|
COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 9,1999 PSA#2428Department of the Air Force, Direct Reporting Units, 10 ABW/LGC, 8110
Industrial Drive, Suite 200, USAF Academy, CO, 80840-2315 58 -- PUBLIC ADDRESS SYSTEM REPLACEMENT SOL F05611-99-T-1817 DUE
091599 POC Scott Walker, Contracting Specialist, Phone (719) 333-6081,
Fax (719) 333-4404, Email scott.walker@usafa.af.mil -- Bruce Taylor,
Contracting Officer, Phone (719) 333-2869, Fax (719)333-4747, Email
WEB: Visit this URL for the latest information about this,
http://www.eps.gov/cgi-bin/WebObjects/EPS?ACode=M&ProjID=F05611-99-T-1
817&LocID=479. E-MAIL: Scott Walker, scott.walker@usafa.af.mil. Reason
for Modification: Change response date from 10 Sep 1999 to 15 Sep 99,
provide the following additional information to the para entitled
Contractor is required to: 3. Test, equalize, adjust, and balance the
entire Falcon Stadium Main Speaker Cluster, add and correct NOTES to
the Combined Synopsis/Solicitation posted 01 Sep 99. TEST EQUIPMENT:
The contractor shall will supply, utilize, and be proficient with the
following at a minimum the following test equipment, to conduct the
specified tests, adjustments, and demonstrations set forth below:
FILTER SET: One third octave band filter set meeting ANSI S1.11
specifications; SINE WAVE GENERATOR: Continuously sweep from 20 Hz to
20,000 Hz within -- or+1 dB with less than 0.5% THD; IMPEDANCE METER:
At least 250Hz, 1kHz and 8 kHz with a range of 0-100k ohms;
OSCILLOSCOPE: At least 20MHz bandwidth and external horizontal inputs.
Sensitivity of 10 mV/division or less; DISTORTION ANALYZER: Automatic
tunable 1/10 octave band wave analyzer allowing reading down to and
including .001% THD; REAL-TIME ANALYZER: One third octave band meeting
specifications of ANSI SS1.4 and S1.11; PINK NOISE GENERATOR: Capable
of producing at least -50 dBV to 0 dBV of pink noise; AC VOLTMETER:
Frequency response of + or -- 1dB from 20 Hz to 20,000 Hz,0.001 volts
rms to minimum input impedance of 0.01m ohms; PHASE TESTER: Capable of
measuring electrical and acoustical polarity using an encoded sine
wave with low, low midrange, midrange high, and high output
frequencies; TEF (Time Energy Frequency) Analyzer: Capable of measuring
time, energy and frequency domain to include Nyquist curves and 2nd/3rd
harmonic distortion plots; SLM: Meets ANSI S1.4 specifications for Type
1 SLM level meters; Other miscellaneous cabling and connectors required
to perform tests, equipment setups, or equipment checkouts; Other
miscellaneous cabling and connectors required to perform tests,
equipment setups, or equipment checkouts. TESTING: If applicable, the
following tests will be performed by the contractor: TRANSDUCER LINE
IMPEDANCE: Measure the impedance of each line exiting the equipment
rack with the line disconnected from its normal driving source. Confirm
impedance values within + 10% of the value calculated for the circuit
based upon the parallel impedance values plus the resistance of the
cable. Record the impedance at 1000 Hz for full range devices. Verify
the minimum load impedance's are not exceeded and there are no
electrical short; HUM AND NOISE LEVEL: Adjust the gain controls for the
optimum signal-to-noise ratio. This adjustment should be such that full
output would be achieved with 0VU; POWER OUTPUT AND SIGNAL LEVEL
ADJUSTMENTS: Measure the electrical distortion of the overall system.
Set variable filter sets for a flat response. Apply a 1000Hz sine wave
signal at each input at a level required for the specific type of
input. Use a distortion analyzer to measure and record the output level
and total harmonic distortion of the amplification equipment. Make all
measurements with the loadsactually incurred in the system; PARASITIC
OSCILLATION AND RADIO FREQUENCY PICK UP: Check to ensure the system is
free from spurious oscillation and radio frequency (RF) pick up, both
in the absence of any input signal and also when the system is driven
to full output potential at 1000 Hz. Using a hand held radio provided
by the Public Address Maintenance Workcenter (10 CS/SCMRP) to check the
above; POLARITY: Phase all lines identically with respect to color
coding. Visually inspect all transformer primary and secondary wiring
to insure proper phasing; FREEDOM FROM BUZZES, RATTLES AND
OBJECTIONABLE DISTORTION: Apply a slow sine wave sweep from 100Hz to
10,000Hz at a level 6dB below the rated power input levels. Listen
carefully for buzzes, rattles and objectionable distortion. Correct all
causes of any defects; GAIN CONTROL SETTINGS: Establish "normal"
settings for all gain controls. All gain controls will be adjusted for
optimum signal-to-noise ratio and signal balance. Clearly mark all
knob and control settings with a red nail polish dot; LIMITER
ADJUSTMENT: Adjust all limiters so the peak LED illuminates at the
failure point of the transducer to be protected. Adjust RMS limiters
for -3 DB of compression at the same failure point; FREQUENCY RESPONSE:
The overall space average frequency response within each area served
will be within the limits given below. Test signals will consist of a
broad band pink noise signal applied to the system input. System
performance measurements will be made using a calibrated ANSI S1.4 type
1 SLM set for slow meter damping and flat response. The SLM will be
positioned 5 to 6 feet above the floor within the space served by the
system. The system gain will be set to provide octave band levels at
least 15dB above any background noise levels in any octave band at the
measuring location for these areas. Provide a hard copy of the average
frequency response based upon the measurements at least ten locations
to the Public Address Maintenance Workcenter (10CS/SCMRP). Ensure
identical measurements are obtained when using the TEF measuring
methods and compare the real time response using pink noise; Using the
TEF Analyzer, measure the STI after filter set adjustments are
completed. Provide the Public Address Maintenance Workcenter (10
CS/SCMRP) with a hard copy of the results. NOTE: Results of all tests
performed are to be submitted, reviewed, approved and accepted by,
10CS/SCMRP, POC assigned to this project. NOTE: Contractor will be
required to remove existing speaker horns on top of scoreboard and
retrofit as required to accommodate new components. Offers are to be
received at the Operational Contacting Office 8110 Industrial, Dr., Ste
200, USAF Academy, CO 80840, No later than 15 Sep 99, 3:00 PM, Mountain
Standard Time. Questions and proposals may be faxed to (719)333-4404 or
Email to the addresses above. Offers are to be received at the
Operational Contacting Office 8110 Industrial, Dr., Ste 200, USAF
Academy, CO 80840, No later than 15 Sep 99, 3:00 PM, Mountain Standard
Time. Questions and proposals may be faxed to (719)333-4404 or Email
to the addresses above. Posted 09/07/99 (D-SN377157). (0250) Loren Data Corp. http://www.ld.com (SYN# 0239 19990909\58-0006.SOL)
58 - Communication, Detection and Coherent Radiation Equipment Index Page
|
|