COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 13,1999 PSA#2430WR-ALC/PKOS, 215 Byron St, Robins Air Force Base, GA 31098-1611 N -- INSTALLATION OF LIQUID NITROGEN LINES FOR AVIONICS REPAIR SHOP AT
ROBINS AFB GA 31098-1611 SOL F09650-99-Q-1108 DUE 092099 POC Joy
Carroll, (912) 926-3135 E-MAIL: Contracting Officer's E-Mail Address,
Joy.Carroll@robins.af.mil. This requirement is for the installation of
Liquid Nitrogen Lines in the Avionics Repair Shop at Robins AFB GA.
This synopsis record will serve as a combination synopsis-solicitation
as procured under FAR 12. Faxed responses are acceptable. The fax
number is 912-926-3590. Source: Industrial Cryo-Services Inc, Tampa FL.
Note 22 APPLIES. Quantity: 1 JB. The following is the Statement of
Work. Statement of Work Installing Liquid Nitrogen Lines
F09650-99-Q-1108 General: Provide all tools, material, labor,
transportation, travel, and per diem to complete the installation of
Liquid Nitrogen Lines in the Avionics Repair Shop (LYP) at Robins AFB
GA 31098. Task 1: Install piping from the existing capped tee to
provide two additional Liquid Nitrogen line drops below the drop
ceiling, located 22 feet to the east. Task 2: Install a line connecting
the Liquid Nitrogen drop to the RMTS station, including shutoff valve,
safety valve and regulator. Task 3: Remove existing Cryovent, and
install new vertical riser to extend the line and elevate Cryovent
location above the roof through the roof curb. Install new Cryovent
above roof. Task 4: Remove existing Cryovent and install new Cryovent;
reattach copper tubing to new valve outlet for venting nitrogen gas to
exterior of building. Task 5: At the 3000 gallon Liquid Nitrogen Tank,
remove defective section of vacuum jacketed piping and replace with
new section. Defective is designated as VS-1, S/N 66416. Task 6: At the
3000 gallon Liquid Nitrogen Tank, insulate exposed copper tubing
located between the vacuum jacketed piping section and tank's liquid
outlet connection (VS-1, S/N 66416). Task 7: Remove existing Cryovent
and install new Cryovent with 100 volt plug in ventilation heater
located above the roof through the roof curb. Task 8: At the 1500
gallon Liquid Nitrogen Tank, insulate exposed copper tubing located
between the vacuum jacketed piping section designated model VS-1, S/N
86920 and the tank's liquid outlet connection. Posted 09/08/99
(W-SN377842). (0251) Loren Data Corp. http://www.ld.com (SYN# 0106 19990913\N-0003.SOL)