US Bureau of Reclamation, Code 7810, PO Box 620, Grand Coulee, WA 99133

61 -- NEUTRAL CURRENT TRANSFORMERS SOL 00SQ170258 DUE 031300 POC Nora Jenn (509) 633-9509 Fax (509) 633-9175 E-MAIL: Neutral Current Transformers, njenn@pn.usbr.gov. The Bureau of Reclamation, Grand Coulee Power Office, Grand Coulee WA 99133 has a requirement for 36 neutral current transformers specifications as follows: MVA 826 Amp Ratio 7000:2, Accuracy 10C200, 60 Hertz, 15KV Voltage Class, 100 Degree C Temperature Rating, Maximum Expected Primary Current of 31779. Each current transformer (CT) shall come with a mounting base and terminal block. Each CT and mounting base must fit the existing size limitations to accommodate the limited space requirements. See Hammond Engineering Design Bulletin 110489 and CGE 215A9911BC Sheets 1 through 3. Acceptable terminal blocks are listed on CGE 215A9911BC sheet 3. All CT's shall be tested in accordance with the requirements of IEEE Standard C57.13-1993. The solicitation number is 00SQ170268. To request a complete bid packet, please e-mail njenn@pn.usbr.gov, or fax your request to (509) 633-9175. This is a small business set-aside. Posted 02/11/00 (W-SN424757). (0042)