COMMERCE BUSINESS DAILY ISSUE OF FEBRUARY 15,2000 PSA#2537US Bureau of Reclamation, Code 7810, PO Box 620, Grand Coulee, WA
99133 61 -- NEUTRAL CURRENT TRANSFORMERS SOL 00SQ170258 DUE 031300 POC Nora
Jenn (509) 633-9509 Fax (509) 633-9175 E-MAIL: Neutral Current
Transformers, njenn@pn.usbr.gov. The Bureau of Reclamation, Grand
Coulee Power Office, Grand Coulee WA 99133 has a requirement for 36
neutral current transformers specifications as follows: MVA 826 Amp
Ratio 7000:2, Accuracy 10C200, 60 Hertz, 15KV Voltage Class, 100 Degree
C Temperature Rating, Maximum Expected Primary Current of 31779. Each
current transformer (CT) shall come with a mounting base and terminal
block. Each CT and mounting base must fit the existing size limitations
to accommodate the limited space requirements. See Hammond Engineering
Design Bulletin 110489 and CGE 215A9911BC Sheets 1 through 3.
Acceptable terminal blocks are listed on CGE 215A9911BC sheet 3. All
CT's shall be tested in accordance with the requirements of IEEE
Standard C57.13-1993. The solicitation number is 00SQ170268. To request
a complete bid packet, please e-mail njenn@pn.usbr.gov, or fax your
request to (509) 633-9175. This is a small business set-aside. Posted
02/11/00 (W-SN424757). (0042) Loren Data Corp. http://www.ld.com (SYN# 0234 20000215\61-0003.SOL)