas.Manning@sheppard.af.mil -- Kevin Slone, Contracting Officer, Phone (940) 676-5185, Fax (940) 676-3784, Email WEB: Visit this URL for the latest information about this, http://www.eps.gov/cgi-bin/WebObjects/EPS?ACode=P&;ProjID=F41612-99-T04 74&LocID=563. E-MAIL: Thomas Manning, Thomas.Manning@sheppard.af.mil. A. The purpose of this amendment is to change the offer due date and provide answers to the questions submitted.; B. The offer due date is hereby changed from 25 JUN 99 to 09 JUL 99.; C. All other terms and conditions remain the same and in full effect.; Q1: What are the sizes and weights of the floats and cables in tanks 1 and 2 (dimentions)?; A1: No data is available regarding the weights and size of the floats and cables. My best reccommendation at this time to have the contractors field verify during the site visit.; Q2: What part of the roof vent on tank 3 needs replacement? Is it welded or bolted on?; A2: The roof vent on tank 3 is a 12" opening, mushroom type vent. The mushroom and the screen associated with it have rusted away from the neck. The mushroom appears to be welded to the neck.; Q3: Why do you need TNRCC hatch on old tank,tank 4? A3: In accordance with TNRCC 290-43, c.2, the hatch must be a 30" opening. If it is not, it must be corrected at such time renovaitons or repairs are done. The existing hatch is 24", and we must correct it to meet the regulations. Posted 06/30/99 (D-SN349136). (0181)

Loren Data Corp. http://www.ld.com (SYN# 0082 19990702\R-0015.SOL)


R - Professional, Administrative and Management Support Services Index Page