COMMERCE BUSINESS DAILY ISSUE OF OCTOBER 18,1999 PSA#2456Fleet Industrial Supply Center Norfolk, Detachment Philadelphia, 700
Robbins Ave., Bldg. 2B, Philadelphia, PA 19111-5084 70 -- NAVY STANDARD RACK MOUNT 4KVA UNINTERRUPTIBLE POWER SUPPLY FOR
SHIPBOARD USE SOL N00140-00-R-E304 DUE 111799 POC Kathleen Lockhart,
CONTRACT NEGOTIATOR 215-697-9617, H. R. Aldridge, Contracting
Officer(215)697-9610 E-MAIL: click here to contact the contracts office
via e-mail, Kathleen _M_Lockhart@phil.fisc.navy.mil. DESC- The Fleet
& Industrial Supply Center (FISC) Norfolk Detachment Philadelphia
intends to procure on a competitive basis Navy Standard Rack Mount 4.0
KVA Uninterruptible Power Supply with Integrated Power Distribution
Unit. The proposed procurement is for an indefinite delivery/indefinite
quantity contract. The ordering period under this contract will be for
a base year with two option years. The total ordering period will not
exceed thirty-six months if all options are exercised. The total
estimated quantity(including options) is 161 units. The equipment
offered must meet or exceed the following specification: Electrical
Input-Voltage/Frequency 120 VAC/60 Hz, single phase, 10 % ;Input power
connection AMP 208483-1; Battery power connection -- AMP 208485-1;
OUTPUT Voltage/Frequency 120 VAC/60 Hz, single phase; +5 VDC and +12
VDC outputs for a TAC-4 keyboard & associated light shall be provided.
The current draw for the 12 VDC is 300ma and 5 VDC is 1.1A. These
outputs shall be uninterruptible and protected by the UPS; Voltage &
Frequency Regulation shall be Steady State conditions; Total Harmonic
Distortion -- < 5%; Efficiency at full load 80%; Overload -- 125%
for 10 minutes; Power Factor -- 0.7 lead to 0.7 lag; Mechanical-UPS
shall be based upon a High Frequency Pulsed Width Modulation (PWM)
topology to provide a lightweight and compact design. UPS (excluding
external battery) shall not exceed 75 lbs. in weight; UPS and external
battery shall be 19" rack mountable; UPS and external battery shall be
contained in separate units. UPS and external battery shall not take up
more than 7U (12.75") of rack space. UPS height shall not exceed 3U
(5.25");Battery height shall not exceed 4U (7"); UPS shall provide
eight (8) 5-15R output receptacles with cable locks. UPS shall not
exceed 24" in length; External battery shall not exceed 25 " in length.
UPS input power receptacle shall be AMP 208483-1; UPS battery input
receptacle shall be AMP 208485-1. Battery output receptacle shall be
AMP 208485-1. UPS and external battery units shall have front panel
mounted handles. UPS and external battery unit shall provide for the
acceptance of rack mount slides. Type of slide to be determined at time
of order. Exhaust fan air flow shall be from front to rear. Controls
and indicators -Front panel shall include: eight (8) power distribution
load circuit breakers to individually control eight (8) output
receptacles. Circuit breakers shall each have a physical protective
feature to prevent inadvertent release; battle short switch to override
interlocks and shutdown features; a "red" toggle switch guard for the
battle short switch; a designated space for load switch labeling; a
double pole main input circuit breaker; an audible alarm reset push
button an audible alarm disable switch; indicators shall include: AC
power to UPS is available; UPS is ON and operating properly; Sequenced
LEDs/readout gauge for battery level; Sequenced LEDs/readout gauge for
UPS load level. Indicators with alarms shall include: AC Input failure;
Low Battery; Over temperature; Fan failure; Internal logic/electronic
failure; Battle short switch ON; EXTERNAL BATTERY- Battery back-up
shall be: 4U battery Half-load(20-30 minutes); Full load (10-15
minutes); Batteries shall have no out-gassing; Batteries shall be
maintenance free and of the immobilized electrolyte type. The UPS shall
meet the following shock, vibration and electrical standards: MIL-STD
901 grade B and MIL-STD-462. The following standards will be referenced
for guidance only: MIL-STD 167C Type I; MIL-STD 1399 section 300A, Type
I; MIL-STD 1310; MIL-STD 461. UPS shall be developed and produced under
ISO9000 quality control standards; UPS shall include communications and
diagnostic capabilities through a software Power Monitoring package.
Operating Temperature (-20 C to +50 C) Storage Temperature (UPS
only)(-40 C to +85 C); Operating Humidity -- To 95% non-condensing;
Operating Elevation -- To 15,000 ft. (40,000 ft. non-operating);
Audible noise -- < 55dba at 5ft.; Material Safety Data Sheets (MSDS)
shall be provided for the UPS and Battery units. Orders will indicate
either 3U and/or 4U battery units with the UPS. A pre production first
article' will be required for Government testing. Additional
information will be provided in the solicitation document. A written
solicitation will be issued on or about 29 October 1999. Requests for
the solicitation may be faxed. Faxes will be received on a Panasonic
UF-770, Fax number (215) 697-9739 and should be marked with the
solicitation number and directed to the attention of Kathleen Lockhart,
Code 02P12K. Requests for the solicitation may also be submitted
electronically to the following: Kathleen_M_Lockhart@phil.fisc.navy.mil
Please include your email address in your request. All responsible
sources are encouraged to participate. Posted 10/14/99 (W-SN391784).
(0287) Loren Data Corp. http://www.ld.com (SYN# 0218 19991018\70-0003.SOL)