COMMERCE BUSINESS DAILY ISSUE OF MARCH 9,2000 PSA#2553U.S. Department of Interior, Bureau of Indian Affairs, San Carlos
Irrigation Project, P.O. Box 250, Coolidge, AZ 85228 61 -- PUMP CONTROL PANEL SOL 0H59SCIP002 DUE 032000 POC Mary Lou
Tiznado, (520) 723-6210/5886, Fax (520) 723-9044 E-MAIL: Mary L
Tiznado/PHOENIX/BIA/DOI@BIA, Mary L Tiznado/PHOENIX/BIA/DOI@BIA. The
Bureau of Indian Affairs, San Carlos Irrigation Project is soliciting
quotations for purchase of fifteen (15) pump control panels. San Carlos
Irrigation Project is located at 13805 North Arizona Boulevard,
Coolidge, Arizona 85228. Coolidge is located in Pinal County in Central
Arizona. The pump control panels are to be for part winding motor, in
weather proof cabinet, for outdoor installation, with main circuit
breaker, three phase, 480 volt 60 cycle A.C., overcurrent protection in
all six (6) motor leads; undervoltage protection with single phase
reverse phase current style relay, with special time delay relay for
automatic restarting after power failure, with "HANDS-OFF-AUTO"
selector switch, with "TEST" push button for starting when in hand mode
for controlling deep well turbine pump "part winding" motor as follows:
STARTERS: Magnetic type, for increment part winding motor, each
contactor to be ample size with easily serviced contacts, capable of
interrupting ten times the normal running currentof the individual
motor windings, contactors to open all three phases and be wired and
equipped to open positively in case of under voltage or loss of
voltage, starter is not to go through restart sequence if selector
switch is set for hand operation unless "TEST" push button is actuated.
If selector switch is in "AUTOMATIC" position, starter is to go through
restart sequence after definite time interval as set by timing relay
provided voltage has returned to normal. OVER-CURRENT PROTECTION: Six
(6)each; one for each motor lead, to be of temperature compensated type
to insure accuracy of current measurement from 0 degree to 160 degree
fahrenheit. To be magnetic type dast pot compensated, adjustable from
80 to 120% of full current of individual motor winding with manual
reset facilities. Tripping of any one unit to open both main
contactors. Shall be five (5) ampere rating with current transformers
in motor leads. TIME DELAY RELAY: A relay adjustable to 0.2 to 180
seconds, sequences the starter contactors during starting sequence.
SINGLE PHASE/REVERSE PHASE RELAY: Current sensing type, to open control
circuit of starter when motor current becomes dangerously unbalanced or
when phases reversed, with manual reset features. To be connected with
over-current protection of first closing contactor current
transformers. TIME DELAY RELAY: A relay inserted in the control circuit
to restart pump at a pre-determined time after power failure or
undervoltage conditions and return of normal voltage. Relay to be
adjustable from one minute to fifteen minutes or more and will be
connected to the "AUTOMATIC" control circuit. CABINET: To be of heavy
gauge steel sheet metal, weatherproof construction, freestanding, for
outdoor installation in desert country, with lifting eyes to facilitate
field installation, finished in grey enamel. Power access and exit will
be through side and bottom entrance conduit spaces provided. The
following is required: 150 horsepower, minimum of NEMA size 4 (10 each)
and 200 horsepower, minimum of NEMA size 5 (5 each). Partial shipments
are acceptable, please give estimated ship date(s). INTERESTED PARTIES
MUST RESPOND WITH THEIR QUOTATIONS, NO HARD COPIES OF THIS REQUEST FOR
QUOTATION WILL BE MAIL/FAXED. TO SUBMIT BY E-MAIL, THE ADDRESS IS:
Mary L Tiznado/PHOENIX/BIA/DOI@BIA. THE FAX NUMBER IS (520) 723-9044.
THE MAILING ADDRES IS BIA -- SAN CARLOS IRRIGATION PROJECT, P. O. BOX
250, COOLIDGE, AZ 85228. ALL QUOTATIONS MUST BE RECEIVED BY 2:00 PM
(ARIZONA TIME) ON 03/20/00. Posted 03/07/00 (W-SN432101). (0067) Loren Data Corp. http://www.ld.com (SYN# 0234 20000309\61-0003.SOL)
61 - Electric Wire and Power and Distribution Equipment Index Page
|
|