COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 8,1999 PSA#2427Department of Veterans Affairs, James A. Haley Veterans Hospital, AMMS
(90C), 13000 Bruce B. Downs Blvd., Tampa, FL 33612 J -- D.I. WATER, WATER SOFTNER SALT, & PORTABLE D.I. TANKS SOL RFQ
673-27-00 DUE 092199 POC Charlene K. Stiens, 813-972-7655 This is a
combined synopsis/solicitation for commercial items prepared in
accordance with the subparts in Federal Acquisition Regulation 12.6 and
Veterans Administration Acquisition Regulations as supplemented with
additional information included in this notice. This announcement
constitutes the only solicitation; quotations are being requested and
a written solicitation will not be issued. Solicitation number
673-27-00 applies and is issued as a request for quotation. This
solicitation document and incorporated provisions and clauses are those
in effect through Federal Acquisition Circular 97-12. The Standard
Industrial Classification Code is 7389 and the business size standard
is $5 million. Provide the James A. Haley Veterans Hospital, 13000
Bruce B. Downs Blvd., Tampa, FL 33612 with 15 megohms D.I. water from
portable exchange D.I. tanks (pedi) installed in D.I. recirculation
system; salt for water softeners throughout hospital; and provide
portable deionized tanks to be utilized as back-up system,for the
period October 1, 1999 thru September 30, 2000. The Government may
extend the term of this contract four (4) optional years. PRICING SHALL
BE SUBMITTED FOR: Base Year and each optional year for 1) D.I. water,
per gallon, est. 900,000 gal per year; 2) Salt, 80 lb bag, est. 2200
bags per year; and 3) Tank, est. 12 tanks per year, in accordance with
(IAW) Statement of Work. STATEMENT OF WORK: 1) Contractor shall
provide all necessary equipment, chemicals, laboratory services and
exchange exhausted pedi tanks for freshly-regenerated pedi tanks within
24 hours to ensure continued uninterrupted supply of 15 megohms D.I.
water to hospital. Price will be charged per gal. on an as used basis,
based on monthly water production for the reverse osmosis water
conditioning unit and that product water from this unit does not exceed
0 PPM hardness and 10 PPM TDS. Estimated usage per year is 900,000
gallons. 2) Contractor shall supply salt for water softeners throughout
hospital in locations listed as follows: Contractor shall on a weekly
basis, Wednesday or Thursday, fill the salt tanks of the 4 A/C cooling
tower softeners, others filled as needed based on weekly observation,
deliver salt directly to brine tanks utilizing Contractor's labor &
equipment; fill brine tanks with sufficient quantity of salt to
minimize the number of trips & visually check softeners and brine tanks
for correct operation and perform hardness test on softeners product
water to ensure a zero hardness. If any problems occur, the contractor
shall respond within one hour by telephone. If the problem cannot be
solved by telephone the contractor shall respond to the VA Hospital
within eight hours. There are (11) eleven softeners covered by this
contract. Four located in boiler plant; one located in penthouse RTU
Bldg.; one located in NHCU Room G005; one located at chiller #3 cooling
tower; one located in the 2nd floor dining room; one located at cooling
tower #1; one located at chiller #6; and one located at cooling tower
#2. Estimated usage per year is 2200, 80 pound bags. 3 Contractor shall
provide portable deionized tanks, 6W (6th floor) and Bldg. #2 to be
utilized as back-up system. Tanks shall be supplied with deionized
water with a total dissolved solid content of less than 1 PPM. Three
(3) MBR-844 (8" x 44) tanks will be provided. Tanks shall be charged
out a minimum of semi-annually or when the indicator lights are out.
Price per tank will be billed when installed and when changed out.
Estimate 12 tanks per year. The government intends to make a single
award to the responsible offeror whose offer is the most advantageous
to the government considering price and price related factors.
Provision 52.212-2 Evaluation Commercial Items, applies to this
acquisition. Award will be made on the basis of the lowest evaluated
price of quotes meeting or exceeding the acceptability standards for
non-cost (technical) items. The following factors shall be used to
evaluate technical acceptability: 1) Past Performance and 2) Ability to
provide the supplies as required in the Statement of Work. Offerors
shall provide all necessary documentation needed to support technical
evaluation of your quote. Offerors shall provide a completed set of
provisions with quotation found at 52.212-3, Offeror Representations
and Certification Commercial Items. Provisions and clauses found at
52.212-1, 52.212-2, 52.212-4, 52.212-5, 52.216-18, 52.216-19,
52.216-21, 52.217-8, 852.216-70, 852.237-70, 852.270-4 also apply.
Subject to the availability of funds. Note 1 applies. Quotations shall
be submitted to the address listed above or faxed to 813-903-4838 and
directed to the attention of Charlene K. Stiens (90C). The
solicitation number 673-27-00 shall be listed on the outside of your
quotation for identification purposes. Posted 09/03/99 (W-SN376553).
(0246) Loren Data Corp. http://www.ld.com (SYN# 0054 19990908\J-0009.SOL)