COMMERCE BUSINESS DAILY ISSUE OF MARCH 23,2000 PSA#2563Department of the Air Force, Air Mobility Command, 22 CONS, 53147
Kansas St, Suite 102, McConnell AFB, KS, 67221-3606 43 -- SUPPLY AND REPLACE PUMP SEALS FOR FUEL PUMPS JP8 SOL
F14614-00-T-0026 DUE 042700 POC Bill Pinkowski, Contract Specialist,
Phone (316) 759-4523, Fax (316) 759-4507, Email
bill.pinkowski@mcconnell.af.mil -- Timothy Officer, Contracting
Officer, Phone (316) 759-4513, Fax (316) 759-4507, Email WEB: Visit
this URL for the latest information about this,
http://www.eps.gov/cgi-bin/WebObjects/EPS?ACode=P&ProjID=F14614-00-T-0
026&LocID=821. E-MAIL: Bill Pinkowski, bill.pinkowski@mcconnell.af.mil.
Provide and install 10 mechanical seals for the hydrant fueling system.
The new seals shall comply with all fuel system (API) standards. The
contractor shall provide the seals and install them. The contractor
shall set forth in the quotation the method of installation and seals
to be used with their technical specifications. The contractor shall be
liable for any repairs to pump and/or new seals, during the warrantee,
if there are any leaks, drips or wetness after installation. All work
shall comply with API 610, 8th edition for fueling pumps, also API
682, 1st edition Specifications The specifications for the pumps the
seals are to be installed on: Manufacturer: Sulzer Bingham Type: CAP8
Service: Fueling Pumps Pumpage: Jet Fuel (JP8) Capacity: 600 GPM, 3560
RPM Stuffing Box: Mechanical Seal Bearings: Radial Roller, Thrust Ball
Driver: 100 HP Coupling: Type TSCS, Size 0060-0055/5000 This will be a
Performance Price Trade Off acquisition. Award shall be made to the
responsible offeror whose offer conforming to the solicitation will be
most advantageous to the Government, price and other factors
considered. Past performance is approximately equal to price in
importance. This is a 100% small business set aside. The SIC code is
5084 The scope of this project is between $25,000 and $100,000 **The
Government would appreciate any comments or suggestions in regards to
the type of seals and the no leakage requirement, in order to
facilitate the further development of the specifications. A site visit
shall be conducted after solicitation issue. The solicitation issue
date shall be on or about 6 April Posted 03/21/00 (D-SN436509). (0081) Loren Data Corp. http://www.ld.com (SYN# 0199 20000323\43-0002.SOL)
43 - Pumps and Compressors Index Page
|
|