COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 29,1999 PSA#2443Fleet and Industrial Supply Center, Puget Sound, Bldg 467 W Street,
Code 200 Bid Desk, Bremerton, WA 98314-0051 61 -- STATIC FREQUENCY CONVERTER SOL N00406-99-R-5249 DUE 111799 POC
Maureen Renville (360)476-7772 E-MAIL: Contracting Officer,
maureen_renvill@puget.fisc.navy.mil. Static Frequency Converters (SFC)
capable of converting Type I, 60 jertz (HZ), 440 volts, 3-phase power
as defined in MIL-STD-1399 (NAVY) to 400 HZ power.b. This is a 100%
Small Business Set-Aside. To be procured as an Indefinite Quantity,
Indefinite Delivery Contract. Minimum requirement will be the 1st
Article. Total quantity is one each 1st Article; 52 each as follows:
1st Option period (FY2002) -- 22 each; 2nd Option period (FY2003)- 18
each; 3rd Option period (FY2004)- 10 each; and 4th Option period
(FY2005) -- 2 each. Unit shall be designed so that each can be
paralleled with an identical SFC with an output of 10 KVA. Fuses shall
be kept to a minimum consistent with protection of various components
within the SFC. Circuitry shall be of solid state design. SFC shall
use IGBT technology or newer. All electrical components including
relays, switches and wiring shall conform to and be located in
accordance with applicable NEMA, ANSI and NFPA standards for the
intended application. A supply circuit disconnect device shall be
provided and installed on the SFC. Main and auxillary controlcircuits
shall operate on a circuit of 115 volts or less derived from isolation
transformer(s) integral with the equipment. All exposed, non-current
carring metal parts on the SFC shall be maintained at common, zero
ground potential. None of the primary circuits in the equipment shall
be connected to ground. Solid state design shall be employed throughout
for electronic components. Performance requirements: a) The overall
nput/output efficiency at rated load shall be 70%. b) The SFC will
provide MIL-STD-1399 (NAVY) Type I power within the following
parameters: OUTPUT power -- 120 V AC; NO OF PHASES-3; TYPE OF
CONNECTION -- Delta; CONTINUOUS POWER OUTPUT RATING -- 5 k VA; OUTPUT
FREQUENCY -- 400 Hz. The SFC shall operate satisfactorily under any of
the following conditions: a) Ambient Temperature Range -- 0 to 55
degrees C; b) Ambient Humidity Range 0 to 95% relative humidity.
MAXIMUM dimension including requiredshock mounts and cable pull boxes:
Height -- 60'; Width -- 24"; Depth -- 38" (with max service envelope
of 57'). FIRST ARTICLE TESTS to include the following: a) vibration IAW
MIL-STD-167; b) shock IAW MIL-S-901; c) Electromagnetic interference
characteristics IAW MIL-STD-461; d) Ferrous Magnetic Field Test and
Stray Magnetic Field Test; e) 250-hour life test. Production Unit(s)
test to include Operational Test and Manufacturing Reliability Test.
Data Items to be provided are: a) First Article Test Procedures and
Reports; b) Production Test Procedures and Reports; c) Engineering
Drawings and Associated Lists (parts/tools); d) PTD documentation or
Standard Commercial Manuals if information containedwithin meets or
exceeds the PTD requirements. Delivery of First Article desired 90 days
after date of contract. Inspection at source, inspection at
destination, Puget Sound Naval Shipyard, Bremerton, WA 98314-5100.
Notes 1,9,and 26 apply. All responsible sources may submit offer/bid
which shall be considered by FISC Puget Sound. Telephone requests will
not be honored. Fax requests to (360)476-2931 or e-mail
bid_officer@puget.fisc.navy.mil. Posted 09/27/99 (W-SN385066). (0270) Loren Data Corp. http://www.ld.com (SYN# 0248 19990929\61-0002.SOL)