COMMERCE BUSINESS DAILY ISSUE OF MARCH 24,2000 PSA#2564Bid Office, SPAWARSYSCEN, Code D21B, 53570 Silvergate Avenue, Bldg.
A33, Room 0061, San Diego, CA 92152-5112 70 -- UNINTERRUPTIBLE POWER SYSTEM SOL N66001-00-Q-3272 DUE 041200 POC
Purchasing Agent, Ms. Gina Bennett, D212, (619) 553-5208. Alt poc: Ms.
Chris Lewis, D211, (619) 553-7503. This is a combined
synopsis/solicitation prepared in accordance with FAR Part 13. No RFQ
will be prepared or made available for distribution; award will be made
based on responsive, responsible, technically acceptable low bids.
Uniterruptible Power System (UPS), Quantity 1 each. Technical
Specifications: This purchase request is for a new Three Phase
Uninterruptible Power System (UPS) to replace an existing
Emerson/Liebert system. The UPS distributes conditioned power to our
Software Development Laboratories. The critical load is powered by an
inverter, which obtains its power from a battery backup system in the
event of a utility power outage. This system is required to provide
reliable power distribution 24 hours a day, 365 days a year. The new
unit shall be compatible with the existing site infrastructure. The
minimum specifications for this unit are as follows: 1. System
Description: 225kVA / 180kW, 60 Hz, Liebert Series 600T Three Phase
Uninterruptible Power Supply (UPS). Input Voltage, -- 480 VAC, 3 Phase,
3 Wire plus ground. Output Voltage -- 480 VAC, 3 Phase, 3 Wire plus
ground. >= 94 % efficiency at 480 VAC input to 480 VAC output,
calculated as output kW divided by input kW with a .8 P.F. 120kW load,
with standard factory settings to deliver full catalogued performance
including optimal output voltage THD. ETL listed per UL Standard 1778
Uninterruptible Power Supplies and CSA Certified. UL backfeed
protection shall not require interfaces to any external equipment.
Seismic mounted components. NEMA Type I enclosures. Operate as an
on-line reverse transfer system in modes (Normal, Emergency, Recharge,
Bypass, and Off-Battery). All bussbars, wiring and transformers shall
be made of copper. Redundant cooling fans. Redundant integrated logic
circuitry. Redundant logic power supplies. Programmable Two-layer
circuitry limiting input current. Programmable Two-layer circuitry
limiting battery charge current. Internal input thermal magnetic
circuit breaker. Internal output thermal magnetic circuit breaker.
Internal Bypass thermal magnetic circuit breaker. Internal Maintenance
Bypass. Dual Input (rectifier and bypass feed) Automatic Equalize
Charge Timer. Local Emergency Power Off (EPO) with provisions for a
remote E.P.O. Inverter shall be a pulse-width-modulated 6-step design
utilizing IGBT's. Microprocessor based monitoring with large 4" x 6"
LCD display (English). Remote status panel interface compatible with
existing remote display and wiring. Event History File to maintain a
history of alarm conditions accessible by customer. Supplier shall
provide with bid, empirical reliability documentation to support quoted
MTBF calculations with manufacturer's last 7 years of installed UPS
systems of this size and rating. 2. Battery Power Pack System: VRLA
Battery Pack System providing 15 minutes under full load operation
designed and sized for 10-year life values. System shall be future
expandable by including paralleling buss and control wiring in base
cabinet. The battery cells and disconnect breaker shall be installed
and housed in a NEMA Type I enclosures, matching the UPS style and
design, that attaches to the UPS module to form an integral system
Circuit breaker on each cabinet for maintenance isolation. Battery
Cycle Monitor (BCM) to document the cycle service of the batteries. BCM
shall be approved by the battery manufacturer to validate and
substantiate warranty. Battery overcharge protection by temperature
compensated charging by the UPS. 3. Accessories: Input filter with 7%
Input Reflected Total Harmonic Distortion (THD) at full output load.
External Maintenance Bypass Compatible with existing electrical
infrastructure. Remote Alarm Summary Panel -- Mimic UPS Audible and
Visual status indicators with LED test function. 4. Warranty and
Service: 1 year from initial startup against defects in workmanship and
materials. All remedial service shall include parts, labor and travel
expenses and be provided by UPS manufacturer's factory employed
technicians. Emergency 4-hour on site response time during bothnormal
working hours and off-hours. 5. Installation of the UPS to include:
Mandatory pre-bid inspection of the installation space to ensure
compatibility. Bid documents shall provide single lines including UPS
datasheets complete with MTBF reliability documentation, one copy of
installation operation and maintenance manual and warranty documents.
Startup and training to be provided UPS manufacturer's factory
technicians. Install Maintenance Bypass. De-install, remove and dispose
of existing UPS, batteries and remote alarm panel. Remove unused
power/battery wiring conduit, racks and battery breaker box. Install
new UPS. Provide and Connect input and output feeders to required
existing or new distribution. Install and attach battery cabinets with
all required wiring and interfaces. Connect controls and alarms.
Install and connect the Remote Alarm Summary Panel in room 117 (PGC).
Maintain space habitability. Work to start on a SSC SD off-Friday and
be operational within twenty-four hours. 6. Additional Task: Convert an
existing 75 kVA Power Distribution Unit (PDU) currently on street
Power, to an existing Distribution Panel that contains an unused 150
amp circuit breaker. Competitive awards may be based on the evaluation
criteria stipulated in the Red, Yellow, Green (RYG) Contractor
Evaluation System. The evaulation criteria is avaiable upon request.
This document will be posted to the Navy Electronic Commerce Online
(NEC) at www.neco.navy.mil. Interested parties are invited to respond
to this synopsis. Facsimile quotations are acceptable and must be
received on or before the COB on the closing date stated above.
Facsimile quotations may be sent to (619) 553-1062/4464/4842. Questions
may be directed to the Purchasing Agent via e-mail:
gina@spawar.navy.mil. The applicable Standard Industrial Code (SIC)
3577 and Size Standard is 500 employees. Posted 03/22/00 (W-SN437290).